WorksEngineering
Mode-in-Variance Participation Factors under Stochastic Excitation
Abstract
This paper investigates how the dynamic modes of a power system contribute to the stationary variance of its variables under continuous stochastic excitation. Using a modal decomposition of the covariance matrix, the variance of each state or algebraic variable can be resolved into components associated with individual modal responses and their interactions. These components are shown to correspond to within-mode variance and cross-modal covariance, respectively, and the corresponding normalized contributions are termed mode-in-variance participation factors (PFs). The proposed PFs can be used to identify modes governing the variability of important system quantities such as frequency and voltage, quantify the effect of modal interactions, and reveal control dynamics that can be targeted to reduce their stochastic variability. These capabilities are demonstrated through case studies based on the Kundur two-area and IEEE 39-bus systems.
Introduction
Motivation
Power systems are continuously subjected to stochastic forcing arising from fluctuations in loads and primary energy resources, such as wind and solar generation [1], [2]. Such forcing induces variability in important system quantities, including frequency and voltage [3, 4, 5]. Existing methods can quantify the magnitude of this variability, but they do not explain which dynamic modes are responsible for it or how different modal contributions combine in the observed response. Identifying the dynamic modes contributing to stochastic variability can provide a means to characterize its origin and support control design. This motivates the modal perspective adopted in this work.
Literature Review
Power systems subject to continuous stochastic variations can be represented through stochastic differential algebraic equations (SDAEs) [6], [7]. Existing works have adopted both numerical and analytical approaches within this framework [8, 9, 10, 11, 12, 13, 14]. For example, Monte Carlo time-domain simulations have been used to study voltage and frequency dynamics under stochastic excitation [9], [11]. Analytical studies have examined statistical properties of the system response, including stationary variance and frequency distributions [10], [12, 13, 14].
A systematic basis for relating system variables to dynamic modes is provided by classical modal analysis [15]. Probabilistic small-signal approaches have extended modal analysis to describe the distributions of eigenvalues, damping ratios, and participation factors induced by uncertain operating conditions [16, 17, 18, 19, 20]. Related studies have examined modal variations across prescribed ranges of operating conditions and parameters [21, 22, 23].
A complementary line of work has examined how the modal structure of a system is reflected in energy-based response measures following initial perturbations. In particular, [24], [25] propose Lyapunov modal analysis to attribute accumulated state or signal energy to individual modes and their interactions. Modal attribution following initial perturbations has also been used to analyze the magnitude of voltage and frequency deviations. In particular, [26] defines small-signal variability in terms of the maximum linearized time-domain deviation and quantifies the contribution of individual modes from the corresponding decoupled modal responses.
To the best of our knowledge, a systematic approach to linking stochastic fluctuations in power system quantities arising from continuous variations in demand and generation to the underlying dynamic modes of the system is currently missing. Such an approach is particularly relevant because the observed stochastic variability cannot be attributed solely to the characteristics of the stochastic inputs, as the system dynamics also shape how these fluctuations propagate to individual system variables. Moreover, the modes that dominate stochastic variability need not coincide with those identified as most important by classical modal participation factors. This paper aims to address this gap.
Contribution
The contribution of this paper is twofold, as follows:
A modal decomposition of the stationary covariance matrix is applied to define mode-in-variance PFs, which quantify the contribution of dynamic modes to the stationary variance of system variables under continuous stochastic excitation. The approach is formulated for both state and algebraic variables, enabling modal contributions to the variability of quantities such as frequency and voltage to be studied.
The contribution of each mode is resolved into a direct component associated with within-mode variance, an interaction component associated with cross-modal covariance, and a net component combining both effects. The interaction and net contributions are signed, thereby accounting for reinforcement or cancellation among modal responses.
Paper Organization
The remainder of this paper is organized as follows. § 2 provides background on the modeling of power systems under stochastic variations and defines the stationary covariance matrix of the system under small stochastic perturbations. § 3 introduces the proposed mode-in-variance PFs and presents their formulation for both state and algebraic variables. § 4 evaluates the proposed approach through case studies based on the Kundur two-area and IEEE 39-bus systems. Finally, § 5 draws conclusions and discusses directions for future work.
Preliminaries
Stochastic Power System Model
Power systems subject to stochastic variations can be modeled by a set of nonlinear SDAEs [6], as follows:
where and are the state and algebraic variables, respectively; and define, respectively, the differential and algebraic equations; is the vector of stochastic inputs representing fluctuations in generation and demand, entering the system as continuous external forcing. The dynamics of are represented as a multivariate Itô diffusion process
where is the drift vector, which describes the deterministic evolution of ; is the diffusion matrix, which determines the intensity of the random fluctuations; and is a vector of independent Wiener processes. The stochastic response of the nonlinear model in (1)–(2) can be studied through time-domain simulations. In this work, the stochastic inputs are represented by the commonly used multivariate Ornstein–Uhlenbeck (OU) process, obtained from (2) by considering a linear mean-reverting drift and a constant diffusion matrix:
where is the vector of mean values, is the mean-reversion matrix, and is the diffusion matrix.
