A Decoupled Approach for Modeling N-k Interdiction with Induced Failures in Electric Power Grids

Abstract

The electric power grid is a critical infrastructure system subject to different types of failures which can have devastating impacts on society. One framework to study the resilience of the grid is the N-k interdiction model, which introduces an attacker and defender model to identify grid vulnerabilities. However, traditional N-k interdiction models characterize the power grid with steady-state assumptions. One key aspect missing from this analysis is the behavior of the grid as it evolves from the pre-failure grid state and post-failure grid state. During such a transition period, automated protection systems, transient instabilities, and other phenomena can trigger cascading failures that can occur before grid operators can respond. To bridge this gap, this paper first introduces the generalized induced failure N-k (N-k.k') problem, where an initial set of k failures induces an additional set of k' failures. In this context, we propose a disjoint optimization approach that decouples the computation of cascading failures from the interdiction model. This system response model, furthermore, is treated as a black box module without compromising the underlying performance guarantees of the interdiction model. Extensive experiments on several benchmark power grid case studies showcase the efficacy and scalability of the approach.

Introduction

The electric grid is a critical infrastructure system that consists of an interconnected network of generators, substations, buses, and transmission/distribution lines, which work to supply power to consumers. As power moves through the grid, systems for real-time monitoring and control, including Supervisory Control and Data Acquisition (SCADA) and automated protection systems, are used to help maintain safe operation. However, recent events, e.g., natural disasters and man-made attacks [1], have revealed vulnerabilities in the grid, and their severe consequences on cities and communities.

To ruggedize the grid against such failures, research efforts often focus on identifying the core components (generators and lines) that the grid depends on most. In this context, one framework used is the NN-kk interdiction model, which is based on the zero-sum Stackelberg game [2, 3, 4]. The standard setting considers two opposing players: the attacker who selects kk components in a network of size NN to simultaneously (or

near-simultaneously) fail; and the defender who controls the grid response to minimize the disruption to service caused by the failure. Traditionally, worst-case NN-kk models assume that the electric grid before and after failure is fully characterized by a steady-state model. In practice, these models capture the total amount of load that can be carried through the network while allowing for operator responses, such as generator re-dispatch and transmission switching. However, one key aspect missing from NN-kk interdiction analysis is the trajectory that captures the evolution of the grid from its pre-failure state to its post-failure state. During this transition period, the automated activation of protection systems and transient instabilities may potentially cause additional failures in the network. As a result, there may be no feasible trajectory that allows the grid to reach the desired post-failure state. This can yield steady state analyses that underestimate the disruption of a NN-kk event.

One major challenge lies in incorporating appropriate models to bridge the disconnect between steady-state assumptions and the transient behavior of the grid. This is due to additional non-convexities introduced when directly incorporating these features into traditional optimization-based NN-kk interdiction models. This can cause the interdiction models to become computationally intractable or produce suboptimal solutions. To address this, many emerging methods have looked to capture some aspects of the dynamics. Initial efforts include the NN-1-1 interdiction model, which studies the evolution of the network when two failures occur one after another, with a short, interleaved recovery period [5, 6]. Other work has explored limitations on the degree to which generators can re-dispatch [7], examining failures under shorter timescales [8, 9], and running simulation studies on full grid dynamics [10, 11, 12, 13] for NN-kk events. However, these techniques only begin to tackle the core problem of how to identify the worst-case kk failures for a network, while accounting for both transient dynamics and steady-state constraints.

In this paper, we develops a model that integrates the standard steady-state assumptions on interdiction, and the immediate system behavior following grid failures. We begin by considering an extended NN-kk analysis, which we term the NN-kk-k′k' problem, where the defender model is augmented with a model for the immediate response of the grid. In doing so, the defender becomes responsible for computing how the initial kk failures lead to an additional set of k′k' failures. We then leverage the key insight that this computation for the system response can be decoupled from the optimization problem. This allows us to reduce the complexity of the defender while preserving solution optimality. Moreover, such a response model can be treated as an abstract black box, which enables

Image not extracted

Figure 1.

interoperability with a variety of complex computational models for system response [10, 11]. Our key contributions are:

  • The formulation of the N−k⋅k′N-k\cdot k' problem as a Stackelberg game, where the initial failure of kk components in the grid induces k′k' subsequent failures of other components as part of the immediate automated system response.

  • The development of an approach incorporating arbitrarily complex grid response models for N−k⋅k′N-k\cdot k' analysis without impacting the underlying performance guarantees.

  • The design of a disjoint optimization framework that decouples the immediate system response from the attacker and the defender in the interdiction, enabling an efficient solution for the N−k⋅k′N-k\cdot k' problem. A key novelty of this approach is its interoperability with different response models, which allows for flexibility in capturing dynamics at a desired scale and fidelity.

  • An extensive evaluation of the proposed approach on several benchmark grid case studies, which highlights its utility and scalability in studying grid vulnerabilities.

We organize the paper as follows: § 2 reviews related literature on N−kN-k interdiction models for contingency analysis, and discuss the state of the art in modeling grid dynamics. Section III then presents the preliminary formulation for the electric grid, and describes the standard N−kN-k interdiction model. We define the new N−k⋅k′N-k\cdot k' problem in § 4. Then, in § 5, we present our proposed disjoint approach by constructing it through a progression of steps that build on one another. Our experiments in § 7 validate our model, and Section VII presents conclusions and future directions.

Related Literature

We next review related literature for contingency analysis with N−kN-k interdiction models in power grid systems. We then discuss the realism and scalability provided by different types of models, examine techniques used to capture grid dynamics, and place our paper’s contributions in the broader literature.

On N−kN-k contingency analysis. Studying grid resilience often involves using contingency analysis to identify and evaluate the reliability risks of potential faults [14, 15]. N−kN-k interdiction models provide a framework to study contingencies through a Stackelberg game. Early work by [2] introduced bilevel mathematical models to capture the network interdiction setting for the electric grid. This is used as a basis from which many variants of attacker and defender models have been defined. The realism and the scalability of computation depend on several aspects modeling choices in the interdiction. The standard attacker has full knowledge of the network state and its operation [16, 17, 18]. This conservative assumption allows the attacker to explore worst-case scenarios of grid components to fail in the N−kN-k contingency. However, the power of the attacker to fail certain grid components, such as generators or lines, can vary. While many models allow attackers to disable any component in the grid [18, 19], other efforts have examined different types of constraints to better reflect real-world conditions. Such work has incorporated the probabilistic failure of lines [20], scenarios with ruggedized grid components [21, 22], and spatial limitations for enhanced credibility of attacks [23]. For the defender, models differ in how they represent the grid operator’s capacity to prepare for and respond to failure. This ranges from full observability and control which occurs under normal operating conditions [19, 23], to models that look to include uncertainties stemming from factors such as false data injections [24, 25] and unpredictable demand patterns [26]. The defender model can also consider hardening budgets that proactively protect some grid components from failure, as in [21, 27].

The scalability of these methods provides another central challenge. The N−kN-k interdiction problem is combinatorial and NP-hard [28, 29], so full enumeration is often infeasible beyond small cases. Thus, different modeling assumptions consider how to balance the tradeoff between computational efficiency and accuracy of capturing the underlying complexities of power flow. This includes efforts such as [30, 31], which examine how heuristic bounds on the dual variables of the defender model can be made tighter for the optimization. The role of neural networks in capturing network state [18], and network science-based approaches that exploit spatial and empirical grid behavior patterns during failure [7, 32] have also been explored. A key limitation is the lack of modeling for grid dynamics: many works rely on the steady state network representations. As a result, these models can potentially disregard grid behaviors during or immediately after failures.

