WorksPhysics and Astronomy
Versatile two-layer model for thermohydraulic prediction of microchannel heat sinks
Abstract
Three-dimensional conjugate heat-transfer simulations provide detailed predictions for microchannel heat sinks but can be computationally demanding when many geometries and operating conditions are evaluated. This study develops a versatile two-layer model (VTLM) that reduces the three-dimensional problem to two coupled two-dimensional fields while retaining the in-plane geometry of the flow passages and fins. Effects associated with the unresolved channel-height direction are incorporated through hydraulic and thermal closures that account for wall friction and the fluid- and fin-side contributions to interlayer heat transfer. The closures are evaluated from the representative channel geometry, flow-development condition, and fin configuration. The VTLM was assessed against three-dimensional reference models across broad ranges of channel aspect ratios and operating conditions, including uniform and nonuniform fin arrangements. Compared with the existing two-layer models, the VTLM showed improved overall agreement with the three-dimensional reference results. The results showed that prediction accuracy was governed mainly by the flow-development condition and channel aspect ratio, from which a conservative screening guideline was proposed for the examined straight-channel configurations. The assessment of finned expansion–contraction channels further supported the applicability of the VTLM to the investigated passages with abrupt width changes. Overall, the VTLM provides a reduced-dimensional framework for thermohydraulic analysis across the range of microchannel heat-sink configurations examined in this study without explicitly resolving the channel-height direction.
Introduction
Microchannel heat sinks are widely used for thermal management because their small characteristic dimensions and large heat-transfer area enable efficient heat removal from compact systems [1, 2, 3]. Their thermohydraulic behavior is inherently three-dimensional, as coolant flow and thermal development are coupled with heat conduction through the fins and substrate [4, 5, 6]. Geometric features such as interrupted or segmented fins further modify the local flow and thermal boundary-layer development, increasing the difficulty of accurate performance prediction [7, 8, 9]. Consequently, detailed analysis commonly relies on three-dimensional conjugate heat-transfer models that resolve both the fluid and solid domains.
Three-dimensional conjugate heat-transfer simulations can resolve the coupled fluid and solid fields in detail, but their computational cost becomes substantial when repeated evaluations are required for many geometries or operating conditions [10, 11, 12]. Physics-based reduced-dimensional modeling provides an alternative for applications requiring repeated thermohydraulic evaluations. In such models, the governing equations are averaged or approximated in the height direction, with additional terms introduced to account for unresolved out-of-plane momentum and heat-transfer effects [13, 14, 15]. These models retain conservation equations for the flow and temperature fields in a lower-dimensional physical domain while substantially reducing the computational cost.
Porous-medium and averaging approaches have been developed primarily for microchannel heat sinks composed of regular channel-fin arrays. In porous-medium formulations, the repeated channel-fin structure is homogenized as an equivalent porous domain, whereas averaging approaches describe its thermohydraulic behavior using spatially averaged momentum and energy equations [16, 17]. A subsequent formulation incorporated entrance effects by distinguishing between developed and developing-flow regimes and was assessed against a three-dimensional conjugate heat-transfer model [18]. These approaches provide efficient predictions by representing regularly arranged channels and fins through averaged geometric and thermohydraulic properties.
Reduced-dimensional models have also been developed to retain more complex in-plane channel and fin arrangements. Harpole and Enginer formulated an early two-dimensional flow and thermal model for a manifold microchannel heat exchanger, in which unresolved viscous resistance and fluid-solid heat exchange were represented through effective relations [19]. Mandel et al. subsequently developed a 2.5-D model for manifold microchannels that retained the inertial terms and incorporated developing-flow effects within a two-dimensional computational representation. The model substantially reduced the computational cost relative to fully three-dimensional simulations, although its accuracy deteriorated when secondary three-dimensional flow structures became significant [20]. Kamal
Nomenclature
| Symbol | Description | Symbol | Description |
| fluid velocity vector (m/s) | dimensionless fin heat-transfer parameter | ||
| in-plane position vector (m) | normalized streamwise fin length | ||
| AR | channel aspect ratio, | normalized transverse fin width | |
| ER | expansion ratio, | dynamic viscosity (Pa · s) | |
| Nu | Nusselt number | computational region | |
| Po | Poiseuille number | density (kg/m) | |
| Pr | Prandtl number | wall shear stress (Pa) | |
| Re | Reynolds number | wall-friction allocation fraction | |
| area (m) | fin excess temperature (K) | ||
| coefficients in the Poiseuille-number correlation | dimensionless fin-height parameter | ||
| specific heat capacity (J/(kg · K)) | Subscripts | ||
| wall-friction coefficient (Pa · s/m) | 1 | Layer 1 | |
| representative-height closure coefficients | 2 | Layer 2 | |
| hydraulic diameter (m) | ax | axial | |
| relative difference in the quantity (%) | b | fin base | |
| Darcy friction factor | bt | bottom surface | |
| common channel and fin height (m) | c | characteristic | |
| heat-transfer coefficient (W/(m · K)) | dev | developing flow | |
| thermal conductivity (W/(m · K)) | e | entrance | |
| length (m) | eff | effective | |
| dimensionless hydraulic flow-development length | f | fluid | |
| streamwise length used for the hydraulic closure (m) | fin | fin | |
| number of mesh elements | fp | flow passage | |
| fin parameter (m) | GW | geometry-weighted | |
| number of fins | in | inlet | |
| blending exponent in the representative-height closure | int | interlayer | |
| blending exponent in the Nusselt-number correlation | io | inlet and outlet | |
| blending exponent in the Poiseuille-number correlation | ref | reference | |
| perimeter (m) | s | solid | |
| pressure (Pa) | side | fin side | |
| heat flow (W) | SW | shear-weighted | |
| heat flux (W/m) | tb | top and bottom walls | |
| thermal resistance (K/W) | top | representative Layer 1 height | |
| temperature (K) | wf | wall friction | |
| representative height or thickness (m) | fin index | ||
| characteristic velocity (m/s) | streamwise direction | ||
| width (m) | transverse direction | ||
| entrance-region weighting factor | Superscripts | ||
| dimensionless thermal flow-development length | 3D | three-dimensional reference model | |
| coordinate measured from the fin base (m) | tot | total | |
| Greek symbols | VTLM | versatile two-layer model | |
| rectangular-channel aspect ratio |
and Dewan adopted a two-dimensional model for high-aspect-ratio interrupted microchannels after comparing its predictions with three-dimensional simulations [21]. In this case, the validity of the reduced representation relied on sufficiently high aspect ratios to limit variations in the unresolved direction. These studies demonstrate that planar computational models can accommodate relatively complex in-plane flow passages, although their applicability depends on the significance of the unresolved three-dimensional effects.
The need for computationally efficient reduced-dimensional models is particularly pronounced in topology optimization (TO), where the governing equations must be solved repeatedly as the fluid–solid distribution evolves. TO provides a systematic approach for generating flow-channel layouts by optimizing the spatial distribution of fluid and solid regions within a prescribed design domain [22]. Following the density-based formulation introduced by Borrvall and Petersson for Stokes flow [23], fluid topology optimization was extended to more general flow problems [24, 25, 26] and coupled thermal-fluid systems [27, 28, 29]. To reduce the computational cost associated with these repeated analyses, pseudo-three-dimensional and two-layer models have also been introduced for heat-sink design and topology optimization. In these models, the three-dimensional conjugate heat-transfer problem is reduced to coupled planar domains, while effects associated with the unresolved direction are represented through simplifying assumptions or effective relations. Haertel et al. developed a pseudo-three-dimensional model comprising two thermally coupled planar layers: a conducting base layer and a thermofluid design layer [30]. Comparison with a three-dimensional model showed that the omission of top- and bottom-wall friction introduced systematic differences in the predicted flow rate, although the thermal-resistance predictions remained in good agreement. A related formulation was adopted by Zeng and Lee for heat-sink topology optimization, and the resulting designs were subsequently assessed using three-dimensional simulations and experiments [31]. Yan et al. proposed a two-layer model for the topology optimization of microchannel heat sinks based on a plane-flow assumption, in which coupled fluid and solid thermal fields were used to approximate three-dimensional conjugate heat transfer [32]. Zhao et al. [33] introduced a multilayer thermofluid model in which adaptive temperature profiles in the height direction were employed to better represent out-of-plane heat-transfer effects. A related multilayer formulation was later used for heat-sink topology optimization under turbulent forced-convection conditions [34]. More recently, Jia et al. incorporated a multilayer representation into a topology optimization framework for microfluidic heat sinks with non-Newtonian fluids [35].
A useful distinction among the reduced-dimensional modeling approaches reviewed above is how the in-plane channel-fin geometry is represented. Porous-medium and averaging approaches replace the detailed channel-fin structure with an equivalent averaged representation and have been developed mainly for regularly arranged channel-fin configurations [16, 17, 18]. By contrast, several reduced-dimensional formulations retain the in-plane flow-passage geometry within the computational domain, including two-layer models used in heat-sink design and topology optimization [30, 31, 32]. However, their applicability tends to depend on the channel-height regime. Models based on a plane-flow assumption are most appropriate for low-aspect-ratio channels, where variations across the channel height remain limited [32, 33, 34, 35]. In contrast, the limitation associated with neglecting top- and bottom-wall friction becomes less significant at high aspect ratios, where the relative contribution of these walls to the total hydraulic resistance is reduced [30, 31]. Simplified thermal treatments may likewise lose accuracy as the channel geometry and thermal-development condition vary [31].
The applicability of existing reduced-dimensional formulations is generally limited to particular aspect-ratio regimes. A formulation capable of retaining the in-plane geometry while accommodating a wide range of aspect ratios remains needed, and its applicable range should be clearly established. To address this need, the present study develops a versatile two-layer model (VTLM) for thermohydraulic prediction of microchannel heat sinks over a broad range of channel aspect ratios. The original three-dimensional conjugate heat-transfer problem is represented by two coupled two-dimensional fields: one describing the in-plane fluid and fin regions and the other accounting for heat conduction near the fin-base junction and within the substrate. The VTLM accounts for the unresolved height-direction effects through three closure models evaluated according to the representative geometry and development conditions. The wall-friction closure accounts for momentum loss at the unresolved top and bottom walls, the fluid-side heat-transfer closure incorporates flow-passage geometry and thermal development, and the fin-side effective heat-transfer closure represents both axial fin conduction and lateral heat transfer to the coolant. The prediction accuracy and applicable range of the VTLM are systematically assessed against three-dimensional reference simulations over a wide range of channel aspect ratios and fin configurations. In addition, the models of Yan et al. [32] and Zeng and Lee [31] are compared at representative aspect ratios to evaluate the VTLM relative to existing two-layer formulations. Although both models were developed in the context of topology optimization, the present comparison concerns only their underlying thermohydraulic analysis formulations.
The remainder of this paper is organized as follows. Section 2 presents the assumptions, governing equations, and thermohydraulic closure models of the VTLM. Section 3 describes the numerical implementation of the VTLM and the three-dimensional simulations. Section 4 presents the numerical assessment for different fin-array configurations and flow-passage geometries and discusses the applicability of the proposed model. Finally, Section 5 summarizes the conclusions.