Small Disturbance Analysis
For sufficiently small disturbances, (1) can be linearized around an equilibrium point , with , allowing the stochastic response to be characterized analytically. Under the standard assumption that is nonsingular, the algebraic variables can be locally eliminated. Combining the resulting linearized model with (3) gives
where , with and , and are the Jacobians evaluated at the equilibrium point. The solution of (4) is given by
The first term represents the deterministic response to the initial condition , while the second term represents the response to the stochastic forcing. The expectation of the stochastic integral in (5) is zero [27], such that
where denotes the expectation operator. We thus have
Since the right-hand side is an integral of Wiener increments, is Gaussian. Moreover, if all eigenvalues of have negative real parts (which is equivalent to both and being Hurwitz), then from (6), i.e., the stationary distribution of has zero mean.
The stochastic variability of can be characterized through its covariance matrix, defined as
Substituting (7) into (8) and applying the Itô isometry property [27] gives
where
Taking and applying the change of variable gives the stationary covariance matrix
(11) shows that the stationary covariance results from the accumulation of stochastic disturbances propagated through the system dynamics. Hence, it is jointly determined by the stochastic forcing, represented by , and the system dynamics, represented by the state-transition matrix . Observe that, since , (11) is also the controllability Gramian associated with (4).
The diagonal elements of correspond to the stationary variances of the variables in , i.e., for :
while the off-diagonal elements quantify the covariance between pairs of variables. Equivalently to (11), the stationary covariance matrix satisfies the Lyapunov equation
The derivation of (13) is provided in the Appendix.
Modal Characterization of Stochastic Variability
This section presents the proposed approach for quantifying the contribution of system dynamic modes to the stationary variance of state and algebraic variables.
Spectral Decomposition of the Covariance Matrix
The stationary covariance in (11) can be decomposed in terms of the eigenvalues and eigenvectors of . Let and , where the columns of are the right eigenvectors of , and the rows of are the corresponding left eigenvectors; . Under the assumption that is diagonalizable, the left and right eigenvectors are normalized such that . Accordingly, we can write , where contains the eigenvalues of . The state-transition matrix can then be expressed as
Substitution of (14) into (11) gives
For asymptotically stable , , and
It follows that matrix can be written as
which expresses as a sum of contributions associated with pairs of eigenvalues. This pairwise structure arises because covariance is quadratic in the system response (see (8)). In (15), the modal expansion therefore enters on both sides of , producing one modal index from each side and, hence, contributions associated with pairs . Accordingly, the contribution associated with the eigenvalue pair is
Matrix is then recovered as
We note that an analogous spectral decomposition in terms of pairs of eigenvalues can be obtained in a deterministic free response analysis for the accumulated response energy following an initial perturbation [24]. However, the objective and quantity of interest in the present work are different, as the decomposition in (19) serves as the basis for identifying modal contributions to the stationary variance of system variables. To establish the statistical meaning of these contributions, we substitute the modal representation of in (14) into the centered stochastic response in (7). This gives
where
denotes the contribution of the th eigenvalue to the centered stochastic response of .
Proposition 1. The quantity is equal to the stationary nonconjugate cross-covariance between the contributions of the th and th eigenvalues to the stochastic response, i.e.,
The proof of (22) is given in the Appendix.
Each complex-conjugate eigenvalue pair is next grouped into a single oscillatory mode. Let denote the set of eigenvalue indices associated with the th mode. Consequently, each contains either one index, corresponding to a real eigenvalue representing a nonoscillatory mode, or two indices, corresponding to a complex-conjugate pair. The contribution of each mode to the stochastic response is defined as
From (20) and (23), the centered stochastic response can then be written as
Substituting into (8), separating within-mode from cross-mode terms, and taking the limit , the stationary covariance can be written as
The first term represents the stationary covariance associated with individual modes, whereas the second term represents the covariance between distinct modes.
Mode-in-Variance Participation Factors
For variable , with stationary variance , the contribution of pair is obtained from (18) as
where is the th canonical basis vector in . Hence,
The contributions of the eigenvalue pairs to are subsequently grouped into direct and interaction contributions. The direct contribution associated with a single mode is obtained by collecting the terms with :
The pairwise interaction contribution between two distinct modes and is obtained by collecting the corresponding cross mode terms:
Summing over all , we define the total interaction contribution of mode as
where the factor is introduced because each pairwise contribution between modes and enters the interaction term of both modes. To prevent the same quantity from being counted twice when the modal contributions are summed, one half is assigned to each mode.
From (28) and (30), the stationary variance in (27) can be written as
Proposition 2. The direct contribution represents the part of the stationary variance of associated with mode and is therefore nonnegative. Moreover, the interaction contribution represents the part of the stationary variance of arising from the cross covariances between mode and the remaining modes, and can therefore be positive or negative.