Towards capturing grid dynamics. Integrating grid dynamics for this interdiction problem requires models that include a temporal dimension. The N−1−1N-1-1 model studies the state of the network when a single fault is followed by a short recovery period and then a second fault [5, 6]. Extensions have also examined sequential attacks on the grid, where grid components are failed iteratively. This can be due to a sequential attacker [7, 33], or through the modeling of shorter timescales [8], or cascading failures [9]. Finally, a number of power system simulation libraries have also been developed that focus on simulating the full dynamics of the grid, e.g., simulating waveforms and generator operation. Examples of simulations include PowerWorld [10], PowerSimulationsDynamics [11], Moasik [12], and PyPSA [13], among many others. However, a major limitation of these works is their scalability, they can be used to enumerate all N−kN-k interdictions for a given kk. Thus, many case studies are small in scale, and depending on the level of detail used to model the operation of the grid, computationally expensive to run.

Limitations and High-level Approach. This paper addresses these limitations by developing a new methodology to bridge the gap between steady-state models and complex grid dynamics. In particular, a new model is developed that incorporates the immediate, automated system response into the attacker-defender optimization. Notably, our approach decouples the computation of this response from the optimization, this is allowed under certain conditions on the response model. We prove that this decoupling preserves optimality, and show how it enables improved scalability and interoperability with arbitrarily complex dynamics models. Through this design, our work provides an efficient method for conducting worst-case contingency analysis that captures both steady-state constraints and the immediate effects arising from grid dynamics.

SymbolDefinition
G=(N,E)\mathcal{G}=(\mathcal{N},\mathcal{E})Graph of the network
i∈Ni\in\mathcal{N}Set of buses (nodes)
(i,j)∈E(i,j)\in\mathcal{E}Set of branches / lines (edges)
Ef(i)\mathcal{E}^{\mathrm{f}}(i)Set of edges directed from bus ii
Et(i)\mathcal{E}^{\mathrm{t}}(i)Set of edges directed to bus ii
θi\theta_iVoltage phase angle at bus ii
pigp_i^gActive power generated at bus ii
pijp_{ij}Active power flow on branch (i,j)(i,j)
pisp_i^sActive power shed from bus ii
αi\alpha_iGenerator response at generator ii
βi\beta_iLoad shutoff binary variable for loads ii
pidp_i^dPower consumed at ii
pig‾\overline{p_i^g}Maximum power generated at bus ii
bijb_{ij}Inverse of the reactance in branch (i,j)(i,j)
tijt_{ij}Thermal limit of branch (i,j)(i,j)
A\mathcal{A}Attacker Player in the interdiction model
D\mathcal{D}Defender Player in the interdiction model
R\mathcal{R}Response Model
σ(⋅)\sigma(\cdot)Value of variable (⋅)(\cdot) in network state σ\sigma
kkNumber of lines interdicted by the attacker
xijx_{ij}Binary variable for if line (i,j)(i,j) is interdicted
x⃗\vec{x}A vector of binary variables {xij}\{x_{ij}\}
k′k'Number of lines failed in the response model
xij′x'_{ij}Binary variable for if line (i,j)(i,j) fails in R\mathcal{R}
x⃗′\vec{x}'A vector of binary variables {xij′}\{x'_{ij}\}

Table I. Electric Grid Notations

Preliminaries

We present the key notations and concepts to model the structure and operation of the electric grid. We then describe the formulation of the standard NN-kk interdiction model and the primal cut algorithm used for its optimization [31]. For convenience, Table I summarizes the notations used.

The Electric Grid Infrastructure

The electric power grid is a network graph G=(N,E)\mathcal{G}=(\mathcal{N},\mathcal{E}), where nodes are buses, and edges are power lines or branches. The bus nodes, i∈Ni\in\mathcal{N}, are characterized by their voltage phase angle θi\theta_i, which is a measure of the shift in voltage relative to a reference bus in the grid. Nodes are co-located with generators and load demands that represent power production and consumption. A generator can produce up to pig‾\overline{p_i^g} power, while a load demand consumes pidp_i^d power. Each branch, (i,j)∈E(i,j)\in\mathcal{E}, is defined by its thermal power rating tijt_{ij}, which indicates the maximum power it can safely carry; and a quantity representing the inverse of its reactance, bijb_{ij}, which reflects the difficulty of transmitting power.

During operation, the power produced at generators and carried by branches to satisfy load demands determines the state of the grid. Let σ\sigma denote a grid state, consisting of: generator setpoints pigp_i^g, indicating the power output of a generator ii; and power flows pijp_{ij} indicating the power transmitted across branch (i,j)(i,j). We define σ(⋅)\sigma(\cdot) as the value of the variable (⋅)(\cdot) for a state σ\sigma. Power flows are directed: Ef(i)\mathcal{E}^{\mathrm{f}}(i) and Et(i)\mathcal{E}^{\mathrm{t}}(i) denote the sets of edges leaving and entering bus ii, with direction assigned arbitrarily. When load demands cannot be satisfied, e.g., due to inadequate power generation, a grid operator may need to shed load from the system for stability. We use pisp_i^s to denote the amount of power load shed from bus ii.

The Standard NN-kk Interdiction Model

The NN-kk interdiction model analyzes grid vulnerabilities using a two-player game where an attacker A\mathcal{A} aims to fail components to cause the most disruption in the grid, and a defender D\mathcal{D} controls the grid’s response to the failure. This disruption is typically modeled through load shed. For ease of exposition, this work considers only the failure of transmission lines. Extensions for other grid components, e.g., generators, substations, can be obtained from formulations such as in [19] and the NN-kk-k′k' formulation described here can be extended to these formulations. We next present the standard formulations for the attacker and defender, followed by the primal cut algorithm used to identify worst-case failures.

The Standard Attacker Model. The standard attacker A\mathcal{A} in (1) identifies the kk lines whose simultaneous (or near-simultaneous) failure produces the most load shed. Let xijx_{ij} denote a binary indicator variable whose value is 1 if branch (i,j)(i,j) has failed, and 0 otherwise. We use x⃗\vec{x} to represent the vector consisting of the binary indicator variables xijx_{ij} for (i,j)∈E(i,j)\in\mathcal{E}. The attacker’s objective in (1) is to maximize the load shed response from the defender. To do this, the attacker selects kk lines to disable in the grid, as shown through Constraints (2) and (3). Note that the attacker’s choice in x⃗\vec{x} is combinatorial, and thus full enumeration is often intractable.