Mathematical model
Assumptions
As illustrated in Figure 1, the VTLM reduces the three-dimensional conjugate heat-transfer domain to two coupled planar fields. Layer 1 resolves the in-plane coolant and fin regions, whereas Layer 2 represents heat conduction near the fin–base junction and within the substrate. Variations in the channel-height direction are not resolved explicitly. Instead, their effects on momentum loss and heat exchange between the two layers are incorporated through the closure models described in Section 2.3. The formulation is developed under the following conditions:
Figure 1. Schematic representation of the VTLM. The three-dimensional microchannel heat sink is reduced to two coupled planar fields: Layer 1, which contains the fluid and fin regions ( and ), and Layer 2, which represents the fin-base junction and substrate region. The representative height associated with Layer 1 and the substrate thickness are denoted by and , respectively.
The coolant flow is steady, laminar, incompressible, and Newtonian. The thermophysical properties of the coolant and solid materials are assumed to be constant.
The in-plane channel-fin geometry is extruded uniformly in the height direction. This assumption excludes configurations with spatially varying channel or fin heights, such as tapered or stepped profiles.
The configurations have a predominant mean flow direction, with the inlet and outlet located on opposite sides of the computational domain. This direction is used to define the representative streamwise dimensions and flow-development lengths required by the closure models.
Heat conduction along the fin height is represented by a one-dimensional fin model with an adiabatic tip [36].
Governing equations
The VTLM is formulated on the two-dimensional plane shown in Figure 1. Layer 1 is divided into the fluid region and the fin region , whereas Layer 2 spans the entire in-plane footprint and represents the fin-base junction and the underlying substrate. The velocity and pressure fields are solved only in . The temperatures in the fluid and fin regions of Layer 1 are denoted by and , respectively, while denotes the temperature in Layer 2. The common channel and fin height is denoted by , while and denote the representative height associated with Layer 1 and the substrate thickness, respectively. The former also specifies the representative height of Layer 1 in the fin-side closure, whereas the latter corresponds to the substrate thickness. All spatial differential operators appearing below act in the in-plane directions. For steady incompressible flow, mass conservation in the fluid region is expressed as
where is the fluid velocity. The corresponding momentum equation is
where is the fluid density, is the dynamic viscosity, and is the pressure. The final term represents the momentum loss associated with viscous shear on the unresolved top and bottom channel walls. The wall-friction coefficient is evaluated using the closure model presented in Section 2.3.1. The energy equation in the fluid region of Layer 1 is given by
where and are the specific heat and thermal conductivity of the fluid. The coefficient represents the effective heat transfer between the fluid region of Layer 1 and Layer 2. Within the fin region, heat transport in Layer 1 is governed by
where is the thermal conductivity of the solid material and is the fin-side effective heat-transfer coefficient. The latter accounts for heat conduction along the fin height and heat transfer from the fin side surfaces, as described in Section 2.3.3. To express the coupling with Layer 2 in a unified form, the Layer 1 temperature and the interlayer coefficient are defined as
where denotes the in-plane position vector. The energy balance in Layer 2 is then written as
where is the heat flux supplied at the bottom surface. The second term represents the applied heat input distributed over the thickness , whereas the third term describes heat exchange between the two planar fields. When the bottom-surface temperature is required, the in-plane temperature variation is already represented by the Layer 2 temperature field. The unresolved temperature drop across the substrate thickness is reconstructed locally using a one-dimensional conduction relation, following Zeng and Lee [31]:
Thermohydraulic closure models
Wall-friction closure
The in-plane momentum equation in Layer 1 does not resolve the velocity gradients normal to the top and bottom channel walls. The associated viscous resistance is represented by the linear momentum sink . By matching this sink with the pressure gradient of laminar flow through a rectangular duct, the wall-friction coefficient is expressed as
where Po is the Poiseuille number, and denotes the fraction of the total wall friction attributed to the unresolved top and bottom walls. For a rectangular channel of height and width , hydraulic diameter can be expressed as follows:
To account for both hydrodynamically developing and fully developed flow, the Poiseuille number is evaluated using the composite correlation proposed by Muzychka and Yovanovich [37], expressed in the Churchill–Usagi form [38]:
where is the Darcy friction factor, , , and
where denotes the streamwise length of the flow-passage segment over which the hydraulic closure is evaluated, and is the characteristic velocity, defined as the mean velocity at the inlet. The fully developed contribution is obtained from the rectangular-duct relation of Shah and London [39]:
where denotes the cross-sectional aspect ratio, defined as
Consequently, Eq. (10) adjusts the predicted friction according to both the duct geometry and hydrodynamic development. The fraction is evaluated by blending the geometry-weighted estimate for the entrance region with the shear-weighted estimate for fully developed flow as follows:
where is the entrance-region weighting factor and is the estimated hydrodynamic entrance length [40]. Near the inlet, the wall-shear profile has not yet approached its fully developed distribution. Therefore, the top- and bottom-wall contribution is approximated from the corresponding fraction of the wetted perimeter:
Farther downstream, the allocation between the two pairs of opposing walls is instead determined from their mean shear stresses.
stresses. Let and denote the magnitudes of the mean shear stresses on the wall groups whose individual lengths are and , respectively. Since the top and bottom surfaces belong to the -wall group, their fully developed contribution is written as
Following the rectangular-duct solution reported by Delplace [41], the mean shear-stress magnitudes are evaluated from the following expressions:
and
where is the pressure drop over the streamwise length , and the summations are taken over the positive odd integers .
For channels containing fin arrays, the flow passage cannot be uniquely assigned a rectangular cross-section. Although the hydraulic resistance associated with the fin boundaries is resolved directly in Layer 1, the closure still requires a representative rectangular cross-section to evaluate the top- and bottom-wall contribution. Accordingly, the flow passage is mapped to an area-preserving straight channel, as shown in Figure 2. Its effective width is evaluated as where is the flow-passage area of the corresponding segment. The associated aspect ratio and hydraulic diameter are
Figure 2. Equivalent straight-channel representation used in the wall-friction closure for a fin-array passage: (a) original fin-array passage and (b) equivalent straight channel.
All quantities in the wall-friction closure are then evaluated for the equivalent rectangular channel by replacing , , and with , , and , respectively. Accordingly, , , and are evaluated using . This equivalent representation provides the global geometric quantities required by the straight-channel friction closure.
Fluid-side heat transfer coefficient
The fluid-side contribution to the interlayer heat exchange is evaluated by distinguishing the portions associated with the fin sidewalls and the flow-passage surface. These two portions generally have different streamwise thermal-development lengths and are treated separately before being combined into a single coefficient. The area-averaged fluid-side heat transfer coefficient is defined as
where and denote the heat-transfer coefficients assigned to the fin and flow-passage contributions, respectively. The quantity denotes the total in-plane fin area. Both coefficients are evaluated using a laminar developing-flow correlation for a rectangular channel, with separate thermal-development lengths for the fin-sidewall and flow-passage contributions:
The corresponding dimensionless thermal-development lengths are shown below:
where is the Prandtl number, while and denote the representative streamwise fin length and the streamwise flow-passage length, respectively. The developing-flow Nusselt number is calculated using the correlation proposed by Muzychka and Yovanovich [42]:
where is the fully developed rectangular-duct coefficient defined in Eq. (12), is the channel aspect ratio defined in Eq. (13), and is the blending exponent. The correlation was originally formulated for a rectangular channel heated on all four walls. In the present model, it is applied as an approximation to the three-sided heating configuration.
For a uniform fin array, is the streamwise fin length. For a nonuniform fin array, the geometry is mapped to an equivalent uniform fin array, as illustrated in Figure 3, and is evaluated as follows:
Figure 3. Equivalent uniform fin-array representation for evaluating the fin-side thermal-development length: (a) nonuniform fin array and (b) equivalent uniform fin array characterized by .
where and denote the total in-plane fin perimeter and the sum of the streamwise fin lengths, respectively.
Fin-side effective heat transfer coefficient
The fluid-side coefficient introduced in § 2.3.2 describes heat transfer from the fin sidewalls to the coolant but does not account for heat conduction within the fin. A fin-side effective heat transfer coefficient is introduced to represent the combined influence of axial fin conduction and lateral heat transfer to the fluid.
Figure 4 illustrates the corresponding heat-flow representation. Heat entering the fin from Layer 2 is denoted by . A portion of this heat is transferred laterally to the fluid as , while the remaining axial heat flow reaches the representative Layer 1 height . The fin-side effective heat transfer coefficient is defined from this remaining heat flow as
Figure 4. Schematic of the fin-side thermal closure. Heat entering the fin from Layer 2 is divided into lateral heat transfer to the coolant and the remaining axial heat flow evaluated at the representative height .
where is the temperature at the fin-base junction, and is the fin temperature at the representative height. Under the uniform-extrusion assumption, also serves as the total cross-sectional area normal to heat conduction along the fin height. Here, denotes the representative height of Layer 1 and is an effective closure parameter rather than a physical geometric dimension.
Using a one-dimensional fin approximation with constant properties and an adiabatic fin tip, Eq. (25) can be written in closed form as
where
Here, denotes the common channel and fin height. The coefficient is evaluated using the fluid-side closure described in § 2.3.2. The detailed derivation of Eqs. (26) and (27) is provided in Appendix § 6.
The dimensionless parameter characterizes lateral heat transfer relative to axial conduction within the fin. Because the effective location of the interlayer heat exchange changes with , the representative height is not prescribed as a fixed fraction of . As illustrated in Figure 5, weak lateral heat transfer allows heat to travel farther toward the fin tip and gives a larger . By contrast, strong lateral heat transfer concentrates the effective exchange closer to the fin base and leads to a smaller . The representative-height ratio is evaluated using the following Churchill–Usagi-type blending relation:
Figure 5. Effect of the lateral heat-transfer intensity on the representative Layer 1 height: (a) weak lateral heat transfer with small and (b) strong lateral heat transfer with large . Increasing shifts the representative Layer 1 height toward the fin base.
where closure parameters are set to , , and . These values were calibrated using the baseline straight-channel dataset and were retained without further adjustment in the subsequent cases. For configurations without fins, the solid region is absent from Layer 1. Accordingly, the fin-side coefficient and the representative-height relation in Eq. (28) are not used. Interlayer heat transfer is represented solely by the fluid-side coefficient .
Numerical implementation
The VTLM and the corresponding three-dimensional reference model were implemented using the finite-element method in COMSOL Multiphysics 6.1. In both models, the velocity and pressure fields were solved using the Laminar Flow interface, while conjugate heat transfer in the fluid and solid regions was evaluated using the Heat Transfer in Solids and Fluids interface. For the VTLM, Layer 1 and Layer 2 were constructed as separate two-dimensional components, with Layer 2 modeled using the Heat Transfer in Solids interface. The velocity and pressure fields were discretized using equal-order first-order finite elements (P1+P1), while linear finite elements were used for the temperature field. Consistent streamline-diffusion and crosswind-diffusion stabilization were applied to both the flow and heat-transfer equations. The wall-friction sink term was introduced into the Layer 1 momentum equation, and the interlayer heat-transfer terms were applied with opposite signs in the energy equations of the two layers, using and in the flow-passage and fin regions, respectively. The three-dimensional reference model was resolved directly without reduced-dimensional hydraulic or thermal closure terms. All calculations were performed under stationary conditions. The same material properties and boundary conditions were imposed in the VTLM and three-dimensional calculations for each case. A relative solver tolerance of was used throughout the study. All simulations were performed on the same workstation equipped with a 13th Gen Intel Core i7-13700 processor. The global energy balance was also verified by comparing the imposed heat input with the coolant enthalpy increase, , confirming that the energy imbalance was negligible for the conjugate heat-transfer cases.