Proof: Using (25), can be expressed as
Moreover, for two distinct modes and , the pairwise interaction contribution is
Using (30), it follows that
Since covariances can be positive or negative, is a signed quantity.
A positive (negative) indicates reinforcement (cancellation) between the contribution of to and the contributions of the remaining modes.
Definition 1 (Mode-in-variance PFs). Based on the variance decomposition in (31), the direct and interaction contributions of mode to the stationary variance of are normalized by . The corresponding normalized quantities are defined as the direct and interaction mode-in-variance PFs:
The corresponding net mode-in-variance PF is defined as
The net mode-in-variance PF represents the overall contribution of mode to the stationary variance after accounting for its interactions with other modes. From Proposition 2, , whereas and can be positive or negative. For , the net mode-in-variance PFs sum to unity by construction, i.e., .
Projection to Algebraic Variables
The proposed mode-in-variance PF framework is extended to algebraic variables by accounting for their dependence on the states and stochastic inputs. From the linearized model (4), the variations of algebraic variables satisfy
where
is the corresponding algebraic mapping matrix. Hence, the stationary covariance matrix of is [12]
Substituting the decomposition of in (19) into (38) gives
where represents the contribution of the eigenvalue pair to the stationary covariance of the algebraic variables.
For a with stationary variance
the contribution of pair is obtained from (39) as
where is the th canonical basis vector in . Hence,
The eigenvalue pair contributions to are grouped following the construction in § 3-B. The direct and total interaction contributions associated with mode are
and
Thus, the direct and interaction mode-in-variance PFs for are defined as
The corresponding net mode-in-variance PF is defined as:
For , the net mode-in-variance PFs sum to unity by construction, i.e., .
Case Studies
This section illustrates the proposed mode-in-variance PF framework through numerical case studies based on the Kundur two-area and IEEE 39-bus benchmark systems. All simulations are performed using Dome [7].
Kundur Two-Area System
This section considers the two-area four-machine system shown in Figure 1. The system consists of eleven buses and four synchronous machines (SMs) connected through a relatively weak tie line. Each SM is equipped with an automatic voltage regulator (AVR) and a turbine governor (TG). The system feeds two loads, modeled as constant power demands subject to independent stochastic variations represented by OU processes. Considering active and reactive power variations per load gives . This leads to a special case of (3) with
Figure 1. Kundur two-area system: single-line diagram.
The coefficients and determine the autocorrelation decay rates of the active and reactive power variations, respectively, while and , where and are the corresponding stationary standard deviations. We set and for the active power variations, and and for the reactive power variations.
The decomposition in (31) is first validated by comparing the variances obtained by summing the direct and interaction contributions of all modes with the reference values obtained by solving (13) using SLICOT [28]. In addition, the variances are also validated against the reference values estimated from a 10,000 s nonlinear time-domain simulations (TDS). For each comparison, the relative error is calculated as the 2-norm of the difference between the variance vectors, normalized by the 2-norm of the corresponding reference vector. The error relative to the Lyapunov solution is as expected negligible, at , while the error relative to the TDS is 3.696%, confirming the numerical accuracy of the decomposition and indicating good agreement with the simulated responses.
The proposed mode-in-variance PFs are used to identify the dynamic modes contributing to the stationary variability of the rotor speed of SM 1. The stationary standard deviation of is pu. The results are reported in Table I, which lists the five modes with the largest absolute net contributions.
| Mode | (Hz) | |||||
| 27 | 0.075 | 0.680 | 0.9086 | 0.0249 | 0.9335 | |
| 17 | 0.498 | 0.037 | 0.0422 | -0.0025 | 0.0397 | |
| 23 | 0.224 | 1.000 | 0.0082 | 0.0122 | 0.0204 | |
| 24 | 0.135 | 1.000 | 0.0006 | 0.0043 | 0.0049 | |
| 28 | 0.075 | 0.773 | 0.0001 | -0.0048 | -0.0047 |
Table I. Kundur system: mode-in-variance PFs for .
Mode 27, represented by the eigenvalue pair , has the largest direct and net mode-in-variance PFs in . The shapes of the two oscillatory modes with positive net contributions are shown in Figure 2. With a natural frequency of 0.075 Hz, Mode 27 exhibits a coherent shape across the rotor speeds of all machines, corresponding to the common mode of the system [29, 30, 31]. In contrast, the second-largest contributor, Mode 17, corresponds to the interarea mode. With a , compared with 0.0397 for the interarea mode, Mode 27 dominates the stationary variability of . Notably, Mode 27 has a high damping ratio and thus, although not critical from the perspective of conventional small-signal screening, is highly relevant under stochastic excitation. Moreover, the small value of indicates that interactions with the remaining modes slightly influence the variability of .
Figure 2. Kundur system: Mode shapes (a) common mode and (b) interarea.