A(k)=max⁡x⃗ D(x⃗)(1)\mathcal{A}(k)=\max_{\vec{x}}\ \mathcal{D}(\vec{x}) \tag*{(1)}
s.t.∑(i,j)∈Exij=k(2)\begin{aligned} \text{s.t.}\quad&\sum_{(i,j)\in\mathcal{E}}x_{ij}=k \tag*{(2)} \end{aligned}
xij∈{0,1}∀(i,j)∈E(3)x_{ij}\in\{0,1\}\qquad\forall(i,j)\in\mathcal{E} \tag*{(3)}

The Standard Defender Model. The defender D\mathcal{D} in (2) controls the grid response to failures, and maximizes the power load that can be safely served to consumers. The defender’s objective is expressed in (4) as a minimization of the total load shed across all nodes, given the failures x⃗\vec{x}. We then introduce x⃗′\vec{x}' as a vector equal to x⃗\vec{x} in (5). While this is a redundant constraint, it will be useful for later formulations. The constraints in (6) and (7) are used to capture physical limitations on branches and generators, i.e., power flows on branches cannot violate their thermal ratings, and generators cannot exceed their maximum generation. We use (8) to limit the load shed per node. The defender is also constrained by physical laws that govern power flows: Kirchhoff’s law ensures the balance of power flows for each bus in the grid, while Ohm’s Law relates power flows to voltage phase angles differences for each branch. This is shown in (9) and (10). We assume that DC linear approximations are applied for modeling the grid network, similar to the models in [19], [23], which approximates AC power with linearized DC power.

D(x⃗)=min⁡∑i∈Npis(4)\mathcal{D}(\vec{x})=\min\sum_{i\in\mathcal{N}}p_i^s \tag*{(4)}
x⃗^=x⃗(5)\hat{\vec{x}}=\vec{x} \tag*{(5)}
−tij(1−x^ij)≤pij≤tij(1−x^ij)∀(i,j)∈E(6)-t_{ij}(1-\hat{x}_{ij})\leq p_{ij}\leq t_{ij}(1-\hat{x}_{ij})\qquad\forall(i,j)\in\mathcal{E} \tag*{(6)}
0≤pig≤pig‾∀i∈N(7)0\leq p_i^g\leq\overline{p_i^g}\qquad\forall i\in\mathcal{N} \tag*{(7)}
0≤pis≤pid∀i∈N(8)0\leq p_i^s\leq p_i^d\qquad\forall i\in\mathcal{N} \tag*{(8)}
pid−pig+pis=∑(i,j)∈Ef(i)pij−∑(i,j)∈Et(i)pji∀i∈N(9)p_i^d-p_i^g+p_i^s=\sum_{(i,j)\in\mathcal{E}^{\mathrm{f}}(i)}p_{ij}-\sum_{(i,j)\in\mathcal{E}^{\mathrm{t}}(i)}p_{ji}\qquad\forall i\in\mathcal{N} \tag*{(9)}
pij=bij(θi−θj)(1−x^ij)∀(i,j)∈E(10)p_{ij}=b_{ij}(\theta_i-\theta_j)(1-\hat{x}_{ij})\qquad\forall(i,j)\in\mathcal{E} \tag*{(10)}

The Primal Cut Algorithm. The attacker AA and defender DD are optimized through the primal cut algorithm. This algorithm optimizes the attacker and defender in two alternating steps: (i) the attacker selects x⃗\vec{x} representing the kk lines to fail; and (ii) the defender re-dispatches generators, re-routes power flows, and sheds loads as necessary to continue serving load demands in the network. These steps are repeated iteratively until convergence is reached. At the end of each iteration, the total load shed (computed by the defender) is provided back to the attacker. The primal cut algorithm accomplishes these steps by constructing cutting planes consisting of linear functions, with the goal of defining an upper bound on the total load that was shed by the defender. We adopt the heuristic version discussed in [31] to form a cutting plane using coefficients computed for each branch. The approach developed in this paper also applies to the exact method discussed in [31], albeit with slower convergence to global optimality.

Algorithm 1: Primal Cut Optimization

Input: int kk, tolerance ϵ\epsilon, Grid G=(N,E)\mathcal{G} = (\mathcal{N}, \mathcal{E}) Output: Optimal Attack x⃗∗\vec{x}^{*}, Load shed plbsp_{lb}^{s}

  1. A←InitializeAttackerModel()\mathcal{A} \leftarrow\mathrm{InitializeAttackerModel}()

  2. plbs←0p_{lb}^{s} \leftarrow0; pubs←∞p_{ub}^{s} \leftarrow\infty;

  3. x⃗←InitializeAttack()\vec{x} \leftarrow\mathrm{InitializeAttack}()

  4. x⃗∗←x⃗\vec{x}^{*} \leftarrow\vec{x}

  5. while pubs−plbs≥ϵplbsp_{ub}^{s} - p_{lb}^{s} \ge\epsilon p_{lb}^{s} do

  6. D←InitializeDefenderModel()\qquad\mathcal{D} \leftarrow\mathrm{InitializeDefenderModel}()

  7. pDs,σD←Optimize D(x⃗)\qquad p_{D}^{s}, \sigma_{D} \leftarrow\mathrm{Optimize}\ \mathcal{D}(\vec{x})

  8. \qquad if plbs<pDsp_{lb}^{s} < p_{D}^{s} then plbs←pDsp_{lb}^{s} \leftarrow p_{D}^{s}; x⃗∗←x⃗\vec{x}^{*} \leftarrow\vec{x};

  9. cut←MakeConstraint:pubs≤pDs+∑(i,j)∈EσD(pij)xij\qquad\mathrm{cut} \leftarrow\mathrm{MakeConstraint}: p_{ub}^{s} \le p_{D}^{s} + \sum_{(i,j)\in\mathcal{E}} \sigma^{D}(p_{ij})x_{ij}

  10. A.addConstraint(cut)\qquad\mathcal{A}.\mathrm{addConstraint}(\mathrm{cut})

  11. pubs,x⃗←Optimize A(k)\qquad p_{ub}^{s}, \vec{x} \leftarrow\mathrm{Optimize}\ \mathcal{A}(k)

  12. return x⃗∗,plbs\vec{x}^{*}, p_{lb}^{s}

Algorithm 1 describes the primal cut optimization algorithm. It starts by initializing the attacker model A\mathcal{A}, the lower and upper bounds on load shed, and the initial attack consisting of kk random lines (lines 1-3). The best attack found is denoted by x⃗∗\vec{x}^{*} (line 4). The defender model is then executed on x⃗\vec{x}, and the best lower bound on the load shed is cached. This occurs until convergence, which occurs when the upper and lower bounds on load shed are within a tolerance, ϵ\epsilon, of each other (line 5-8). We then construct the cutting plane, and add it as a constraint to the attacker model (lines 9-10). The attacker model is optimized to find an upper bound on the load shed (line 11). The optimal attack and load shed are returned once the algorithm converges (line 12).

The NN-kk-k′k' Interdiction Problem

One key limitation of the standard NN-kk interdiction model is the lack of modeling for the behavior of the grid during and immediately after failures occur. That is, the standard model implicitly assumes that the grid transitions directly from its pre-failure state to the computed post-failure steady state. In practice, however, the grid’s immediate response is governed by physical laws and automated local controls, which can cause additional components to fail or trip. The NN-kk-k′k' problem addresses this gap by extending the NN-kk framework with a model for the immediate response model accounts for how the initial kk failures can trigger an additional k′k' failures in the network.