Results and discussion
Assessment of the three-dimensional reference model
Before its use as the reference model for evaluating the VTLM, the three-dimensional numerical implementation was examined through a mesh-independence study and comparison with analytical solutions. Both tests employed a straight square channel containing only the fluid domain. No solid domain and conjugate heat transfer were included.
The channel had a width and height of mm and a length of mm. For this benchmark, the streamwise development length in was taken as the full channel length, . Water was used as the working fluid, with kg/m, Pa s, W/(m K), and J/(kg K). A uniform velocity and temperature were prescribed at the inlet, while the outlet pressure was set to zero. No-slip conditions were imposed on all channel walls, which were subjected to a uniform heat flux. The hydraulic and thermal predictions were evaluated using the Darcy friction factor and the mean Nusselt number:
where is the mean heat transfer coefficient over the heated walls. For , the relative difference from a reference value was defined as
where is the percentage relative difference in , and denotes the reference value selected for each comparison.
Mesh-independence study
Mesh sensitivity was examined at and 1000 using structured hexahedral meshes successively refined in the streamwise and cross-sectional directions. These two Reynolds numbers represent different levels of flow and thermal development. The relative difference was evaluated using Eq. (30), where denotes the result obtained using the current mesh and denotes that obtained using the preceding coarser mesh.
The mesh-independence results are summarized in Table 1. The variations in both and Nu decreased progressively with increasing mesh resolution. For the mesh, the changes relative to the preceding mesh were within 1.5% at both Reynolds numbers. This mesh was adopted for the subsequent straight-channel calculations.
| \multicolumn{4}{c}{Re = 10} | \multicolumn{4}{c}{Re = 1000} | |||||||||
| (%) | Nu | (%) | (%) | Nu | (%) | |||||
| 4 | 120 | 4 | 5.471 | – | 5.738 | – | 0.116 | – | 19.281 | – |
| 6 | 180 | 6 | 5.638 | 3.04 | 5.584 | -2.69 | 0.119 | 3.14 | 17.576 | -8.84 |
| 8 | 240 | 8 | 5.736 | 1.74 | 5.546 | -0.68 | 0.122 | 2.29 | 16.888 | -3.91 |
| 10 | 300 | 10 | 5.801 | 1.15 | 5.533 | -0.24 | 0.124 | 1.64 | 16.519 | -2.18 |
| 12 | 360 | 12 | 5.849 | 0.83 | 5.527 | -0.10 | 0.125 | 1.19 | 16.298 | -1.34 |
| 14 | 420 | 14 | 5.887 | 0.64 | 5.525 | -0.04 | 0.127 | 0.90 | 16.152 | -0.90 |
| 16 | 480 | 16 | 5.917 | 0.51 | 5.524 | -0.02 | 0.127 | 0.71 | 16.050 | -0.63 |
Table 1. Mesh-independence results for the straight-channel benchmark. The signed errors indicate changes relative to the preceding coarser mesh.
Comparison with benchmark solutions
The accuracy of the mesh-independent model was evaluated by comparing the predicted friction factor and Nusselt number with the developing-flow solutions of Muzychka and Yovanovich [37, 42]. Calculations were performed over the range . The analytical values of and Nu were obtained from Eqs. (10) and (23), respectively. For this comparison, and in Eq. (30) denote the three-dimensional and analytical results, respectively.
Table 2 compares the numerical and analytical values. Good agreement was obtained throughout the investigated Reynolds-number range, with maximum absolute differences of 0.82% for and 0.85% for Nu. These results confirm that the three-dimensional implementation accurately predicts both the hydraulic resistance and developing convective heat transfer in the straight channel.
| Re | \multicolumn{2}{c}{Analytical} | \multicolumn{2}{c}{3D model} | \multicolumn{2}{c}{Error (%)} | |||||
| Nu | Nu | |||||||
| 10 | 1.500 | 0.2152 | 5.802 | 4.176 | 5.849 | 4.177 | 0.82 | 0.04 |
| 100 | 0.150 | 0.0215 | 0.671 | 6.521 | 0.668 | 6.514 | -0.47 | -0.10 |
| 200 | 0.075 | 0.0108 | 0.380 | 8.026 | 0.379 | 8.010 | -0.16 | -0.20 |
| 400 | 0.038 | 0.0055 | 0.228 | 10.173 | 0.229 | 10.134 | 0.47 | -0.38 |
| 600 | 0.025 | 0.0036 | 0.173 | 11.834 | 0.174 | 11.770 | 0.36 | -0.54 |
| 800 | 0.019 | 0.0027 | 0.144 | 13.246 | 0.144 | 13.154 | -0.03 | -0.69 |
| 1000 | 0.015 | 0.0022 | 0.126 | 14.499 | 0.125 | 14.376 | -0.41 | -0.85 |
Table 2. Comparison of the analytical and three-dimensional results for the straight-channel benchmark.
Straight-channel flow and conjugate heat transfer
A straight-channel conjugate heat-transfer case was used as the baseline configuration for calibrating the representative-height closure in Eq. (28). Unlike the fluid-only benchmark in § 4.1, this configuration includes heat conduction through a solid fin and a heated base. Figure 6(a) shows the three-dimensional domain, while Figure 6(b) shows its two-layer representation. The channel consists of inlet and outlet sections of length and a central section of length containing the fin and heated base. The wall-friction closure was evaluated separately for these streamwise sections, with for the inlet and outlet sections and for the central section. Unless otherwise stated, the values reported in the subsequent conjugate heat-transfer assessments refer to the central section and are evaluated using . In the symmetry-reduced domain, both the flow passage and the fin have a transverse width of .
Figure 6. Computational domains for the baseline straight-channel conjugate heat-transfer case: (a) symmetry-reduced three-dimensional model and (b) corresponding VTLM representation.
The channel length and width were mm and mm, respectively. The substrate thickness was fixed at mm for all conjugate heat-transfer cases considered in this study. The water properties were identical to those used in § 4.1, and copper with W/(m K) was assigned to the fin and heated base. The inlet temperature was fixed at K, and a uniform heat flux of kW/m was applied at the bottom surface. The Reynolds number was maintained at . The geometric aspect ratio was defined as and varied from 0.2 to 5.0 by changing while keeping fixed.
The hydraulic comparison was performed using the Darcy friction factor defined in Eq. (29), with the relative difference evaluated using Eq. (30). For the thermal comparison, the area-averaged bottom-surface temperature was adopted as the primary thermal metric, consistent with previous two-layer models for microchannel heat sinks [31, 32]. To avoid a temperature-relative error that depends on the chosen temperature reference, the thermal discrepancy was defined as the signed difference
The calibration results are summarized in Table 3. Across the baseline dataset, the hydraulic discrepancy remains within 4.62%, while the signed bottom-temperature difference ranges from to 1.32 °C. At low aspect ratios, the VTLM slightly overpredicts and underpredicts . The bottom-temperature difference changes sign as AR increases, whereas the hydraulic prediction remains slightly higher than the three-dimensional value in all cases. The parameters in Eq. (28) were determined from this baseline dataset and retained without readjustment in the remaining cases. Accordingly, these baseline cases are treated as calibration cases and are not included in the subsequent assessment of the VTLM prediction accuracy.
| AR | (°C) | (°C) | (%) | (°C) | ||
| 0.2 | 0.206 | 36.49 | 0.213 | 35.03 | 3.44 | -1.46 |
| 0.3 | 0.202 | 38.38 | 0.207 | 37.30 | 2.30 | -1.08 |
| 0.4 | 0.202 | 39.08 | 0.204 | 38.46 | 1.03 | -0.62 |
| 0.5 | 0.205 | 39.10 | 0.206 | 38.77 | 0.46 | -0.33 |
| 1.0 | 0.225 | 36.34 | 0.230 | 36.85 | 2.10 | 0.51 |
| 2.0 | 0.259 | 31.55 | 0.268 | 32.67 | 3.50 | 1.12 |
| 3.0 | 0.276 | 29.04 | 0.288 | 30.34 | 4.28 | 1.30 |
| 4.0 | 0.288 | 27.63 | 0.301 | 28.95 | 4.55 | 1.32 |
| 5.0 | 0.295 | 26.77 | 0.309 | 28.04 | 4.62 | 1.27 |
Table 3. Comparison of the VTLM and three-dimensional reference results for the baseline straight-channel conjugate heat-transfer cases used for calibration.
To further compare the behavior of the VTLM with existing reduced-dimensional approaches, the two-layer models of Zeng and Lee [31] and Yan et al. [32] were evaluated at representative channel aspect ratios. The predicted values are summarized in Table 4, and the corresponding hydraulic and thermal prediction differences from the three-dimensional reference results are shown in Figure 7. Because these baseline configurations were used only to calibrate the representative-height thermal closure, the hydraulic comparison remains independent of that calibration. Therefore, the thermal comparison is included to illustrate the behavior of the different reduced-dimensional formulations under the same baseline conditions rather than to provide an independent assessment of the VTLM.
| AR | ||||||||
| 3D reference | 3D reference | VTLM | VTLM | Zeng and Lee | Zeng and Lee | Yan et al. | Yan et al. | |
| 0.2 | 0.206 | 36.49 | 0.213 | 35.03 | 0.019 | 46.70 | 0.163 | 46.89 |
| 1.0 | 0.225 | 36.34 | 0.230 | 36.85 | 0.108 | 40.60 | 0.157 | 43.70 |
| 5.0 | 0.295 | 26.77 | 0.309 | 28.04 | 0.254 | 27.90 | 0.250 | 28.65 |
Table 4. Comparison of the VTLM and existing two-layer models with the three-dimensional reference results at representative channel aspect ratios. The bottom-surface temperature is given in °C.

Figure 7. Prediction differences from the three-dimensional reference results for the VTLM and existing two-layer models at AR = 0.2, 1.0, and 5.0: (a) relative difference in the Darcy friction factor and (b) area-averaged bottom-temperature difference.
The hydraulic comparison in Figure 7(a) shows the substantial differences among the models. At AR = 0.2, the VTLM predicts the Darcy friction factor with 3.40% of the three-dimensional result, whereas the models of Zeng and Lee and Yan et al. underpredict it by 90.78% and 20.87%, respectively. The large discrepancy of the Zeng and Lee model is consistent with its omission of the friction associated with the unresolved top and bottom walls, whose contribution becomes particularly important at low aspect ratios. The Yan et al. model also shows appreciable underprediction because its plane-flow formulation does not account for hydrodynamic development in the height direction. By contrast, the VTLM incorporates both effects through its hydraulic closure. As AR increases, the errors of the existing models decrease substantially because the relative contribution of the top and bottom wall friction becomes smaller.