The proposed framework is further illustrated by considering the center-of-inertia (COI) frequency of the system, which is an algebraic variable. Its stationary standard deviation is
| Mode | (Hz) | |||||
| 27 | 0.075 | 0.680 | 0.9542 | 0.0191 | 0.9733 | |
| 23 | 0.224 | 1.000 | 0.0086 | 0.0153 | 0.0238 | |
| 24 | 0.135 | 1.000 | 0.0008 | 0.0056 | 0.0064 | |
| 28 | 0.075 | 0.773 | 0.0000 | -0.0040 | -0.0040 | |
| 17 | 0.498 | 0.037 | 0.0006 | -0.0001 | 0.0005 |
Table 2. Kundur system: mode-in-variance PFs for .
pu, and the corresponding mode-in-variance PFs are reported in Table II. As can be seen, the common mode again provides the largest direct and net contributions, with , indicating that it is the dominant contributor to stochastic frequency variability.
The information provided by the proposed mode-in-variance PFs is next contrasted with that of classical mode-in-state PFs. In particular, Table III reports the classical PFs for the rotor speed of SM 1. The column "dom." indicates the state in which each mode exhibits the largest participation. The local mode at Hz and interarea mode exhibit the largest classical PFs, while the common mode at Hz ranks third. This difference results from the distinct quantities characterized by the two formulations. The larger classical PFs of the local and interarea modes indicate their greater contributions to the response of following an initial perturbation of that variable. In contrast, the mode-in-variance PFs identify the common mode as the dominant contributor to the stationary variance of under continuous stochastic excitation.
| Mode | dom. | (Hz) | PF | ||
| 18 | 1.054 | 0.061 | 0.2951 | ||
| 17 | 0.498 | 0.037 | 0.2836 | ||
| 27 | 0.075 | 0.68 | 0.1906 | ||
| 23 | 0.224 | 1 | 0.1640 | ||
| 16 | 1.077 | 0.06 | 0.0895 |
Table 3. Kundur system: classical PFs for .
Modified Kundur Two-Area System
This section considers a modified version of the Kundur two-area system, in which the SMs in Area 1 are replaced by grid-following (GFL) converters modeled with a synchronous-reference-frame Phase-Locked Loop (SRF-PLL), inner PI current control loops, and constant DC voltage [32]. The converters are equipped with frequency controllers consisting of a droop gain and a first-order filter with time constant s. The stochastic load model and parameters are kept the same as in the previous section.
We examine the stochastic voltage response at two representative buses of the modified system: Bus 1, i.e., the terminal bus of a GFL converter, and Bus 3, i.e., the terminal bus of a SM. Figure 3 shows a realization of the two voltage responses obtained from a nonlinear TDS of (1). The voltage at the GFL terminal exhibits substantially larger variability than that at the SM terminal, with stationary standard deviations of pu and pu, respectively.
Figure 3. Modified Kundur system: Voltage responses at Buses 1 and 3.
The mode-in-variance PFs for are reported in Table IV. Mode 17, whose classical PFs indicate dominant participation to the GFL frequency control dynamics, has the largest net contribution, with . Its direct contribution is larger, with , but is partially offset by the negative interaction contribution, . The second-largest positive contribution is provided by Mode 25.
| Mode | (Hz) | |||||
| 17 | 0.023 | 1.000 | 1.1719 | -0.2486 | 0.9233 | |
| 25 | 0.016 | 1.000 | 0.0252 | 0.1222 | 0.1474 | |
| 24 | 0.016 | 1.000 | 0.0999 | -0.1361 | -0.0362 | |
| 14 | 0.110 | 0.766 | 0.0350 | -0.0683 | -0.0333 | |
| 1 | 9.440 | 1.000 | 0.0204 | 0.0019 | 0.0223 |
Table 4. Modified Kundur system: mode-in-variance PFs for .
| Mode | (Hz) | |||||
| 13 | 0.171 | 0.339 | 2.4606 | -1.7440 | 0.7167 | |
| 1 | 9.440 | 1.000 | 0.2099 | -0.0262 | 0.1837 | |
| 14 | 0.110 | 0.766 | 3.5554 | -3.4414 | 0.1140 | |
| 18 | 0.073 | 0.771 | 0.1079 | -0.1971 | -0.0892 | |
| 17 | 0.023 | 1.000 | 0.1086 | -0.0757 | 0.0329 |
Table 5. Modified Kundur system: mode-in-variance PFs for .
The mode-in-variance PFs for are reported in Table V. Mode 13, corresponding to the system’s common mode, exhibits the largest net contribution, with . In contrast, Mode 14, associated with the SM voltage control dynamics, has the largest direct contribution, , but its strong negative interaction contribution reduces its net PF to . Thus, a large direct contribution does not necessarily translate into a large overall contribution, highlighting the importance of accounting for modal interactions when attributing stationary voltage variability.