Diagram of the $N$-$k$-$k'$ interdiction model

Figure 1 (PDF p. 4). The NN-kk-k′k' Interdiction Model

Next, we define the NN-kk-k′k' problem. Initially, we assume that the grid operates at full capacity, and that all loads in the network are satisfied. After some time, kk transmission lines in the grid simultaneously (or near simultaneously) fail. As a result, the network state shifts, which causes k′k' additional lines to subsequently fail, e.g., due to the activation of protection systems. The grid operator then applies grid control actions on the joint k⋅k′k \cdot k' failures to determine the next steady state for the network. In this context, the NN-kk-k′k' problem identifies the set of kk failures that leads to the highest disruption in the grid, measured by the load shed response to the k⋅k′k \cdot k' failure. We let x⃗\vec{x} and x⃗′\vec{x}' denote the vectors of binary variables xijx_{ij} and xij′x'_{ij}, where xijx_{ij} is 1 if branch (i,j)(i,j) is among the initial kk failures and xij′x'_{ij} is 1 if branch (i,j)(i,j) fails during the immediate automated response. In Figure 1, we illustrate the NN-kk-k′k' problem setting. In the following section, we present our disjoint optimization framework that solves this problem by decoupling the response computation from the attacker-defender optimization.

Solution Technique

This section details our disjoint approach to solve the NN-kk-k′k' problem. We present this approach through a progression of models, starting with an integrated formulation that directly incorporates the response model into the defender. While mathematically correct, this integrated approach introduces significant computational load that makes it difficult to scale to larger grid networks. We then show that this computation can be decoupled in the NN-kk-k′k' analysis without impacting the underlying optimality and convergence properties of the original problem. This decoupling enables an efficient, scalable solution that is also interoperable with complex response.

An integrated model for grid response after failure

For illustration, consider an overly simplified model that extends the NN-kk analysis to capture the immediate grid response after failures. This model examines the impact of re-routed power flows and generator responses if the x⃗\vec{x} failures isolate grid components into islands. Let the defender in this interdiction model be augmented to include a formulation for the additional lines x⃗′\vec{x}' (i.e., immediate response failures) that trip as a result of x⃗\vec{x}. For this simple example, we assume that these additional failures occur when power flows on lines exceed their thermal ratings. This new defender model is presented in (3) below.

D(x⃗)=min⁡∑i∈Npis(11)\mathcal{D}(\vec{x}) = \min\sum_{i \in\mathcal{N}} p_i^s \tag*{(11)}
s.t.(2c),(2d),(2e),(2f),(2g)(12)\begin{aligned} \text{s.t.}\quad&(2c), (2d), (2e), (2f), (2g) \tag*{(12)} \end{aligned}
x⃗^=x⃗+x⃗′(13)\hat{\vec{x}} = \vec{x} + \vec{x}' \tag*{(13)}
p~ig=ϕig+αi∀i∈N(14)\tilde{p}_i^g = \phi_i^g + \alpha_i \qquad\forall i \in\mathcal{N} \tag*{(14)}
αi(1−xij)=αj(1−xij)∀(i,j)∈E(15)\alpha_i(1-x_{ij}) = \alpha_j(1-x_{ij}) \qquad\forall(i,j) \in\mathcal{E} \tag*{(15)}
xij′≤∣p~ij∣tij∀(i,j)∈E(16)x'_{ij} \leq\frac{|\tilde{p}_{ij}|}{t_{ij}} \qquad\forall(i,j) \in\mathcal{E} \tag*{(16)}
Mxij′≥∣p~ij∣−tij∀(i,j)∈E(17)M x'_{ij} \geq|\tilde{p}_{ij}| - t_{ij} \qquad\forall(i,j) \in\mathcal{E} \tag*{(17)}
xij+xij′≤1∀(i,j)∈E(18)x_{ij} + x'_{ij} \leq1 \qquad\forall(i,j) \in\mathcal{E} \tag*{(18)}
0≤xij′≤1∀(i,j)∈E(19)0 \leq x'_{ij} \leq1 \qquad\forall(i,j) \in\mathcal{E} \tag*{(19)}
p~ig−pid=∑(i,j)∈Ef(i)p~ij−∑(j,i)∈Et(i)p~ji∀i∈N(20)\tilde{p}_i^g - p_i^d = \sum_{(i,j)\in E^f(i)} \tilde{p}_{ij} - \sum_{(j,i)\in E^t(i)} \tilde{p}_{ji} \qquad\forall i \in\mathcal{N} \tag*{(20)}
p~ij=bij(θi−θj)(1−xij)∀(i,j)∈E(21)\tilde{p}_{ij} = b_{ij}(\theta_i-\theta_j)(1-x_{ij}) \qquad\forall(i,j) \in\mathcal{E} \tag*{(21)}

The new defender model keeps the standard defender’s objective and most of its constraints in (3a) and (3b). One key difference is that the failures x⃗^\hat{\vec{x}} are now set to x⃗+x⃗′\vec{x}+\vec{x}' in (3c). In doing so, the defender will take control actions to minimize the disruption with respect to the combined failure.

Physical laws in the grid dictate that the system stays in balance, with generators instantaneously adjusting their production in response to imbalances – in this case, when x⃗\vec{x} separates the network into two or more pieces (islands). This is sometimes referred to as droop or frequency response. If an island experiences a significant mismatch between generation and load, the resulting frequency deviations can trigger protective systems and cause other component failures beyond those in x⃗\vec{x}. To model droop, we introduce a generator response variable αi\alpha_i, and assign the next setpoint for each generator in (3d). Here, p~ig\tilde{p}_i^g is a generator setpoint variable used during the immediate automated response, and ϕig\phi_i^g is a constant denoting the generator setpoint prior to x⃗\vec{x} failing. We enforce a uniform droop response within each island formed after the initial failures x⃗\vec{x} by requiring that αi=αj\alpha_i=\alpha_j for edges (i,j)(i,j) that have not failed, in (3e). While this is an oversimplified model of droop control, we note that even this model introduces computational complexity to the defender model that is only exacerbated for more sophistical models of droop response.

Finally, as mentioned earlier, power flows on branches that have not failed may potentially exceed their thermal rating and trip. Similar to above, we introduce p~ij\tilde{p}_{ij} as the power flow variable during the immediate automated response. To model the tripping of overloaded lines, we use (3f) and (3g) to assign xij′x'_{ij} based on whether the power flow magnitude exceeds the thermal rating. When ∣p~ij∣≤tij|\tilde{p}_{ij}| \leq t_{ij}, the constraint in (3f) requires xij′x'_{ij} to be 0. Conversely, when ∣p~ij∣>tij|\tilde{p}_{ij}| > t_{ij}, the constraint in (3g) requires xij′x'_{ij} to be 1. In each case, only one constraint actively restricts xij′x'_{ij}; the other becomes redundant and is automatically satisfied.1 We use (3h) and (3i) to define bounds for xijx_{ij} and ensure that at most one of xijx_{ij} and xij′x'_{ij} equals 1 across all branches. Finally, during the immediate automated response, power flows and generation in the grid still follows laws of physics; however, load cannot be shed at this timescale. These laws are expressed in (3j) and (3k).

Decoupling the response computation from steady-state optimization

While the integrated model in (3) captures the immediate automated response following the initial failures x⃗\vec{x}, it greatly increases the computational complexity of the defender by coupling x⃗\vec{x} and x⃗′\vec{x}'. As a result, when more realistic and/or complex response models are used, e.g., those that use more detailed models of droop or details of grid dynamics (modeled with partial differential equations (PDEs)), they can introduce additional non-convexities to the defender optimization model. This can compromise the computational efficiency, convergence, and optimality guarantees of the primal cut algorithm.