The thermal comparison in Figure 7(b) shows a similar reduction in model differences with increasing aspect ratio. At AR = 0.2, the VTLM gives a bottom-temperature difference of °C, whereas the models of Zeng and Lee and Yan et al. overpredict the bottom temperature by 10.21 °C and 10.40 °C, respectively. The larger discrepancies of the latter are associated with their simplified treatment of the height-direction thermal behavior, using either an effective thermal-resistance representation or a plane-flow-based formulation. In contrast, the VTLM evaluates its thermal closures from the representative geometry and development condition. At AR = 1.0, the VTLM gives a bottom-temperature difference of only 0.51 °C, compared with 4.26 °C and 7.36 °C for the Zeng and Lee and Yan et al. models, respectively. At AR = 5.0, all three models give differences below 2 °C, indicating that the discrepancies among the reduced-dimensional formulations become less pronounced as the aspect ratio increases.
The computational cost of the VTLM was also compared with that of the three-dimensional reference model using the representative straight-channel cases. The solution times reported in Table 5 correspond to the stationary solution process. The VTLM substantially reduces the computational cost relative to the three-dimensional model, with solution-time speedups ranging from approximately 20 to 171 over the examined aspect ratios. The computational advantage becomes more pronounced at larger aspect ratios, as the VTLM avoids explicit discretization in the channel-height direction.
| AR | 3D DOFs | VTLM DOFs | (s) | (s) | Speedup |
| 0.2 | 749525 | 25469 | 137 | 7 | 19.6 |
| 1.0 | 749525 | 25469 | 138 | 4 | 34.5 |
| 5.0 | 3373577 | 25469 | 682 | 4 | 170.5 |
Table 5. Computational cost of the VTLM and three-dimensional reference model for representative straight-channel conjugate heat-transfer cases.
Fin arrays in a straight channel
The straight-channel assessment was extended from the baseline configuration shown in Figure 6 to channels containing uniformly arranged fin arrays. The fins were placed within the central heated section of length and were assigned identical rectangular footprints. The streamwise fin length and transverse fin width are denoted by and , respectively, and their dimensionless values are defined as
The numbers of fins in the streamwise and transverse directions are denoted by and , respectively. In each direction containing multiple fins, the fins were uniformly spaced. The channel dimensions, material properties, and boundary conditions were the same as those used for the straight-channel conjugate heat-transfer case. The VTLM predictions were compared with the corresponding three-dimensional results using and . The hydraulic discrepancy was evaluated using the relative difference , while the thermal discrepancy was quantified by the signed bottom-temperature difference.
The uniform fin-array cases were divided into the three groups illustrated in Figure 8. Transverse fin arrays have a single streamwise fin section, and , while the transverse fin number and width are varied. Streamwise segmented fin arrays have and , allowing the effects of segment number and streamwise fin length to be examined. Two-directional fin arrays have and , providing configurations in which the flow passage is subdivided in both in-plane directions.
Figure 8. Uniform fin-array groups considered in the straight-channel assessment. Only the central heated section is shown: (a) transverse fin arrays with and , (b) streamwise segmented fin arrays with and , and (c) two-directional fin arrays with and .
Uniform transverse fin arrays
Uniform transverse fin arrays were examined using the configuration shown in Figure 8(a). For these cases, and , so that each fin extends over the full heated-section length. The transverse arrangement was varied through the number of fins and the normalized fin width . Cases UT11–UT14 vary the hydraulic diameter at fixed AR = 1 and with the same normalized single-fin configuration to examine the influence of separately from that of the Reynolds number. The uniform transverse fin-array cases and the corresponding results are summarized in Table 6 for AR = 1 and in Table 7 for AR = 0.2 and 5.0.
| Case | Re | AR | (%) | (°C) | (°C) | (°C) | |||||
| UT1 | 100 | 1.0 | 0.0750 | 1 | 0.10 | 1.338 | 1.374 | 2.72 | 32.43 | 32.72 | 0.29 |
| UT2 | 100 | 1.0 | 0.0750 | 1 | 0.60 | 9.517 | 9.223 | -3.09 | 28.05 | 28.63 | 0.58 |
| UT3 | 100 | 1.0 | 0.0750 | 3 | 0.05 | 3.994 | 3.856 | -3.47 | 25.05 | 25.63 | 0.58 |
| UT4 | 100 | 1.0 | 0.0750 | 3 | 0.10 | 6.767 | 6.502 | -3.93 | 24.40 | 24.99 | 0.59 |
| UT5 | 100 | 1.0 | 0.0750 | 5 | 0.05 | 11.692 | 11.105 | -5.02 | 23.41 | 23.89 | 0.48 |
| UT6 | 100 | 1.0 | 0.0750 | 5 | 0.10 | 37.903 | 36.045 | -4.90 | 22.89 | 23.32 | 0.43 |
| UT7 | 500 | 1.0 | 0.0150 | 1 | 0.10 | 0.342 | 0.381 | 11.49 | 26.67 | 27.35 | 0.68 |
| UT8 | 500 | 1.0 | 0.0150 | 1 | 0.40 | 0.861 | 0.857 | -0.47 | 24.94 | 25.84 | 0.90 |
| UT9 | 500 | 1.0 | 0.0150 | 3 | 0.05 | 0.890 | 0.898 | 0.85 | 23.00 | 23.50 | 0.50 |
| UT10 | 500 | 1.0 | 0.0150 | 5 | 0.10 | 8.221 | 7.668 | -6.72 | 21.37 | 21.75 | 0.38 |
| UT11 | 500 | 1.0 | 0.0225 | 1 | 0.10 | 0.310 | 0.341 | 9.84 | 25.26 | 25.74 | 0.48 |
| UT12 | 500 | 1.0 | 0.0450 | 1 | 0.10 | 0.276 | 0.293 | 6.20 | 23.59 | 23.65 | 0.06 |
| UT13 | 100 | 1.0 | 0.2250 | 1 | 0.10 | 1.216 | 1.213 | -0.29 | 26.56 | 26.49 | -0.07 |
| UT14 | 100 | 1.0 | 0.0150 | 1 | 0.10 | 1.911 | 2.041 | 6.82 | 53.69 | 56.21 | 2.52 |
Table 6. Comparison of the VTLM and three-dimensional reference results for uniform transverse fin arrays at AR = 1.
| Case | Re | AR | (%) | (°C) | (°C) | (°C) | |||||
| UT15 | 100 | 0.2 | 0.225 | 1 | 0.20 | 1.016 | 1.051 | 3.44 | 34.65 | 33.21 | -1.44 |
| UT16 | 100 | 0.2 | 0.225 | 1 | 0.60 | 2.586 | 2.509 | -2.98 | 35.41 | 34.73 | -0.68 |
| UT17 | 500 | 0.2 | 0.045 | 1 | 0.20 | 0.291 | 0.260 | -10.65 | 27.24 | 26.95 | -0.29 |
| UT18 | 500 | 0.2 | 0.045 | 1 | 0.60 | 0.794 | 0.700 | -11.84 | 26.20 | 30.41 | 4.21 |
| UT19 | 100 | 0.2 | 0.225 | 3 | 0.05 | 1.263 | 1.273 | 0.79 | 29.23 | 27.96 | -1.27 |
| UT20 | 500 | 0.2 | 0.045 | 3 | 0.05 | 0.284 | 0.306 | 7.75 | 24.58 | 24.23 | -0.35 |
| UT21 | 500 | 0.2 | 0.045 | 3 | 0.15 | 0.631 | 0.618 | -2.06 | 23.97 | 23.84 | -0.13 |
| UT22 | 500 | 0.2 | 0.045 | 5 | 0.075 | 0.766 | 0.725 | -5.35 | 22.83 | 22.60 | -0.23 |
| UT23 | 100 | 5.0 | 0.045 | 1 | 0.20 | 3.360 | 3.422 | 1.85 | 26.03 | 26.82 | 0.79 |
| UT24 | 100 | 5.0 | 0.045 | 1 | 0.40 | 7.248 | 7.260 | 0.17 | 24.33 | 25.24 | 0.91 |
| UT25 | 500 | 5.0 | 0.009 | 1 | 0.20 | 0.784 | 0.806 | 2.81 | 24.08 | 24.71 | 0.63 |
| UT26 | 500 | 5.0 | 0.009 | 1 | 0.40 | 1.708 | 1.693 | -0.88 | 22.85 | 23.60 | 0.75 |
| UT27 | 500 | 5.0 | 0.009 | 1 | 0.60 | 5.483 | 5.320 | -2.97 | 22.15 | 22.85 | 0.70 |
| UT28 | 100 | 5.0 | 0.045 | 3 | 0.05 | 9.405 | 9.397 | -0.09 | 24.12 | 24.22 | 0.10 |
| UT29 | 500 | 5.0 | 0.009 | 3 | 0.05 | 2.019 | 2.010 | -0.45 | 22.80 | 23.11 | 0.31 |
| UT30 | 500 | 5.0 | 0.009 | 3 | 0.15 | 7.090 | 7.038 | -0.73 | 21.67 | 21.98 | 0.31 |
| UT31 | 500 | 5.0 | 0.009 | 5 | 0.075 | 10.478 | 10.601 | 1.17 | 21.51 | 21.74 | 0.23 |
Table 7. Comparison of the VTLM and three-dimensional reference results for uniform transverse fin arrays at AR = 0.2 and 5.0.
For AR = 1, the dominant change in prediction accuracy is associated with the flow-development condition. At , the maximum absolute hydraulic error and bottom-temperature difference are 5.02% and 0.59 °C, respectively. Reducing to 0.015 increases the hydraulic sensitivity, particularly for the weakly obstructed single-fin configuration UT7, whereas increasing the fin width or subdividing the solid region among multiple fins generally reduces this bias. The bottom-temperature differences remain within 0.90 °C for these AR = 1 configurations.
The aspect ratio and blockage distribution modify this dependence on . At AR = 0.2, combining a low flow-development length with a large localized blockage produces the largest discrepancy, as shown by Case UT18, with a hydraulic error of −11.84% and a bottom-temperature difference of 4.21 °C. Configurations with multiple narrower fins exhibit substantially smaller temperature differences than the single wide-fin case. By contrast, the AR = 5.0 cases remain thermally robust, with absolute bottom-temperature differences within 0.91 °C, even at . These comparisons show that governs the overall hydraulic accuracy, while the aspect ratio and localization of the transverse blockage influence the remaining temperature discrepancy.