For comparison, the classical mode-in-algebraic variable PFs for are calculated using the formulation in [15] and reported in Table VI. The modes with the largest mode-in-algebraic PFs exhibit their dominant state participation in the internal transient voltage states of the SMs, namely , , the d-axis PI state of the GFL , the SRF-PLL state , and the AVR state . In contrast, the mode-in-variance PFs identify Mode 17, associated with the GFL frequency control dynamics, as the dominant contributor to the voltage variance at Bus 1. These results further confirm that classical PFs should not be used to assess modal contributions to variability under continuous stochastic excitation.
| Mode | dom. | (Hz) | PF | ||
| 18 | 0.073 | 0.771 | 0.0657 | ||
| 16 | 0.77 | 1 | 0.0425 | ||
| 33 | 0.08 | 1 | 0.0362 | ||
| 1 | 9.44 | 1 | 0.0338 | ||
| 14 | 0.11 | 0.766 | 0.0261 |
Table VI. Modified Kundur system: classical PFs for .
To further examine the relationship between frequency control and voltage variability, a second configuration is considered in which the frequency control of the GFLs is disabled. The resulting terminal bus voltage responses of the GFL at Bus 1 and SM at Bus 3 are shown in Figure 4. In this scenario, the stationary standard deviation of decreases to 0.007 pu, corresponding to 65% reduction relative to the previous configuration. The corresponding mode-in-variance PFs are reported in Table VII. Modes 23 and 24, associated with the stochastic active load processes, now provide the largest , equal to 0.6844 and 0.3021, respectively. Notably, both modes have damping ratios , further showing that non-oscillatory modes, often receiving less attention in conventional small-signal stability assessments, can dominate stationary voltage variability under stochastic excitation.
Figure 4. Modified Kundur system: GFL without primary frequency control: voltage at the terminal buses of the GFL at Bus 1 and SM at Bus 3.
| Mode | (Hz) | |||||
| 23 | 0.016 | 1.000 | 0.7805 | -0.0961 | 0.6844 | |
| 24 | 0.016 | 1.000 | 0.2409 | 0.0612 | 0.3021 | |
| 14 | 0.109 | 0.767 | 0.0333 | -0.0181 | 0.0153 | |
| 19 | 0.078 | 1.000 | 0.0002 | -0.0059 | -0.0057 | |
| 11 | 0.731 | 1.000 | 0.0014 | 0.0038 | 0.0052 |
Table VII. Modified Kundur system: mode-in-variance PFs for .
We note that the stochastic load model and parameters remain unchanged between the two configurations considered above, despite the substantial reduction in voltage variability. This illustrates that the magnitude of stochastic variability cannot be inferred solely from the characteristics of the stochastic inputs, since it strongly depends on how the system dynamics shape their propagation to the variable of interest. In this regard, the proposed PFs can be used to identify control dynamics that can be targeted to reduce stochastic variability in electrical quantities of interest. This is further discussed in the next section.
IEEE 39-Bus System
This section considers the standard IEEE 39-bus benchmark system shown in Figure 5. It consists of ten SMs, all represented with fourth-order models and equipped with voltage regulators, TGs, and PSSs. For the purposes of this paper, all 19 loads in the system are modeled by OU processes, with the same parameters for all loads. For the active power variations, and the standard deviation is set to . For the reactive power variations, and .

Figure 5. IEEE 39-bus system: single-line diagram.
The stochastic voltage variability is evaluated at the terminal buses of all ten SMs. Among these buses, has the highest stationary standard deviations, pu, whereas has the lowest, pu. The voltage responses at these two buses for one stochastic realization are shown in Figure 6.
Figure 6. 39-bus system: Highest and lowest bus voltage variances.
Modes 54 and 55, with high damping ratios of and 0.996, respectively, consistently appear among those with the largest net mode-in-variance PFs for the voltages across the SM terminal buses. Figure 7 shows the shapes for Mode 54 and 55, using the eigenvectors related to the voltage states measured by the corresponding SM AVRs (). The mode shapes exhibit a predominantly anti-phase response between SMs 1 and 9. The mode-in-variance PFs for and are reported in Tables VIII and IX, respectively. Mode 54 exhibits the largest net contribution at both buses.

Figure 7. 39-bus system: Mode shapes for (a) Mode 54 and (b) Mode 55.
| Mode | (Hz) | |||||
| 54 | 0.216 | 0.964 | 39.1177 | -34.1835 | 4.9342 | |
| 55 | 0.248 | 0.996 | 30.1559 | -34.3772 | -4.2213 | |
| 47 | 0.289 | 0.748 | 1.3636 | -0.3528 | 1.0108 | |
| 60 | 0.220 | 1.000 | 1.1032 | -1.9298 | -0.8266 | |
| 49 | 0.243 | 0.890 | 1.1595 | -1.8219 | -0.6624 |
Table 8. 39-bus system: Mode-in-variance PFs for .
| Mode | (Hz) | |||||
| 54 | 0.216 | 0.964 | 4.6747 | -3.7215 | 0.9532 | |
| 55 | 0.248 | 0.996 | 6.2868 | -7.206 | -0.9192 | |
| 79 | 0.015 | 1.000 | 2.0632 | -1.2690 | 0.7942 | |
| 49 | 0.243 | 0.890 | 4.2394 | -4.8933 | -0.6538 | |
| 47 | 0.289 | 0.748 | 2.8841 | -2.5197 | 0.3644 |
Table 9. 39-bus system: Mode-in-variance PFs for .