However, we observe the following key insight, that the primal cuts generated in Algorithm 1 are constructed entirely in the space of x⃗\vec{x} and based on the formulation of the standard defender in (2). This allows the computation of x⃗′\vec{x}' to be pulled out of the defender problem. Hence, the immediate automated system response can be captured by computing x⃗′\vec{x}' separately, and passing the combined failures x⃗+x⃗′\vec{x}+\vec{x}' into the standard defender model D\mathcal{D}. This yields the construction of a defender model that operates on the combined failures x⃗+x⃗′\vec{x}+\vec{x}' and produces the same cut coefficients for the primal cut algorithm.

We next present a new attacker and response model that implements this insight in (4). This formulation will be integrated with Algorithm 1, where the response model R\mathcal{R} is invoked during each iteration to compute x⃗′\vec{x}' before evaluating the defender. That is, the attacker continues to select exactly kk initial lines, and the defender is now evaluated on the combined failures x⃗+x⃗′\vec{x}+\vec{x}', as expressed in (4a). Note that these combined failures are passed to the defender, which models how x⃗^\hat{\vec{x}} is set in (3c). The response model R\mathcal{R} computes the additional failures x⃗′\vec{x}' in (4c).

A(k)=max⁡x⃗D(x⃗+x⃗′)(22)\mathcal{A}(k) = \max_{\vec{x}} \mathcal{D}(\vec{x}+\vec{x}') \tag*{(22)}
s.t.∑(i,j)∈Exij=k(23)\text{s.t.}\quad\sum_{(i,j)\in\mathcal{E}} x_{ij}=k \tag*{(23)}
x⃗′=R(x⃗)(24)\vec{x}' = \mathcal{R}(\vec{x}) \tag*{(24)}

One implementation for the response model R\mathcal{R} that reformulates the integrated model is provided in Algorithm 2. Given the grid G\mathcal{G} and a set of failures x⃗\vec{x}, we start by constructing G∗\mathcal{G}^*, the post-failure system consisting of nodes N\mathcal{N} and edges that have not failed (line 1). As mentioned earlier, this can potentially create islands in the grid. x⃗′\vec{x}' is also initialized to the empty set (line 2). For each island Gisl\mathcal{G}_{isl} in the graph G∗\mathcal{G}^*, we explicitly compute α\alpha, its constant generator response. This algorithmically models the constraints stated in (3d) and (3e). The new generator setpoints for the grid network are then computed as a function of the previous network state (lines 5–7). The response model then solves for the power flow on lines (line 8), which internally must satisfy the constraints stated in (3j) and (3k). To determine the k′k' failures that are in x⃗′\vec{x}', we filter the branches in the network whose power flows pijp_{ij} exceed their thermal rating limits tijt_{ij} (lines 9–10). This captures the constraints stated in (3f) and (3g). The algorithm lastly returns x⃗′\vec{x}' as the set of additional failures (line 11).

Note that while Algorithm 2 implements the response logic from our integrated model, the decoupled framework allows for much more general response models. In particular,

Algorithm 2: Decoupled Response Model
Input: Graph $\mathcal{G}=(\mathcal{N},\mathcal{E})$, Previous State $\sigma^{prev}$, Lines $\vec{x}$
Output: Response Model impact $\vec{x}^{\prime}$
1 $\mathcal{G}^{*}\leftarrow DisableComponents(\vec{x},\mathcal{G})$
2 $\vec{x}^{\prime}\leftarrow\emptyset$
// Go through each island in $\mathcal{G}^{*}$
3 for $\mathcal{G}^{isl}\leftarrow ComputeIslands(\mathcal{G}^{*})$ do
4   if $\mathcal{N}^{isl}\ne\emptyset$ then
      // Find new setpoints for generators from $\sigma^{prev}$
5     $\alpha\leftarrow\sum_{i\in\mathcal{N}^{isl}}(p_i^d-p_i^g)/|\mathcal{N}^{isl}|$
6     $new\_gen\_setpoints\leftarrow map()$
7     for $i\in\mathcal{N}$ do
        $new\_gen\_setpoints[i]\leftarrow\sigma^{prev}(p_i^g)+\alpha_i$;
// Determine failures within component
8       $\sigma\leftarrow solve\_pf(\mathcal{G}^{isl},generator\_setpoints=new\_gen\_setpoints)$
9       for $(i,j)\leftarrow\mathcal{E}^{isl}$ do
10        if $|\sigma(p_{ij})|>t_{ij}$ then $\vec{x}^{\prime}\leftarrow\vec{x}^{\prime}\cup\{(i,j)\}$;
11 return $\vec{x}^{\prime}$

this decoupled response model operates as a black-box for computing x⃗′\vec{x}^{\prime} while preserving the original guarantees of the algorithm. As long as R\mathcal{R} produces a mapping from x⃗\vec{x} to x⃗′\vec{x}^{\prime} and operates independently of the defender’s steady-state optimization, any arbitrarily complex response model can be employed by replacing lines 1-10 with an arbitrary response model, such as a transient simulation. This leads to the full NN-k⋅k′k\cdot k^{\prime} model as formalized in Algorithm 3.

Algorithm 3: Evaluating the $N$-$k\cdot k^{\prime}$ Model
Input: Graph $\mathcal{G}=(\mathcal{N},\mathcal{E})$, Previous State $\sigma^{prev}$, int $k$
Output: Worst-case failure event $(p^s,\vec{x}+\vec{x}^{\prime})$
1 $\vec{x}\leftarrow A(k)$
2 $\vec{x}^{\prime}\leftarrow\mathcal{R}(\vec{x})$
3 $p^s\leftarrow D(\vec{x}+\vec{x}^{\prime})$
4 return $(p^s,\vec{x}+\vec{x}^{\prime})$

Theoretical Evaluation

We next show that the decoupling above does not alter the underlying optimization model. We present this through the lemma below, and then state several remarks.

Lemma. Assume that the response model R\mathcal{R} computes x⃗′\vec{x}^{\prime} as a function of only x⃗\vec{x}, and that the defender model D(x⃗)\mathcal{D}(\vec{x}) is deterministic. Then, for any given x⃗\vec{x}, if CC denotes the cut coefficients generated by a deterministic optimization model, the same cut can be subsequently generated when that optimization is treated as a black box.

Proof. Let D1\mathcal{D}_1 and D2\mathcal{D}_2 denote two constructions of the defender model considering the response model R\mathcal{R}. The first defender model D1\mathcal{D}_1 is integrated with R\mathcal{R}; it is given x⃗\vec{x} as input, and must compute both x⃗′\vec{x}^{\prime} and the next grid state. The second defender model D2\mathcal{D}_2 is decoupled from R\mathcal{R}; it is given the combined failure x⃗+x⃗′\vec{x}+\vec{x}^{\prime} as input, and then determines the next grid state. Let C1C_1 and C2C_2 denote the cuts that are generated by each defender model D1\mathcal{D}_1 and D2\mathcal{D}_2, respectively. Since R\mathcal{R} computes x⃗′\vec{x}^{\prime} from x⃗\vec{x} deterministically, the value of x⃗′\vec{x}^{\prime} in D1\mathcal{D}_1 is fixed and enters the model only through the combined failure x⃗+x⃗′\vec{x}+\vec{x}^{\prime}. This input is what is provided to D2\mathcal{D}_2. Thus, it follows that the two constructions share the same parameters, the same feasible set, and the same objective, and therefore represent the same defender problem.