Uniform streamwise segmented fin arrays
Uniform streamwise segmented fin arrays were examined using the configuration shown in Figure 8(b). The transverse fin number was fixed at and , while the full-length fin was divided into or 3 equal segments distributed uniformly within the heated section. The fin-array cases and corresponding results are summarized in Table 8.
| Case | Re | AR | (%) | (°C) | (°C) | (°C) | |||||
| S1 | 100 | 1.0 | 0.075 | 2 | 0.225 | 1.669 | 1.687 | 1.06 | 31.68 | 32.06 | 0.38 |
| S2 | 100 | 1.0 | 0.075 | 2 | 0.125 | 1.325 | 1.352 | 2.04 | 33.60 | 34.15 | 0.55 |
| S3 | 500 | 1.0 | 0.015 | 2 | 0.225 | 0.432 | 0.463 | 7.17 | 25.88 | 26.77 | 0.89 |
| S4 | 500 | 1.0 | 0.015 | 2 | 0.125 | 0.379 | 0.407 | 7.38 | 26.32 | 27.75 | 1.43 |
| S5 | 100 | 1.0 | 0.075 | 3 | 0.133 | 1.638 | 1.653 | 0.93 | 31.83 | 32.17 | 0.34 |
| S6 | 100 | 1.0 | 0.075 | 3 | 0.067 | 1.312 | 1.332 | 1.53 | 33.63 | 34.31 | 0.68 |
| S7 | 500 | 1.0 | 0.015 | 3 | 0.133 | 0.429 | 0.459 | 7.06 | 25.84 | 26.78 | 0.94 |
| S8 | 500 | 1.0 | 0.015 | 3 | 0.067 | 0.383 | 0.409 | 6.71 | 26.02 | 27.72 | 1.70 |
| S9 | 100 | 0.2 | 0.225 | 2 | 0.175 | 0.970 | 1.000 | 3.14 | 34.41 | 32.87 | -1.54 |
| S10 | 100 | 0.2 | 0.225 | 3 | 0.10 | 0.965 | 0.992 | 2.80 | 34.25 | 32.61 | -1.64 |
| S11 | 500 | 0.2 | 0.045 | 2 | 0.175 | 0.231 | 0.253 | 9.62 | 26.67 | 26.58 | -0.09 |
| S12 | 500 | 0.2 | 0.045 | 3 | 0.10 | 0.232 | 0.254 | 9.33 | 26.31 | 26.32 | 0.01 |
| S13 | 100 | 5.0 | 0.045 | 2 | 0.175 | 2.844 | 2.904 | 2.10 | 27.35 | 27.87 | 0.52 |
| S14 | 100 | 5.0 | 0.045 | 3 | 0.10 | 2.775 | 2.832 | 2.05 | 27.77 | 28.13 | 0.36 |
| S15 | 500 | 5.0 | 0.009 | 2 | 0.175 | 0.717 | 0.732 | 2.04 | 24.71 | 25.35 | 0.64 |
| S16 | 500 | 5.0 | 0.009 | 3 | 0.10 | 0.718 | 0.729 | 1.51 | 24.84 | 25.51 | 0.67 |
Table 8. Comparison of the VTLM and three-dimensional reference results for uniform streamwise segmented fin arrays.
Across the streamwise segmented arrays, reducing has a greater influence on the VTLM accuracy than varying the segment number or length. At AR = 1, the maximum hydraulic error increases from 2.04% at to 7.38% at , while the absolute bottom-temperature differences remain within 1.70 °C. Paired cases with and 3 give similar results when their segment dimensions are comparable, indicating that additional streamwise segmentation does not cause a systematic deterioration.
The aspect-ratio comparisons support the same interpretation. At AR = 0.2, reducing from 0.225 to 0.045 increases the hydraulic error to approximately 9.5%, while the absolute bottom-temperature differences remain within 1.64 °C. At AR = 5.0, the hydraulic errors remain within 2.10%, and the absolute bottom-temperature differences remain within 0.67 °C, even at . Thus, the prediction differences are governed primarily by the flow-development condition and channel aspect ratio, with no distinct limitation attributable to streamwise segmentation.
Uniform two-directional fin arrays
Uniform two-directional fin arrays were examined using the configuration shown in Figure 8(c). In these cases, both and exceed unity, and the fluid region is divided into multiple passages in the streamwise and transverse directions. The uniform two-directional fin-array cases and corresponding results are summarized in Table 9 for AR = 1 and in Table 10 for AR = 0.2 and 5.0.
| Case | Re | AR | (%) | (°C) | (°C) | (°C) | |||||||
| D1 | 100 | 1.0 | 0.075 | 2 | 3 | 0.225 | 0.100 | 6.361 | 6.102 | -4.09 | 24.50 | 25.05 | 0.55 |
| D2 | 100 | 1.0 | 0.075 | 2 | 3 | 0.075 | 0.050 | 1.831 | 1.831 | 0.02 | 29.42 | 30.08 | 0.66 |
| D3 | 100 | 1.0 | 0.075 | 5 | 3 | 0.060 | 0.100 | 5.137 | 4.897 | -4.68 | 24.91 | 25.56 | 0.65 |
| D4 | 100 | 1.0 | 0.075 | 5 | 3 | 0.020 | 0.100 | 2.785 | 2.672 | -4.06 | 27.13 | 28.40 | 1.27 |
| D5 | 100 | 1.0 | 0.075 | 5 | 5 | 0.060 | 0.050 | 8.116 | 7.704 | -5.08 | 23.92 | 24.36 | 0.44 |
| D6 | 100 | 1.0 | 0.075 | 9 | 3 | 0.033 | 0.100 | 5.614 | 5.383 | -4.12 | 24.91 | 25.29 | 0.38 |
| D7 | 500 | 1.0 | 0.015 | 2 | 3 | 0.225 | 0.100 | 1.450 | 1.420 | -2.04 | 22.40 | 22.95 | 0.55 |
| D8 | 500 | 1.0 | 0.015 | 2 | 3 | 0.075 | 0.050 | 0.496 | 0.516 | 4.10 | 25.41 | 26.16 | 0.75 |
| D9 | 500 | 1.0 | 0.015 | 5 | 3 | 0.060 | 0.100 | 1.322 | 1.273 | -3.69 | 22.44 | 23.13 | 0.69 |
| D10 | 500 | 1.0 | 0.015 | 5 | 3 | 0.020 | 0.100 | 0.944 | 0.886 | -6.12 | 23.40 | 24.68 | 1.28 |
| D11 | 500 | 1.0 | 0.015 | 5 | 5 | 0.060 | 0.050 | 2.013 | 1.875 | -6.86 | 22.02 | 22.48 | 0.46 |
| D12 | 500 | 1.0 | 0.015 | 9 | 3 | 0.033 | 0.100 | 1.351 | 1.347 | -0.34 | 22.60 | 22.95 | 0.35 |
Table 9. Comparison of the VTLM and three-dimensional reference results for uniform two-directional fin arrays at AR = 1.
| Case | Re | AR | (%) | (°C) | (°C) | (°C) | |||||||
| D13 | 500 | 0.2 | 0.045 | 2 | 3 | 0.225 | 0.100 | 0.392 | 0.401 | 2.23 | 24.06 | 23.69 | -0.37 |
| D14 | 500 | 0.2 | 0.045 | 2 | 3 | 0.075 | 0.050 | 0.232 | 0.254 | 9.34 | 25.07 | 24.92 | -0.15 |
| D15 | 500 | 0.2 | 0.045 | 5 | 3 | 0.020 | 0.100 | 0.348 | 0.344 | -1.31 | 23.29 | 23.94 | 0.65 |
| D16 | 500 | 0.2 | 0.045 | 5 | 5 | 0.060 | 0.050 | 0.474 | 0.463 | -2.31 | 22.60 | 22.51 | -0.09 |
| D17 | 500 | 0.2 | 0.045 | 9 | 3 | 0.033 | 0.100 | 0.381 | 0.395 | 3.52 | 23.75 | 23.17 | -0.58 |
| D18 | 500 | 5.0 | 0.009 | 2 | 3 | 0.225 | 0.100 | 3.500 | 3.498 | -0.06 | 22.07 | 22.28 | 0.21 |
| D19 | 500 | 5.0 | 0.009 | 2 | 3 | 0.075 | 0.050 | 0.951 | 0.974 | 2.34 | 26.02 | 27.20 | 1.18 |
| D20 | 500 | 5.0 | 0.009 | 5 | 3 | 0.020 | 0.100 | 1.970 | 1.973 | 0.14 | 23.83 | 24.94 | 1.11 |
| D21 | 500 | 5.0 | 0.009 | 5 | 5 | 0.060 | 0.050 | 4.715 | 4.939 | 4.76 | 22.16 | 22.84 | 0.68 |
| D22 | 500 | 5.0 | 0.009 | 9 | 3 | 0.033 | 0.100 | 3.091 | 3.314 | 7.21 | 22.58 | 22.39 | -0.19 |
Table 10. Comparison of the VTLM and three-dimensional reference results for uniform two-directional fin arrays at AR = 0.2 and 5.0.
For the AR = 1 cases, reducing from 0.075 to 0.015 increases the maximum hydraulic error from 5.08% to 6.86%, whereas the maximum absolute bottom-temperature difference remains nearly unchanged, increasing only from 1.27 to 1.28 °C. The hydraulic error depends on the detailed in-plane arrangement rather than simply on the total fin number. For example, although Case D12 contains more fins than Case D11, its hydraulic error is only −0.34%, compared with −6.86% for Case D11.
This behavior is consistent with the subdivision of the fluid region into narrower passages. As more of the hydraulic resistance is resolved through the in-plane fin boundaries, the unresolved top- and bottom-wall contribution represents a smaller fraction of the total pressure loss. Therefore, increasing the array density does not necessarily increase the error associated with the wall-friction closure.
The low- and high-aspect-ratio cases show the same general behavior. Across all two-directional arrays, the maximum absolute hydraulic error is 9.34%, while the maximum absolute bottom-temperature difference is 1.28 °C. The dependence on and AR remains consistent with the preceding fin-array groups, and no additional limitation attributable specifically to two-directional subdivision is evident.
Nonuniform fin arrays
Fin arrays with unequal streamwise fin lengths were further examined to assess the representative fin-length treatment used in the thermal closure. The configurations considered here are shown in Figure 9. In the transverse arrays, the fins are centered within the heated section but have different streamwise lengths. In the streamwise segmented arrays, the upstream and downstream segments are aligned with the ends of the heated section, while the middle segment is centered. The individual streamwise fin-length ratios are denoted by , where identifies each fin. The representative fin length defined in Eq. (24) was used to evaluate the fin-side thermal-development length for each nonuniform array.
Figure 9. Nonuniform fin-array configurations considered in the VTLM assessment: (a) transverse fin arrays and (b) streamwise segmented fin arrays. The streamwise fin lengths vary among fins.