The sign of the net mode-in-variance PF provides additional insight into the role of modal interactions. In particular, at Bus 38, Mode 49 has the largest positive net contribution, whereas Mode 54 has a large direct contribution of 42.5011, but its negative interaction contribution of results in (Table X). Notably, Bus 38 is the only SM terminal bus where the interactions of Mode 54 with the remaining modes outweigh its direct contribution, resulting in a net reduction in the total voltage variance.
| Mode | (Hz) | |||||
| 49 | 0.243 | 0.890 | 131.9305 | -123.2937 | 8.6368 | |
| 54 | 0.216 | 0.964 | 42.5011 | -46.6281 | -4.1270 | |
| 55 | 0.248 | 0.996 | 2.5377 | -3.8279 | -1.2902 | |
| 63 | 0.170 | 1.000 | 2.4507 | -3.6901 | -1.2394 | |
| 60 | 0.220 | 1.000 | 1.7542 | -0.7145 | 1.0397 |
Table 10. 39-bus system: Mode-in-variance PFs for .
The classical mode-in-algebraic variable PFs are also evaluated for , with the results reported in Table XI. The largest PFs are associated with generator internal-voltage states, including of SMs 4 and 7 and of SMs 6 and 7, as well as the q-axis current of SM 6.
as the q-axis current of SM 6. Notably, neither Mode 54 nor Mode 55 appears among the modes with the largest PFs.
| Mode | dom. | (Hz) | PF | ||
| 93 | 0.146 | 1 | 0.3042 | ||
| 92 | 0.153 | 1 | 0.2861 | ||
| 63 | 0.170 | 1 | 0.0636 | ||
| 86 | 0.126 | 0.612 | 0.0107 | ||
| 70 | 0.183 | 0.701 | 0.0107 |
Table 11. 39-bus system: Classical PFs for .
For Bus 36, Table IX identifies, in addition to Modes 54 and 55 discussed above, Mode 79 as a significant positive net contributor to voltage variance, with . Mode 79 is a local mode associated with the PSS dynamics of the SM connected to Bus 36. Based on this, we finally investigate whether a retuning of the PSS can be beneficial in reducing the stationary voltage variability at Bus 36. As shown in Figure 8, reducing the PSS gain from 7.5 to 2 decreases the stationary standard deviation from pu to pu, corresponding to a 67.83% reduction in the local voltage variability at bus 36.
Figure 8. 39-bus system: voltage magnitude variations after the adjustment in the PSS gain of the SM at Bus 36.
Conclusions
The variability of a power system quantity cannot be attributed solely to the characteristics of stochastic inputs, since the system dynamics shape how disturbances propagate and affect its response. To investigate this relationship, a mode-in-variance PF framework was proposed based on the modal decomposition of the stationary covariance matrix obtained from a linearized SDAE system model. The proposed formulation quantifies the contribution of dynamic modes to the stationary variance of both state and algebraic variables under continuous stochastic excitation, distinguishing their direct contributions from the effects of modal interactions.
The case studies demonstrated that highly damped modes, which may receive less attention in conventional small-signal stability assessments, can dominate stationary frequency and voltage variability. Comparisons with classical PFs further showed that the modes contributing most strongly to stationary variance do not necessarily coincide with those exhibiting the largest classical participation factors. Moreover, the proposed framework identified control dynamics whose modification can result in reductions in voltage variability, demonstrating its potential to guide targeted control interventions. We will dedicate future work to developing this capability into a systematic control design aimed at reducing the stationary variance of selected power system variables.
Appendix
Derivation of the Lyapunov equation
Since the Wiener increments have zero mean, i.e., , taking expectations in (4) gives
whose solution is (6). Consider now the centered variable
From (8), we have
Differentiating (47) and using (4) and (46) gives:
Applying Itô’s product rule to yields
Substituting (49) and using yields
Taking expectations and using (48) gives
Since is Hurwitz, converges to its stationary value as , and . Hence, we arrive at (13).
Derivation of modal cross covariance
Using (21), the Itô isometry, and , the nonconjugate cross-covariance between and is
For a stable system, , and thus . Hence, in the stationary limit,
Using (18), we arrive at (22).