Let S∗S^{*} denote the set of grid states that minimize the total load shed for this problem, which is common to both defender models. As discussed in [31], the coefficients of the cuts C1C_1 and C2C_2 are determined by σ(pij)\sigma(p_{ij}), the power flows on each branch (i,j)(i,j) in the state of the grid computed by the defender. Let σ1\sigma^{1} denote the grid state computed by D1\mathcal{D}_1, so that the coefficients of C1C_1 are those induced by the power flows in σ1\sigma^{1}. By definition, the objective of the defender is to minimize the load shed in the grid network, and since D1\mathcal{D}_1 is solved to global optimality, σ1\sigma^{1} belongs to S∗S^{*}. The state σ1\sigma^{1} is then an optimal solution of the problem solved by D2\mathcal{D}_2 as well. Consequently, D2\mathcal{D}_2, when solved to global optimality is also able to return σ1\sigma^{1}, and the cut it generates from that state has the same coefficients as C1C_1. Therefore, the cut coefficients generated by a deterministic optimization model can be produced even when the model is treated as a black box.

There are two major consequences of this lemma. First, we note that when the response model is unique and deterministic, then the two methods will produce the same solution. This is because the two constructions will match at each iteration of the cutting plane algorithm. Second, when the response model can yield a non-unique solution, e.g., due to internal stochasticity in the optimizer or solution degeneracy, the two approaches are equivalent at the formulation level. This behavior is common across any two solvers that are applied to a problem with non-unique solutions, e.g., a MIP solver on a problem formulation with multiple optimal solution.

Experiments

We next present the evaluation of the decoupled approach on several benchmark power grid networks of varying scales. Details of each network and our experimental setup is provided in Section VI-A. Our experiments first measure the performance of the decoupled approach and validate the impact of capturing the immediate response for the interdiction analysis (Section VI-B). We then study the selection of components failed across the NN-k⋅k′k\cdot k^{\prime} models, and how it affects the operating margin left on the surviving network (Section VI-C). Lastly, we explore the interoperability of our model with other more complex response models (Section VI-E).

Experimental Setup

Our evaluation considers several benchmark power grid case studies from the PGLib-OPF v23.07 library [34]. Table II presents basic information about each network, operated under typical conditions (the base case benchmarks as originally specified), and under heavy load (API cases). All networks report power in the MW base. We initialize each network to the steady state determined by the DC optimal power flow (DC-OPF) for the system. Our experiments are conducted on a M1 Macbook Pro with 16 GB of memory and 10 CPU cores. The code was implemented in Julia using JuMP [35] and PowerModels [36]. We also used the Gurobi optimization solver v12.0.2 [37], with a 1% optimality tolerance and 30 minute timeout. The implementations of each model are published on GitHub [38].

Case Study#Buses#LinesTotal Load (MW)Total API Load (MW)
case14_ieee1420259.0463.0
case24_ieee_rts24382850.05470.4
case30_ieee3041283.4471.2
case39_epri39466254.210093.5
case73_ieee_rts731208550.016416.4
case89_pegase892105727.96786.8
case118_ieee1181864242.06874.8
case162_ieee_dtc1622847239.17647.8
case179_goc17926330326.671840.9
case197_snem1972861474.12620.8
case200_activ2002451475.72456.4
case240_pserc240448144179.7180688.5
case300_ieee30041123525.926426.7
case500_goc50072817772.927536.9
case588_sdet58868610661.114157.3
case793_goc79391313198.318542.1
case3022_goc3022413557997.568545.7
case4661_sdet4661599788203.6104714.0

Table 2. Electric Power Grid Case Studies

Performance of the decoupled attacker-response-defender model

We first explore the performance of the decoupled attacker-response-defender model by measuring its load shed response and computation time across an increasing number of failures.

Load shed response

Figure 2 shows heatmaps of the load shed response for failures ranging from k=1k=1 to 88. For ease of comparison, color is used to indicate the proportion of load shed response for combinations of network and failure size kk.

Figure 2. Load shed (MW) across the standard NN-kk, and the decoupled/integrated NN-k⋅k′k\cdot k' models for multiple networks of varying scale and on number of failures. Darker colors indicate higher load shed for the system. Both NN-k⋅k′k\cdot k' models identify failures that cause larger load shed than the standard NN-kk model, and the two agree closely with each other. (a)-(c) show results for regular cases, and (d)-(f) show results for the API cases. Gray cells mark runs that did not finish within the time limit.

size kk. We observe that the load shed typically increases with kk, and that the NN-k⋅k′k\cdot k' interdiction models find a disruption at least as large as the standard NN-kk model. Under typical operating conditions, the load shed identified by the decoupled NN-k⋅k′k\cdot k' model was on average 60.8% larger than the standard NN-kk model, while for the API cases, it was an average of 135.6% larger. This gap is widest at small values of kk, where the standard model has fewer choices of failures: at k=1k=1 the mean increase is 161.5% for the normal operation cases and 423.3% for the API cases, and it narrows monotonically to 24.6% and 54.6% at k=8k=8. This difference comes as a result of the lines failed during the initial choice of failures (kk) and its impact (k′k'), which is explored further in § 7-C.

We additionally observe that the integrated and decoupled NN-k⋅k′k\cdot k' models generally produce the same solution on most instances, with discrepancies arising when branch flows are within solver tolerances of their thermal limits. Since this threshold determines whether a line trips during the response model, the induced set x⃗′\vec{x}' can differ slightly, affecting the total load shed. While these effects can be mitigated by tightening tolerances, they will differ from one case study to another; the selection of the correct floating point tolerance is out of the scope of this paper. Together, this motivates the need to study the expanded NN-k⋅k′k\cdot k' model for grid resilience.

Computation time

We next measure the end-to-end computation time taken for one complete run to identify worst-case failures in each network. Figure 3 shows a boxplot of the average time taken by each model across an increasing number of failures from 1 to 8. The reported numbers are normalized by the number of bus nodes in the network. In general, as the value of kk increases, each model takes longer to execute. For the regular cases, the mean normalized runtime grows from 9.3, 18.1, and 210.8 ms at k=1k = 1 to 92.6, 122.8, and 929.7 ms at k=8k = 8 for the standard, decoupled, and integrated models, respectively. This indicates that the cost of the standard and decoupled models are comparable, while the integrated model is significantly more expensive; this causes the integrated model to begin timing out once the network size and number of failures grows. In particular, our empirical results show that the integrated model fails to solve cases larger than 300 buses within the time limit. The results translate to the API cases in a similar manner. Overall, this shows the efficiency and scalability of the proposed decoupled approach.

Figure 3. Box plot on the computational runtime, normalized by bus count, as a function of kk across all cases. At each kk, the three boxes are the spread of the normalized runtime. This shows how the decoupled NN-kk-k′k' model is more computationally efficient than the integrated NN-kk-k′k' model.