For the nonuniform transverse arrays, and were fixed, while , , and were varied. The nonuniform transverse fin-array cases and corresponding results are summarized in Table 11. Cases with equal values of , , and provide uniform-array references under each operating condition.
| Case | Re | AR | (%) | (°C) | (°C) | (°C) | ||||||||
| NT1 | 100 | 1.0 | 0.075 | 3 | 0.1 | 0.500 | 0.500 | 0.500 | 6.755 | 6.495 | -3.85 | 24.42 | 24.89 | 0.47 |
| NT2 | 100 | 1.0 | 0.075 | 3 | 0.1 | 0.500 | 0.375 | 0.250 | 4.839 | 4.670 | -3.49 | 25.28 | 25.83 | 0.55 |
| NT3 | 100 | 1.0 | 0.075 | 3 | 0.1 | 0.500 | 0.250 | 0.500 | 3.033 | 2.971 | -2.05 | 27.25 | 27.92 | 0.67 |
| NT4 | 100 | 1.0 | 0.075 | 3 | 0.1 | 0.250 | 0.500 | 0.250 | 2.537 | 2.495 | -1.65 | 28.22 | 29.09 | 0.87 |
| NT5 | 500 | 1.0 | 0.015 | 3 | 0.1 | 0.500 | 0.500 | 0.500 | 1.482 | 1.478 | -0.29 | 22.44 | 22.84 | 0.40 |
| NT6 | 500 | 1.0 | 0.015 | 3 | 0.1 | 0.500 | 0.375 | 0.250 | 1.122 | 1.122 | 0.02 | 22.85 | 23.41 | 0.56 |
| NT7 | 500 | 1.0 | 0.015 | 3 | 0.1 | 0.500 | 0.250 | 0.500 | 0.763 | 0.777 | 1.89 | 24.00 | 24.75 | 0.75 |
| NT8 | 500 | 1.0 | 0.015 | 3 | 0.1 | 0.250 | 0.500 | 0.250 | 0.649 | 0.666 | 2.65 | 24.41 | 25.39 | 0.98 |
| NT9 | 100 | 5.0 | 0.045 | 3 | 0.1 | 0.500 | 0.500 | 0.500 | 16.636 | 16.514 | -0.73 | 23.01 | 23.16 | 0.15 |
| NT10 | 100 | 5.0 | 0.045 | 3 | 0.1 | 0.250 | 0.500 | 0.250 | 5.599 | 5.604 | 0.09 | 26.83 | 27.21 | 0.38 |
| NT11 | 500 | 5.0 | 0.009 | 3 | 0.1 | 0.500 | 0.500 | 0.500 | 3.512 | 3.512 | -0.02 | 22.06 | 22.28 | 0.22 |
| NT12 | 500 | 5.0 | 0.009 | 3 | 0.1 | 0.250 | 0.500 | 0.250 | 1.318 | 1.328 | 0.81 | 24.60 | 25.16 | 0.56 |
| NT13 | 100 | 0.2 | 0.225 | 3 | 0.1 | 0.500 | 0.500 | 0.500 | 1.706 | 1.678 | -1.61 | 28.94 | 27.82 | -1.12 |
| NT14 | 100 | 0.2 | 0.225 | 3 | 0.1 | 0.500 | 0.375 | 0.250 | 1.434 | 1.425 | -0.62 | 29.55 | 27.74 | -1.81 |
| NT15 | 500 | 0.2 | 0.045 | 3 | 0.1 | 0.500 | 0.500 | 0.500 | 0.395 | 0.407 | 3.03 | 24.34 | 23.77 | -0.57 |
| NT16 | 500 | 0.2 | 0.045 | 3 | 0.1 | 0.250 | 0.500 | 0.250 | 0.266 | 0.283 | 6.44 | 24.64 | 24.87 | 0.23 |
Table 11. Comparison of the VTLM and three-dimensional reference results for nonuniform transverse fin arrays.
For the nonuniform transverse arrays, redistributing the three streamwise fin lengths produces no systematic deterioration relative to the corresponding uniform references. At AR = 1 and 5.0, the hydraulic errors and bottom-temperature differences remain comparable to those of the uniform arrays. Larger discrepancies occur at AR = 0.2, including a bottom-temperature difference of −1.81 °C in Case NT14 and a hydraulic error of 6.44% in Case NT16. However, the discrepancies do not in
crease systematically as the differences among the fin lengths become larger. These results support the use of the representative fin length for transverse variations in streamwise fin length.
The nonuniform streamwise segmented fin-array cases and corresponding results are summarized in Table 12. These arrays show the same tendency. At , redistributing the segment lengths has little effect, whereas at smaller , the hydraulic discrepancy increases for both the uniform and nonuniform cases. The largest hydraulic error of 12.12% occurs in shallow-channel Case NS18, while the largest absolute bottom-temperature difference of 2.20 °C occurs in the uniform reference Case NS15. Therefore, the reduced accuracy is associated primarily with the aspect ratio and flow development rather than with the unequal segment lengths. Overall, no additional limitation attributable specifically to fin-length nonuniformity is identified within the tested range.
| Case | Re | AR | (%) | (°C) | (°C) | (°C) | ||||||||
| NS1 | 100 | 1.0 | 0.075 | 3 | 0.2 | 0.150 | 0.150 | 0.150 | 1.685 | 1.697 | 0.68 | 31.62 | 31.66 | 0.04 |
| NS2 | 100 | 1.0 | 0.075 | 3 | 0.2 | 0.150 | 0.100 | 0.050 | 1.474 | 1.487 | 0.84 | 32.72 | 32.87 | 0.15 |
| NS3 | 100 | 1.0 | 0.075 | 3 | 0.2 | 0.150 | 0.050 | 0.150 | 1.567 | 1.575 | 0.52 | 32.11 | 32.28 | 0.17 |
| NS4 | 100 | 1.0 | 0.075 | 3 | 0.2 | 0.050 | 0.150 | 0.050 | 1.400 | 1.412 | 0.84 | 33.05 | 33.35 | 0.30 |
| NS5 | 100 | 1.0 | 0.075 | 3 | 0.2 | 0.050 | 0.100 | 0.150 | 1.475 | 1.487 | 0.81 | 32.61 | 32.87 | 0.26 |
| NS6 | 500 | 1.0 | 0.015 | 3 | 0.2 | 0.150 | 0.150 | 0.150 | 0.434 | 0.464 | 7.13 | 25.88 | 26.42 | 0.54 |
| NS7 | 500 | 1.0 | 0.015 | 3 | 0.2 | 0.150 | 0.100 | 0.050 | 0.404 | 0.435 | 7.70 | 26.09 | 26.94 | 0.85 |
| NS8 | 500 | 1.0 | 0.015 | 3 | 0.2 | 0.150 | 0.050 | 0.150 | 0.421 | 0.451 | 7.03 | 25.81 | 26.65 | 0.84 |
| NS9 | 500 | 1.0 | 0.015 | 3 | 0.2 | 0.050 | 0.150 | 0.050 | 0.397 | 0.425 | 7.21 | 25.97 | 27.12 | 1.15 |
| NS10 | 500 | 1.0 | 0.015 | 3 | 0.2 | 0.050 | 0.100 | 0.150 | 0.407 | 0.435 | 6.88 | 25.87 | 26.91 | 1.04 |
| NS11 | 100 | 5.0 | 0.045 | 3 | 0.2 | 0.150 | 0.150 | 0.150 | 3.316 | 3.366 | 1.53 | 26.27 | 26.57 | 0.30 |
| NS12 | 100 | 5.0 | 0.045 | 3 | 0.2 | 0.050 | 0.150 | 0.050 | 2.553 | 2.600 | 1.83 | 28.64 | 28.92 | 0.28 |
| NS13 | 500 | 5.0 | 0.009 | 3 | 0.2 | 0.150 | 0.150 | 0.150 | 0.779 | 0.799 | 2.59 | 24.20 | 24.45 | 0.25 |
| NS14 | 500 | 5.0 | 0.009 | 3 | 0.2 | 0.050 | 0.150 | 0.050 | 0.684 | 0.693 | 1.36 | 25.26 | 25.95 | 0.69 |
| NS15 | 100 | 0.2 | 0.225 | 3 | 0.2 | 0.150 | 0.150 | 0.150 | 0.998 | 1.044 | 4.53 | 34.60 | 32.40 | -2.20 |
| NS16 | 100 | 0.2 | 0.225 | 3 | 0.2 | 0.150 | 0.100 | 0.050 | 0.948 | 0.988 | 4.21 | 34.20 | 32.17 | -2.03 |
| NS17 | 500 | 0.2 | 0.045 | 3 | 0.2 | 0.150 | 0.150 | 0.150 | 0.236 | 0.260 | 10.23 | 27.16 | 26.27 | -0.89 |
| NS18 | 500 | 0.2 | 0.045 | 3 | 0.2 | 0.150 | 0.100 | 0.050 | 0.226 | 0.253 | 12.12 | 26.52 | 25.98 | -0.54 |
Table 12. Comparison of the VTLM and three-dimensional reference results for nonuniform streamwise segmented fin arrays.
Model applicability
The preceding numerical comparisons show that the hydraulic accuracy of the VTLM is governed primarily by the dimensionless flow-development length . For the AR = 1 configurations, the hydraulic discrepancies generally increase as approaches 0.015, whereas the detailed fin-array arrangement has a secondary influence. Fin-length nonuniformity does not introduce an additional limitation, since its error levels remain comparable to those of the corresponding uniform arrays.
The aspect ratio modifies this behavior through the relative contribution of wall friction. In shallow channels, the unresolved top- and bottom-wall contributions represent a larger portion of the total hydraulic resistance, making the prediction more sensitive to the equivalent straight-channel treatment. By contrast, this contribution becomes less dominant as the aspect ratio increases. Dense fin arrays may also reduce the sensitivity by partitioning the fluid region into narrower passages, for which the relative contribution of the unresolved wall friction is smaller. Based on these observations, a conservative lower-bound guideline for the straight-channel fin-array cases is expressed as
where is the hydraulic diameter of the channel under consideration and is the hydraulic diameter of the AR = 1 reference channel. The hydraulic diameters in Eq. (32) are evaluated from the original channel cross-section rather than from the equivalent geometry used in the wall-friction closure. For the present geometry, Eq. (32) gives lower bounds of at AR = 0.2 and at AR = 1.
Eq. (32) should be interpreted as a screening guideline for straight channels containing the fin-array configurations examined in this study, rather than as a strict validity boundary. Hydraulic errors may approach or slightly exceed 10% near the estimated lower limit, particularly in low-aspect-ratio channels with sparse or strongly localized blockage. The absolute bottom-temperature differences are generally less sensitive to , although larger deviations may occur when a shallow channel, a near-limit flow-development condition, and a large localized transverse blockage are combined. Accordingly, additional assessment may be necessary for configurations near the lower bound or beyond the geometric and operating ranges examined in this study.
Fin arrays in an expansion–contraction channel
To evaluate the VTLM beyond straight channels of uniform width, the configuration shown in Figure 10 was considered. The domain comprises a central heated section of length , preceded and followed by inlet and outlet sections of length , respectively. The heated section has a width of , whereas the inlet and outlet have a common width . Owing to symmetry about the channel centerline, only half of the domain was modeled. The expansion ratio is defined as . The channel height remains unchanged throughout the domain, so variations in ER arise solely from the lateral change in channel width.
Figure 10. Geometry used to assess the VTLM in an expansion–contraction channel: (a) symmetry-reduced three-dimensional reference domain and (b) corresponding Layer 1 and Layer 2 domains.
In the VTLM, the fluid region is represented in Layer 1, while the heated base is modeled in Layer 2. The material properties and boundary conditions were the same as those adopted in the straight-channel fin-array cases, except for the applied bottom heat flux. Because the heated-section width increases with ER, the bottom heat flux was scaled as to maintain the same total heat input as in the straight-channel baseline case. For the expansion–contraction cases, the hydraulic diameter used to evaluate was calculated from the cross-section of the expanded heated section.
The assessment was conducted in two stages. Channels without fins were first examined at ER = 2–4 to determine the influence of the abrupt lateral expansion and contraction independently of internal structures. Finned channels were subsequently evaluated at ER = 2, including single-fin, streamwise segmented, and two-directional configurations. The two groups are discussed separately in the following subsections.