References
Biographies
Bruno Pinheiro
Bruno Pinheiro (M’26) received the B.S. degree in electrical engineering from the Federal University of Amazonas, Brazil, in 2018, and the M.Sc. and Ph.D. degrees in electrical engineering from the University of Campinas (UNICAMP), Brazil, in 2021 and 2025, respectively. In Apr.-Oct. 2024, he was a visiting researcher at University College Dublin (UCD), Ireland. From Dec. 2025 to May 2026, he was a postdoctoral researcher with UNICAMP. Since May 2026, he has been a Postdoctoral Researcher with UCD, Dublin, Ireland. His research interests include power system stability, control, and modeling.
Liya Huang
Liya Huang (S’26) received the B.S. degree in electrical engineering and automation from Beijing Institute of Technology, Beijing, China, and the M.S. degree in electrical engineering from Central South University, Changsha, China. Since 2024, she has been pursuing the Ph.D. degree in electrical engineering with University College Dublin (UCD), Dublin, Ireland. Her research interests include power system stability and simulation.
Georgios Tzounas
Georgios Tzounas (SM’26) received the Diploma (M.E.) in Electrical and Computer Engineering from the National Technical University of Athens, Greece, in 2017, and the Ph.D. from University College Dublin (UCD), Ireland, in 2021. In Jan.-Apr. 2020, he was a visiting researcher at Northeastern Univ., Boston, MA. From Oct. 2020 to Apr. 2023, he was a postdoctoral researcher with UCD (2020-2022) and ETH Zürich (2022-2023). Since Apr. 2023, he has been an Assistant Professor with the School of Electrical and Electronic Engineering at UCD. His primary research area is power system dynamics.
References
- [1]B. Tan and J. Zhao, “Stochastic dynamic stability assessment with high penetration of uncertain sources: Uncertainty modeling, solutions and applications,” Cyber-Phys. Energy Syst., vol. 2, no. 1, pp. 13–24, 2026.DOI
- [2]B. Pinheiro, M. Llerena Velasquez, G. Faria, A. Aquino, D. Issicaba, and D. Dotta, “Evaluation of the impact of IBR on the frequency dynamics in the Brazilian power system,” Sustainable Energy, Grids and Networks, vol. 43, p. 101827, 2025.DOI
- [3]Y. Xu, C. Wan, Z. He, H. Liu, and P. Ju, “Stochastic stability oriented frequency control: A probabilistic forecasting-based high-order stochastic Koopman approach,” IEEE Transactions on Power Systems, vol. 41, no. 5, pp. 3323–3335, 2026.DOI
- [4]T. Kércsi and F. Milano, “Frequency quality metrics based on second-order derivative and autocorrelation,” IEEE Transactions on Power Systems, vol. 41, no. 5, pp. 4045–4048, 2026.
- [5]S. C. Chevalier and P. D. H. Hines, “Mitigating the risk of voltage collapse using statistical measures from PMU data,” IEEE Transactions on Power Systems, vol. 34, no. 1, pp. 120–128, 2019.arxiv.org/abs/1805.03703
- [6]F. Milano and R. Zárate-Miñano, “A systematic method to model power systems as stochastic differential algebraic equations,” IEEE Transactions on Power Systems, vol. 28, no. 4, pp. 4537–4544, 2013.DOI
- [7]F. Milano, M. Liu, M. A. Murad, G. M. Jónsdóttir, G. Tzounas, M. Adeen, Á. Ortega, and I. Dassios, “Power system modelling as stochastic functional hybrid differential-algebraic equations,” IET Smart Grid, vol. 5, no. 5, pp. 309–331, 2022.DOI
- [8]G. Pierrou and X. Wang, “Analytical study of the impacts of stochastic load fluctuation on the dynamic voltage stability margin using bifurcation theory,” IEEE Transactions on Circuits and Systems I: Regular Papers, vol. 67, no. 4, pp. 1286–1295, 2020.
- [9]B. Pinheiro and D. Dotta, “Dynamic connectivity and local frequency strength under stochastic variations,” in 2026 IEEE Power & Energy Society General Meeting (PESGM), 2026, pp. 1–5.arxiv.org/abs/2603.01902
- [10]Hongyu Li et al., “Analytic analysis for dynamic system frequency in power systems under uncertain variability,” IEEE Trans. on Power Syst., vol. 34, no. 2, pp. 982–993, 2019.DOI
- [11]H. Mushtaq, A. S. Mir, and N. Senroy, “Impact of auto-correlation of wind speed on the dynamics of grid-connected doubly fed induction generator,” IEEE Transactions on Power Systems, vol. 40, no. 4, pp. 3427–3438, 2025.DOI
- [12]M. Adeen et al., “On the calculation of the variance of algebraic variables in power system dynamic models with stochastic processes,” IEEE Trans. on Power Syst., vol. 38, no. 2, pp. 1739–1742, 2023.DOI
- [13]P. Vorobev, D. M. Greenwood, J. H. Bell, J. W. Bialek, P. C. Taylor, and K. Turišyn, “Deadbands, droop, and inertia impact on power system frequency distribution,” IEEE Transactions on Power Systems, vol. 34, no. 4, pp. 3098–3108, 2019.DOI
- [14]G. Ghanavati, P. D. H. Hines, and T. I. Lakoba, “Identifying useful statistical indicators of proximity to instability in stochastic power systems,” IEEE Transactions on Power Systems, vol. 31, no. 2, pp. 1360–1368, 2016.