Selection of Failed Components across the NN-kk-k′k' Models

Our next experiment explores how the choice in the kk lines failed differs between the standard NN-kk model and the decoupled NN-kk-k′k' model. Figure 4a depicts a heatmap where cells are colored based on the proportion of the kk failures selected in the standard NN-kk model that are also selected in the NN-kk-k′k' model. Figure 4b then presents the fraction of lines selected in the standard NN-kk model that lie in either the kk or k′k' failures in the NN-kk-k′k' model. We observe that the choice of the initial kk failures differs across the standard NN-kk model and decoupled NN-kk-k′k' models, for multiple sizes of network and number of failures. On average, only 49.6% of the standard model’s kk targets are also selected by the

Figure 4. Overlap between the failures selected by the standard NN-kk and decoupled NN-kk-k′k' model. (a) Fraction of the standard model’s kk failures also chosen among the decoupled model’s kk failures; (b) Fraction contained in its combined k+k′k+k' failures. Darker colors indicate greater overlap.

decoupled model on the regular cases, and 45.5% on the API cases; the two models select entirely disjoint target sets in 22% and 17% of instances, and agree completely in only 19% and 10%. However, after considering the induced failures, this gap becomes larger: only 63.2% (regular) and 64.1% (API) of the standard model’s targets fall somewhere in the decoupled model’s combined k+k′k+k' failure, which is fully containing in 38% and 33% of instances. Together, these results demonstrate that considering the k′k' failures changes the initial failure, and help to further motivate the need for the NN-kk-k′k' model. In some cases, the failure selected by the standard NN-kk model is part of the k′k' failures identified in the NN-kk-k′k' model, while in others, a completely different, larger disruption was found by considering k+k′k+k'.

Figure 5 shows an illustrative example of this difference for the Case 240 PSERC benchmark grid at k=3k=3, the smallest budget at which the two models select different failures. In particular, both models share two failed lines, but differ on the third: the selection by the standard NN-kk model sheds 20,933 MW (14.5% of system load), while the selection by the NN-kk-k′k' model sheds 36,228 MW (25.1% of system load). This load shed is visualized as larger circles in the figure.

Figure 5. The k=3k=3 failure on Case 240 PSERC. The left graph shows failures from the standard NN-kk model: kk targets are in blue while the k′k' failures it does not account for are in cyan. The right graph shows failures from the decoupled NN-kk-k′k' model: kk failures are in red, and induced k′k' failures are in orange. Circles at nodes represents the amount of load shed.

Examining Network Congestion after Failures

Our next experiment examines the state of the network that remains after failures and its load shed. For kk from 1 to 15, we fail the lines selected by the standard NN-kk model (kk lines) and by the decoupled NN-kk-k′k' model (k+k′k+k' lines), and report the utilization of each surviving line, i.e., its power flow as a fraction of its thermal rating. The failed lines are excluded from this average, since they carry no flow and would otherwise be counted as uncongested. Figure 6 shows the average line utilization across the case studies as kk grows, with the fully operational network plotted at k=0k=0. Before failure, the benchmark networks are loaded to an average of 27.2% of their thermal ratings under typical conditions and 33.8% under heavy load; individual networks range from 10.1% to 46.5% and from 16.8% to 54.9%, respectively. As kk grows, the utilization of the network falls: at k=15k=15, the average utilization of the surviving lines is 19.9% for the standard NN-kk model against 16.3% for the decoupled NN-kk-k′k' model on the regular cases, and 22.0% against 19.0% on the API cases. This decline is faster under the NN-kk-k′k' model because it sheds more load at the same budget: to cause the load shed that the NN-kk-k′k' model causes at kk, the standard model requires a budget larger by an average of 1.2 on the regular cases and 2.6 on the API cases. Overall, this shows that the k′k' response shapes which components fail and how much load is lost, as well as the operating envelope of the remaining network.

Figure 6. Mean congestion in the network after kk or k+k′k+k' failures. Utilization of the network falls as kk grows; this occurs with smaller kk in the NN-kk-k′k' model than the standard NN-kk model.

Utilizing more complex response models

One of the contributions of the decoupling is its interoperability with other, more complex methods for computing the k′k' failures. Our next experiment demonstrates one such example using PowerSimulationDynamics [11], a simulator capturing power system dynamics for a grid network, to compute the failures x⃗′\vec{x}' caused by an initial failure x⃗\vec{x}. The standard defender is then evaluated for the x⃗+x⃗′\vec{x}+\vec{x}' combined failures. We assume that initial lines that are failed cannot disconnect the network (this is a limitation imposed by the simulation library). In our

implementation, when an attack would island the network, we add a no-good cut to the attacker's set of constraints to exclude that x⃗\vec{x}. However, we note that this limitation prevents values of kk greater than 2 from being sufficiently explored. This experiment is also only conducted on modified Case 240 system that includes additional parameters for dynamic generator and inverter devices that are necessary for modeling the dynamics (PDEs).

Table III reports the load shed, run time, and number of iterations taken to converge to a solution using the two different response models. Our results show that the simulation-based response yields higher load shed with a larger number of lines that fail during the immediate automated system response. This is seen for both k=1k=1 and k=2k=2. However, this comes at the cost of a largely increased runtime, since attacks that island the network are disallowed. Another interesting observation is that the run time and number of iterations also become less correlated; many iterations may be spent cutting off infeasible choices of x⃗\vec{x} without evaluating the defender model. These results indicate that by simulating the transience of the network in more detail, it is possible to find larger, different sets of k′k' failures. This highlights a key result of our paper: the decoupled approach enables interoperability with arbitrarily complex response models while preserving the optimality guarantees of the attacker-defender optimization. In practice, this allows flexibility in studying and capturing realistic grid failures.

kkLoad Shed (p.u.)Runtime (s)Iterations
1Algorithm 2381.662.8944
1Ref [11]431.29106.9533
2Algorithm 2387.77245.2111325
2Ref [11]439.386558.699814

Table III. Results from Simulation-based Response Model

Conclusions and Future Directions

In this paper, we presented a decoupled approach for worst-case contingency analysis that extends the standard NN-kk interdiction framework to an NN-k⋅k′k\cdot k' setting by explicitly modeling the grid’s immediate response. Our key insight is that, because primal cuts are constructed entirely in the space of the initial set of failures x⃗\vec{x}, the computation of induced failures x⃗′\vec{x}' can be pulled out of the defender and treated as a deterministic black box, all without altering cut construction or compromising optimality. We formalized this insight and integrated it into a primal cut algorithm, which enables efficient evaluation of the attacker, defender, and the response model in between. We also showed that the defender operating on the combined failures x⃗+x⃗′\vec{x}+\vec{x}' produces the same cut coefficients as the integrated model. Our experiments show that across benchmark networks, accounting for induced failures substantially increases identified worst-case load shed relative to the standard NN-kk model. However, the decoupled formulation scales more reliably than an integrated alternative. We further demonstrated interoperability by substituting a high-fidelity dynamics simulator as the response module, which revealed larger induced failures (and higher load shed). Future work will examine interdependencies and apply such analysis to other related infrastructures such as transportation and water. We also plan to study the impacts of different geocorrelated disaster settings, and analyze the potential failures they cause for the electric grid.

Acknowledgments

This research was supported by the UC National Lab Fees Research Program Grant No. L22GF4561, and NSF Grants No. 1952247 and 2420846. The work was also partially funded by Los Alamos National Laboratory’s Directed Research and Development project, “Artificial Intelligence for Mission (ArtIMis)” and the U.S. Department of Energy Office of Electricity Project “North American Energy Resilience Model” under U.S. DOE Contract No. DE-AC52-06NA25396. The authors would like to acknowledge Manuel Garcia from the Los Alamos National Laboratory for his participation and contributions in discussions.