Baseline channels without fins
The fin-free channels were first examined to quantify the prediction differences caused by the abrupt expansion and contraction before introducing internal fin structures. Because no solid fin region is present in Layer 1, the fin-side closure is inactive, and only the fluid-side interlayer heat-transfer coefficient is employed. The corresponding VTLM and three-dimensional results are listed in Table 13. The VTLM predicts a higher friction factor than the three-dimensional model in all cases. At Re = 100, the hydraulic error ranges from 5.44% to 9.65%. The error increases to 14.68%–16.96% at Re = 300 and 16.43%–18.58% at Re = 500. The increase with Reynolds number is accompanied by a reduction in , whereas the hydraulic error does not exhibit a consistent trend with ER across the three Reynolds numbers. This indicates that the hydraulic discrepancy is more closely associated with the flow-development condition than with the expansion ratio alone. The remaining difference can be attributed to flow redistribution near the width discontinuities, which are not explicitly included in the equivalent straight-channel representation.
| Case | Re | ER | (%) | (°C) | (°C) | (°C) | |||
| E1 | 100 | 2 | 0.056 | 0.503 | 0.552 | 9.65 | 46.53 | 42.91 | -3.62 |
| E2 | 100 | 3 | 0.050 | 0.500 | 0.533 | 6.57 | 42.78 | 39.44 | -3.34 |
| E3 | 100 | 4 | 0.047 | 0.501 | 0.529 | 5.44 | 41.45 | 37.96 | -3.49 |
| E4 | 300 | 2 | 0.019 | 0.228 | 0.262 | 15.17 | 38.26 | 35.99 | -2.27 |
| E5 | 300 | 3 | 0.017 | 0.226 | 0.259 | 14.68 | 36.30 | 35.55 | -0.75 |
| E6 | 300 | 4 | 0.016 | 0.227 | 0.265 | 16.96 | 35.29 | 32.94 | -2.35 |
| E7 | 500 | 2 | 0.011 | 0.164 | 0.195 | 18.58 | 34.85 | 33.71 | -1.14 |
| E8 | 500 | 3 | 0.010 | 0.162 | 0.192 | 17.99 | 33.18 | 33.67 | 0.49 |
| E9 | 500 | 4 | 0.009 | 0.162 | 0.189 | 16.43 | 32.35 | 33.34 | 0.99 |
Table 13. Comparison of the VTLM and three-dimensional reference results for expansion–contraction channels without fins.
The thermal prediction shows a different trend. The magnitude of generally decreases with increasing Reynolds number, whereas no systematic dependence on ER is observed. The largest absolute difference is 3.62 °C, obtained at Re = 100 and ER = 2. At higher Reynolds numbers, the discrepancy becomes smaller and may change sign as ER increases, reflecting the combined effects of flow redistribution and thermal development in the expanded heated section. These fin-free results provide the reference prediction differences for the finned expansion–contraction cases examined in the following subsection. Comparisons with the corresponding fin-free cases allow the influence of the fin arrangement to be distinguished from that of the expansion–contraction geometry.
Finned expansion–contraction channels
Fins were subsequently introduced into the expanded heated section at . The investigated layouts comprise a single fin, streamwise segmented arrays, and arrays subdivided in both the streamwise and transverse directions. These configurations follow the same types of in-plane fin arrangement introduced for the straight-channel cases in Figure 8, but are placed within the expanded region shown in Figure 10. For the ES and ET cases, the fins were distributed over a centered streamwise region of length within the heated section, leaving a fin-free length of at each end. The single-fin results are summarized in Table 14, while the streamwise segmented and two-directional results are listed in Table 15. For all three configuration groups, and correspond to and , respectively. The smaller at is consistent with the generally larger errors observed at this Reynolds number and motivates comparison with the straight-channel screening guideline in Eq. (32).
| Case | Re | ER | (%) | (°C) | (°C) | (°C) | |||||
| EF1 | 100 | 2 | 0.056 | 0.50 | 0.05 | 0.664 | 0.681 | 2.54 | 33.04 | 32.69 | -0.35 |
| EF2 | 100 | 2 | 0.056 | 0.50 | 0.10 | 0.734 | 0.747 | 1.80 | 32.52 | 31.94 | -0.58 |
| EF3 | 100 | 2 | 0.056 | 0.50 | 0.20 | 1.009 | 1.001 | -0.72 | 31.55 | 31.46 | -0.09 |
| EF4 | 100 | 2 | 0.056 | 0.30 | 0.05 | 0.583 | 0.608 | 4.32 | 35.32 | 34.99 | -0.33 |
| EF5 | 100 | 2 | 0.056 | 0.10 | 0.05 | 0.550 | 0.581 | 5.50 | 38.86 | 37.85 | -1.01 |
| EF6 | 500 | 2 | 0.011 | 0.50 | 0.05 | 0.223 | 0.241 | 8.23 | 26.26 | 27.03 | 0.77 |
| EF7 | 500 | 2 | 0.011 | 0.50 | 0.10 | 0.266 | 0.280 | 5.17 | 25.45 | 26.54 | 1.09 |
| EF8 | 500 | 2 | 0.011 | 0.50 | 0.20 | 0.483 | 0.475 | -1.78 | 24.46 | 25.38 | 0.92 |
| EF9 | 500 | 2 | 0.011 | 0.30 | 0.05 | 0.191 | 0.211 | 10.31 | 27.24 | 28.33 | 1.09 |
| EF10 | 500 | 2 | 0.011 | 0.10 | 0.05 | 0.182 | 0.206 | 12.90 | 28.98 | 29.93 | 0.95 |
Table 14. Comparison of the VTLM and three-dimensional reference results for single-fin expansion–contraction channels at ER = 2.
| Case | Re | ER | (%) | (°C) | (°C) | (°C) | |||||||
| ES1 | 100 | 2 | 0.056 | 2 | 1 | 0.18 | 0.05 | 0.601 | 0.624 | 3.67 | 34.30 | 33.98 | -0.32 |
| ES2 | 100 | 2 | 0.056 | 2 | 1 | 0.10 | 0.05 | 0.586 | 0.607 | 3.66 | 35.38 | 35.09 | -0.29 |
| ES3 | 100 | 2 | 0.056 | 2 | 1 | 0.02 | 0.05 | 0.565 | 0.590 | 4.41 | 38.86 | 38.25 | -0.61 |
| ES4 | 100 | 2 | 0.056 | 3 | 1 | 0.11 | 0.05 | 0.600 | 0.622 | 3.68 | 34.44 | 34.04 | -0.40 |
| ES5 | 500 | 2 | 0.011 | 2 | 1 | 0.18 | 0.05 | 0.196 | 0.215 | 9.37 | 26.86 | 27.74 | 0.88 |
| ES6 | 500 | 2 | 0.011 | 2 | 1 | 0.10 | 0.05 | 0.193 | 0.213 | 10.64 | 27.39 | 28.30 | 0.91 |
| ES7 | 500 | 2 | 0.011 | 2 | 1 | 0.06 | 0.05 | 0.191 | 0.213 | 11.34 | 27.99 | 28.89 | 0.90 |
| ES8 | 500 | 2 | 0.011 | 3 | 1 | 0.11 | 0.05 | 0.196 | 0.215 | 9.41 | 26.95 | 27.78 | 0.83 |
| ES9 | 500 | 2 | 0.011 | 3 | 1 | 0.05 | 0.05 | 0.194 | 0.214 | 10.16 | 27.52 | 28.50 | 0.98 |
| ET1 | 100 | 2 | 0.056 | 2 | 3 | 0.18 | 0.05 | 0.907 | 0.894 | -1.47 | 26.58 | 26.87 | 0.29 |
| ET2 | 100 | 2 | 0.056 | 2 | 3 | 0.10 | 0.05 | 0.770 | 0.771 | 0.10 | 28.03 | 28.36 | 0.33 |
| ET3 | 100 | 2 | 0.056 | 2 | 3 | 0.06 | 0.05 | 0.697 | 0.707 | 1.35 | 29.58 | 29.90 | 0.32 |
| ET4 | 100 | 2 | 0.056 | 2 | 3 | 0.18 | 0.25 | 13.595 | 12.965 | -4.63 | 23.69 | 23.94 | 0.25 |
| ET5 | 100 | 2 | 0.056 | 2 | 5 | 0.18 | 0.05 | 1.643 | 1.577 | -4.02 | 24.19 | 24.46 | 0.27 |
| ET6 | 100 | 2 | 0.056 | 2 | 5 | 0.06 | 0.05 | 0.971 | 0.959 | -1.19 | 26.56 | 26.99 | 0.43 |
| ET7 | 500 | 2 | 0.011 | 2 | 3 | 0.18 | 0.05 | 0.270 | 0.281 | 3.97 | 23.12 | 23.74 | 0.62 |
| ET8 | 500 | 2 | 0.011 | 2 | 3 | 0.10 | 0.05 | 0.245 | 0.259 | 5.74 | 23.71 | 24.45 | 0.74 |
| ET9 | 500 | 2 | 0.011 | 2 | 3 | 0.06 | 0.05 | 0.230 | 0.246 | 6.94 | 24.38 | 25.25 | 0.87 |
| ET10 | 500 | 2 | 0.011 | 2 | 3 | 0.18 | 0.25 | 3.371 | 3.198 | -5.11 | 21.49 | 21.88 | 0.39 |
| ET11 | 500 | 2 | 0.011 | 2 | 5 | 0.18 | 0.05 | 0.428 | 0.428 | 0.11 | 22.01 | 22.41 | 0.40 |
| ET12 | 500 | 2 | 0.011 | 2 | 5 | 0.06 | 0.05 | 0.299 | 0.307 | 2.74 | 23.10 | 23.79 | 0.69 |
Table 15. Comparison of the VTLM and three-dimensional reference results for streamwise segmented and two-directional fin arrays in the expansion–contraction channel at ER = 2.
For the single-fin cases, the hydraulic discrepancy depends clearly on the fraction of the expanded region occupied by the fin. At fixed , increasing from to changes from to at and from to at . Conversely, reducing at fixed increases the hydraulic overprediction, with the error reaching at . The generally larger hydraulic errors at also indicate an influence of the flow-development condition. This behavior is consistent with the fin-induced wall resistance accounting for a smaller fraction of the total pressure loss as the fin becomes shorter, thereby increasing the relative influence of the expansion and contraction losses that are not explicitly included in the closure model. No consistent dependence of the bottom-temperature difference on or is observed. At , ranges from to , whereas at , it ranges from to . The maximum absolute bottom-temperature difference among the single-fin cases is .
For the streamwise segmented arrays, the increase in hydraulic discrepancy between the two Reynolds numbers is more pronounced than the variation caused by the segment geometry. The hydraulic error increases from – at to – at . By contrast, the absolute bottom-temperature differences remain within at and at . Cases with and give similar results at comparable streamwise size ratios, indicating that additional segmentation does not introduce a distinct deterioration beyond that associated with the smaller .
The two-directional arrays exhibit a stronger dependence of the hydraulic prediction on the detailed transverse arrangement. At , the maximum absolute hydraulic error is , while the absolute bottom-temperature differences remain within . At , the maximum absolute hydraulic error increases to , whereas the maximum absolute bottom-temperature difference is . For and , increasing from to changes from to at and from to at . At fixed and , increasing from to shifts the hydraulic prediction toward underprediction at both Reynolds numbers, whereas the bottom-temperature differences remain comparatively small.