- [15]G. Tzounas, I. Dassios, and F. Milano, “Modal participation factors of algebraic variables,” IEEE Transactions on Power Systems, vol. 35, no. 1, pp. 742–750, 2019.
- [16]K. N. Hasan, R. Preece, and J. V. Milanović, “Existing approaches and trends in uncertainty modelling and probabilistic stability analysis of power systems with renewable generation,” Renewable and Sustainable Energy Reviews, vol. 101, pp. 168–180, 2019.
- [17]L. I. Benedetti, A. Egea-Álvarez, R. Preece, and P. N. Papadopoulos, “Enabling characterisation of dynamic interactions with probabilistic small-signal analysis in converter-integrated power systems,” IEEE Transactions on Power Systems, vol. 41, no. 2, pp. 942–954, 2026.DOI
- [18]R. Xiao, C. Wan, Z. He, and P. Ju, “Probabilistic small-signal stability analysis of power systems with renewable energy: A truncated GMM-based analytical method,” IEEE Transactions on Power Systems, vol. 41, no. 2, pp. 1294–1307, 2026.DOI
- [19]J. Zhou, D. Ke, C. Y. Chung, and Y. Sun, “A computationally efficient method to design probabilistically robust wide-area PSSs for damping inter-area oscillations in wind-integrated power systems,” IEEE Transactions on Power Systems, vol. 33, no. 5, pp. 5692–5703, 2018.DOI
- [20]W. C. Wong and C. Y. Chung, “Coordinated damping control design for DFIG-based wind generation considering power output variation,” IEEE Transactions on Power Systems, vol. 27, no. 4, pp. 1916–1925, 2012.DOI
- [21]L. I. Benedetti, P. N. Papadopoulos, and R. Preece, “Exploring the variation of critical modal properties in power systems with converter-interfaced units,” Sustainable Energy, Grids and Networks, vol. 43, p. 101841, 2025.DOI
- [22]M. E. C. Bento, “Fixed low-order wide-area damping controller considering time delays and power system operation uncertainties,” IEEE Transactions on Power Systems, vol. 35, no. 5, pp. 3918–3926, 2020.DOI
- [23]A. Piccipicello and A. Vaccaro, “Small-signal stability analysis of uncertain power systems via interval analysis,” Electric Power Systems Research, vol. 212, p. 108339, 2022.
- [24]A. B. Iskakov and I. B. Yadykin, “Lyapunov modal analysis and participation factors applied to small-signal stability of power systems,” Automatika, vol. 132, p. 109814, 2021.
- [25]A. B. Iskakov, E. Y. Kutyakov, N. V. Tomin, D. A. Panasetsky, A. N. Abramenkov, and S. V. Dushin, “Estimation of the location of inter-area oscillations and their interactions in electrical power systems using Lyapunov modal analysis,” International Journal of Electrical Power & Energy Systems, vol. 153, p. 109374, 2023.DOI
- [26]L. Benedetti, P. N. Papadopoulos, and A. Egea-Àlvarez, “A modal contribution metric for quantifying small-signal variability in power systems with converter-interfaced generation,” IEEE Transactions on Power Systems, vol. 40, no. 3, pp. 2636–2647, 2024.DOI
- [27]P. E. Kloeden and E. Platen, Numerical Solution of Stochastic Differential Equations, 3rd ed. Springer, 1999.
- [28]P. Benner, V. Mehrmann, V. Sima, S. Van Huffel, and A. Varga, “Slicot – a subroutine library in systems and control theory,” in Applied and Computational Control, Signals, and Circuits, B. N. Datta, Ed. Boston, MA: Birkhäuser, 1999, vol. 1, ch. 10, pp. 499–539.DOI
- [29]F. Wilches-Bernal, J. H. Chow, and J. J. Sanchez-Gasca, “A fundamental study of applying wind turbines for power system frequency control,” IEEE Transactions on Power Systems, vol. 31, no. 2, pp. 1496–1505, 2016.
- [30]R. Xie, I. Kamwa, D. Rimorov, and A. Moeini, “Fundamental study of common mode small-signal frequency oscillations in power systems,” International Journal of Electrical Power & Energy Systems, vol. 106, pp. 201–209, 2019.DOI
- [31]A. Bouterakos, J. McKeon, and G. Tzounas, “On the eigenvalue tracking of large-scale systems,” International Journal of Electrical Power & Energy Systems, vol. 172, p. 111310, 2025.
- [32]I. Ponce and F. Milano, “Local synchronization of power system devices,” IEEE Transactions on Power Systems, vol. 40, no. 5, pp. 4194–4204, 2025.arxiv.org/abs/2407.02661