References

  1. [1]E. B. Watson and A. H. Etemadi, “Modeling electrical grid resilience under hurricane wind conditions with increased solar and wind power generation,” IEEE TPWRS, vol. 35, no. 2, pp. 929–937, 2019.DOI
  2. [2]J. Salmeron, K. Wood, and R. Baldick, “Analysis of electric grid security under terrorist threat,” IEEE TPWRS, vol. 19, no. 2, pp. 905–912, 2004.DOI
  3. [3]V. Donde et al., “Severe multiple contingency screening in electric power systems,” IEEE TPWRS, vol. 23, no. 2, pp. 406–417, 2008.DOI
  4. [4]P. Cicilio et al., “Electrical grid resilience framework with uncertainty,” Electric Power Systems Research, vol. 189, p. 106801, 2020.DOI
  5. [5]N. Fan et al., “N-1-1 contingency-constrained optimal power flow by interdiction methods,” in 2012 IEEE PES GM. IEEE, 2012, pp. 1–6.DOI
  6. [6]D. A. Z. Vazquez et al., “Reliable power grid expansion considering n − 1 − 1 contingencies,” in IEEE PES ISGT. IEEE, 2020, pp. 1–5.
  7. [7]A. Chio, R. Bent, K. Sundar, and N. Venkatasubramanian, “SEQUIN: A Network Science and Physics-based Approach to Identify Sequential Nk Attacks in Electric Power Grids,” in ACM/IEEE ICCPS, 2025.DOI
  8. [8]C. M. Rocco et al., “Multi-objective power grid interdiction model considering network synchronizability,” IJPE, vol. 17, no. 7, 2021.DOI
  9. [9]H. Ren, I. Dobson, and B. A. Carreras, “Long-term effect of the n-1 criterion on cascading line outages in an evolving power transmission grid,” IEEE TPWRS, vol. 23, no. 3, pp. 1217–1225, 2008.DOI
  10. [10]P. Corporation, “PowerWorld,” 2025. [Online]. Available: https://www.powerworld.com
  11. [11]J. D. Lara et al., “PowerSimulationsDynamics.jl – An Open Source Modeling Package for Modern Power Systems with Inverter-Based Resources,” 2023.
  12. [12]C. Steinbrink et al., “Cpes testing with mosaik: Co-simulation planning, execution and analysis,” Applied Sciences, vol. 9, no. 5, 2019.DOI
  13. [13]T. Brown, J. Hörsch, and D. Schlachtberger, “PyPSA: Python for Power System Analysis,” JORS, vol. 6, no. 4, 2018.DOI
  14. [14]H. L. Willis, Power distribution planning reference book. CRC press, 1997.
  15. [15]Q. Chen and J. D. McCalley, “Identifying high risk nk contingencies for online security assessment,” IEEE TPWRS, vol. 20, no. 2, 2005.DOI
  16. [16]N. Fan et al., “Economic analysis of the n-k power grid contingency selection and evaluation by graph algorithms and interdiction methods,” Energy Systems, vol. 2, no. 3, pp. 313–324, 2011.DOI
  17. [17]J. M. López-Lezama et al., “Assessment of the electric grid interdiction problem using a nonlinear modeling approach,” Electric Power Systems Research, vol. 144, pp. 243–254, 2017.DOI
  18. [18]A. O. Aquino, R. Harris, A. Kody, and D. K. Molzahn, “Comparing machine learning and optimization approaches for the n-k interdiction problem considering load variability,” in HICSS, 2023, pp. 2766–2775.
  19. [19]J. Salmeron et al., “Worst-case interdiction analysis of large-scale electric power grids,” IEEE TPWRS, vol. 24, no. 1, 2009.
  20. [20]K. Sundar, C. Coffrin, H. Nagarajan, and R. Bent, “Probabilistic interdiction for power systems,” CoRR, 2017.
  21. [21]X. Wu and A. J. Conejo, “An efficient tri-level optimization model for electric grid defense planning,” IEEE TPWRS, vol. 32, no. 4, 2016.DOI
  22. [22]K. Lai et al., “A tri-level optimization model to mitigate coordinated attacks on electric power systems in a cyber-physical environment,” Applied energy, vol. 235, pp. 204–218, 2019.DOI
  23. [23]K. Sundar, S. Misra, R. Bent, and F. Pan, “Credible interdiction for transmission systems,” IEEE TCNS, vol. 8, no. 2, pp. 738–748, 2021.DOI
  24. [24]H. Wang et al., “Dynamic data injection attack detection of cyber physical power systems with uncertainties,” IEEE TII, vol. 15, no. 10, pp. 5505–5518, 2019.DOI
  25. [25]K.-D. Lu, Z.-G. Wu, and T. Huang, “Differential evolution-based three stage dynamic cyber-attack of cyber-physical power systems,” IEEE-ASME T MECH, vol. 28, no. 2, pp. 1137–1148, 2022.DOI
  26. [26]R. Rocchetta et al., “Assessment of power grid vulnerabilities accounting for stochastic loads and model imprecision,” IJEPES, vol. 98, 2018.DOI
  27. [27]A. Mastin et al., “Best response intersection: An optimal algorithm for interdiction defense,” IJOC, vol. 5, no. 2, 2023.DOI
  28. [28]R. K. Wood, “Deterministic network interdiction,” Mathematical and Computer Modelling, vol. 17, no. 2, pp. 1–18, 1993.DOI
  29. [29]J. C. Smith et al., “Modern network interdiction problems and algorithms,” in Handbook of combinatorial optimization. Springer, 2013.DOI
  30. [30]E. S. Johnson et al., “A scalable lower bound for the worst-case relay attack problem on the transmission grid,” IJOC, vol. 34, no. 4, 2022.arxiv.org/abs/2105.02801
  31. [31]K. Sundar et al., “Exact and heuristic approaches for the stochastic nk interdiction in power grids,” in 2024 PMAPS. IEEE, 2024, pp. 1–6.arxiv.org/abs/2402.00217
  32. [32]K. Zhou et al., “The most frequent nk line outages occur in motifs that can improve contingency selection,” IEEE TPWRS, vol. 39, no. 1, 2023.
  33. [33]J. Yan et al., “Q-learning-based vulnerability analysis of smart grid against sequential topology attacks,” IEEE TIFS, vol. 12, no. 1, 2016.DOI
  34. [34]S. Babaeinejadsarookolaee et al., “The power grid library for benchmarking of optimal power flow algorithms,” arXiv:1908.02788, 2019.arxiv.org/abs/1908.02788
  35. [35]M. Lubin et al., “JuMP 1.0: Recent improvements to a modeling language for mathematical optimization,” MPC, 2023.
  36. [36]C. Coffrin et al., “Powermodels.jl: An open-source framework for exploring power flow formulations,” in PSCC, June 2018, pp. 1–8.arxiv.org/abs/1711.01728
  37. [37]Gurobi Optimization, LLC, “Gurobi Optimizer Reference Manual,” 2024. [Online]. Available: https://www.gurobi.com
  38. [38]A. Chio, 2025. [Online]. Available: https://github.com/andrewgchio/temporal_nk

Paper details

vlnc:W_24j7ccpv
Version
v1 · latest
Published
Fresh — added to the Hub within the last 30 days
Added
License
CC BY-SA 4.0
Usage

views · 0

downloads · 0

A view counts once per browser per day, a download each time the PDF is requested.

  • Engineering

Not recorded for this paper

View statement
Looking for related papers…
Contents