Across the finned expansion–contraction cases, the maximum absolute hydraulic error is $12.90%$, while the maximum absolute bottom-temperature difference is . The hydraulic error levels follow the distinction implied by the straight-channel screening guideline. At , which satisfies Eq. (32), the maximum absolute hydraulic error is $5.50%, whereas at , below that lower bound, it increases to . In contrast, the maximum absolute bottom-temperature differences are and at and , respectively, indicating substantially weaker sensitivity of the thermal prediction to the flow-development condition within the finned expansion–contraction cases. The hydraulic errors remain below those of the corresponding fin-free channels at both Reynolds numbers, indicating that the internal fins do not amplify the discrepancy associated with the abrupt width changes. As the fin obstruction increases, fin-induced friction accounts for a larger fraction of the total pressure loss, reducing the relative contribution of the unresolved expansion and contraction losses. These results suggest that the straight-channel screening guideline remains informative primarily for the hydraulic prediction of the finned channel at , although they do not establish its general applicability to arbitrary nonuniform-width passages.
Overall thermal-resistance assessment
To provide an overall assessment of the thermal prediction, the thermal resistance was evaluated for all assessment cases as
where is the total heat input applied to the heated bottom surface. The relative difference in thermal resistance between the VTLM and the three-dimensional reference model was then defined as
The baseline straight-channel cases used to calibrate the representative-height closure were excluded from this assessment. Because the VTLM and three-dimensional reference model are subjected to the same heat input for each case, Eq. (34) can also be written as
This relation shows that the thermal-resistance relative difference depends not only on the absolute bottom-temperature difference but also on the reference temperature rise. Figure 11 summarizes the thermal-resistance relative differences for all assessment cases. Figure 11(a) presents the straight-channel configurations, including the uniform and nonuniform fin-array groups, whereas Figure 11(b) presents the fin-free and finned expansion–contraction configurations. For the straight-channel configurations, cases satisfying the screening guideline in Eq. (32) generally exhibit a more concentrated distribution of , whereas cases near or below the lower bound show a wider spread. The same tendency is particularly evident for the finned expansion–contraction configurations. Among the EF, ES, and ET cases, the maximum magnitude of increases from approximately 6.8% to 26.2% as decreases from 0.056 to 0.011, with the latter falling below the straight-channel lower bound. This behavior indicates that the flow-development condition identified from the preceding hydraulic assessment also provides a useful first-stage indication of thermal-resistance accuracy for the examined finned configurations.
Figure 11. Thermal-resistance relative differences for the assessment cases: (a) straight-channel configurations and (b) expansion–contraction configurations. Each marker represents one case. Markers within each case family are slightly offset in the horizontal direction to avoid overlap, and the horizontal offset has no physical meaning.
The thermal-resistance relative difference does not depend on alone. As indicated by Eq. (35), the magnitude of can also become large when the reference temperature rise is small. In such cases, even a small can correspond to a comparatively large thermal-resistance relative difference. For example, Case ET10 has and a reference temperature rise of only , resulting in . By contrast, Case
UT18 exhibits a much larger , while the thermal-resistance relative difference is also pronounced. In this case, the large thermal-resistance relative difference is mainly associated with the relatively large , rather than with a small reference temperature rise.
Accordingly, Eq. (32) remains useful as a conservative first-stage screening guideline for the overall VTLM prediction accuracy. Its strongest relevance is to the hydraulic prediction, while the thermal-resistance results indicate that it also provides a useful indication of thermal accuracy for the examined finned configurations. It should not be interpreted as a strict thermal-resistance validity boundary.
Conclusion
A versatile two-layer model (VTLM) was developed for thermohydraulic prediction of microchannel heat sinks under steady laminar flow. The model represents the three-dimensional conjugate heat-transfer problem using two coupled planar fields while retaining the in-plane geometry of the fluid passages and fins. Effects associated with the unresolved channel-height direction are incorporated through closures for wall friction, fluid-side heat transfer, and fin-side effective heat transfer. These closures are evaluated from the representative channel geometry, flow-development condition, and fin configuration, enabling the model to accommodate the range of channel geometries and fin arrangements examined in this study.
The three-dimensional reference model was first compared with benchmark solutions for developing laminar flow. The representative-height closure was then calibrated using baseline straight-channel conjugate heat-transfer cases spanning a broad range of channel aspect ratios. The VTLM was also compared with the existing two-layer models of Yan et al. [32] and Zeng and Lee [31]. Across these baseline cases, the VTLM showed improved overall agreement with the three-dimensional reference results, highlighting the benefit of explicitly accounting for unresolved wall friction and adapting the hydraulic and thermal closures to the channel geometry and development conditions. With the closure parameters subsequently fixed, the VTLM was independently assessed using uniform transverse, streamwise segmented, two-directional, and nonuniform fin arrays. These comparisons showed that the formulation can accommodate variations in channel geometry, fin arrangement, and operating conditions without case-by-case adjustment of the closure parameters. The results further indicated that the VTLM accuracy is governed primarily by the flow-development condition and channel aspect ratio, while no distinct additional limitations associated with streamwise segmentation or fin-length nonuniformity were identified. Based on the combined straight-channel fin-array results, was proposed as a conservative screening guideline for the configurations examined in this study. The thermal-resistance assessment further showed that depends on both the flow-development condition and the reference temperature rise, so the proposed guideline should not be interpreted as a strict thermal-resistance validity boundary. The assessment was extended to expansion–contraction channels to examine the applicability of the VTLM to passages with abrupt width changes. Fin-free cases were first considered to isolate the effects of flow redistribution and local pressure losses associated with the expansion and contraction. Fins were then introduced into the expanded heated section. The comparisons showed that the wall-friction closure based on the equivalent straight-channel representation does not fully capture the local hydraulic effects caused by the width discontinuities. Nevertheless, the hydraulic discrepancies of the finned cases remained below those of the corresponding fin-free channels. This behavior is consistent with an increased contribution of the fin-induced friction captured by the VTLM to the total pressure loss. These results support the applicability of the model to the examined finned expansion–contraction configurations at ER = 2 and suggest that the straight-channel screening guideline remains informative for these cases. Overall, the results support the VTLM as a reduced-dimensional framework for thermohydraulic analysis of the microchannel heat-sink configurations examined in this study.
Future work will extend the VTLM to more complex channel layouts, including U-shaped channels and passages with multiple bends [20], and further refine the thermal-side closure to improve thermal-resistance prediction accuracy over wider operating and geometric ranges. The extended model can then be integrated into a topology optimization framework for efficient microchannel heat-sink design.
CRediT authorship contribution statement
Chih-Hsiang Chen: Writing – original draft, Conceptualization, Methodology, Validation, Formal analysis, Investigation, Data curation, Visualization. Kentaro Yaji: Writing–review & editing, Conceptualization, Methodology, Software, Supervision, Resources, Project administration, Funding acquisition.
Acknowledgement
This work was supported by JSPS KAKENHI (Grant No. 23K26018).
Derivation of the fin-side effective heat transfer coefficient
The fin-side effective heat-transfer coefficient is derived by representing the collection of fins as an equivalent one-dimensional fin of uniform cross section. Let denote the coordinate measured from the fin base, with at the fin-base junction represented by Layer 2 and at the fin tip. Under the uniform-extrusion assumption, the total cross-sectional area normal to the -direction and the total wetted perimeter are and , respectively. The fluid-side heat-transfer coefficient and the representative Layer 1 fluid temperature are assumed to be uniform along the fin height.
For a differential fin element, the balance between axial conduction and lateral heat transfer gives
Because and are constant, the excess temperature is introduced as . Eq. (A.1) then reduces to
The fin-base temperature is given by the Layer 2 temperature, , and the fin tip is treated as adiabatic. The corresponding boundary conditions are given as follows:
Solving Eq. (A.2) subject to Eq. (A.3) gives
The axial conductive heat flow crossing the fin section at position is obtained from Fourier’s law:
At the representative Layer 1 height , the dimensionless parameters are defined as
The remaining axial heat flow at the representative height is denoted by . Eq. (A.5) therefore gives
The temperature difference used to define the fin-side effective heat-transfer coefficient is obtained from Eq. (A.4):
Using the definition introduced in Eq. (25),
and substituting Eqs. (A.7) and (A.8) yields
This expression corresponds to Eq. (26), with and defined by Eq. (27).
References
- [1]J. Zhou, X. Cao, N. Zhang, Y. Yuan, X. Zhao, D. Hardy, Micro-channel heat sink: a review, Journal of Thermal Science 29 (6) (2020) 1431–1462.DOI
- [2]J. Gao, Z. Hu, Q. Yang, X. Liang, H. Wu, Fluid flow and heat transfer in microchannel heat sinks: Modelling review and recent progress, Thermal Science and Engineering Progress 29 (2022) 101203.
- [3]Z.-Q. Yu, M.-T. Li, B.-Y. Cao, A comprehensive review on microchannel heat sinks for electronics cooling, International Journal of Extreme Manufacturing 6 (2) (2024) 022005.DOI
- [4]A. G. Fedorov, R. Viskanta, Three-dimensional conjugate heat transfer in the microchannel heat sink for electronic packaging, International Journal of Heat and Mass Transfer 43 (3) (2000) 399–415.DOI
- [5]W. Qu, I. Mudawar, Analysis of three-dimensional heat transfer in micro-channel heat sinks, International Journal of heat and mass transfer 45 (19) (2002) 3973–3985.DOI
- [6]K. Bala Subrahmanyam, P. Das, V. Ranjith Kumar, An overview of conjugate heat transfer augmentation methods for thermal management and recent advancements in microchannel heat sink overall performance, Proceedings of the Institution of Mechanical Engineers, Part E: Journal of Process Mechanical Engineering 240 (2) (2026) 2292–2305.
- [7]J. Xu, Y. Song, W. Zhang, H. Zhang, Y. Gan, Numerical simulations of interrupted and conventional microchannel heat sinks, International Journal of Heat and Mass Transfer 51 (25-26) (2008) 5906–5917.DOI
- [8]N. H. Naquiuddin, L. H. Saw, M. C. Yew, F. Yusof, H. M. Poon, Z. Cai, H. San Thiam, Numerical investigation for optimizing segmented micro-channel heat sink by taguchi-grey method, Applied energy 222 (2018) 437–450.
- [9]Y. Ma, R. Mohebbi, Z. Yang, M. A. Sheremet, Numerical analysis of heat sink configurations and their impact on conjugate heat transfer in manifold systems, International Journal of Thermal Sciences 218 (2025) 110145.DOI
- [10]K. Kulkarni, A. Afzal, K.-Y. Kim, Multi-objective optimization of a double-layered microchannel heat sink with temperature-dependent fluid properties, Applied Thermal Engineering 99 (2016) 262–272.DOI
- [11]Y. Alperen, C. Sertac, Multi objective optimization of a micro-channel heat sink through genetic algorithm, International Journal of Heat and Mass Transfer 146 (2020) 118847.DOI
- [12]O. Mohammadbeigi, S. Hassani, S. Mazloumi, Numerical investigation and hybrid optimization of pin-fin microchannel heat sinks using taguchi-anova and ahp-topsis methods, International Communications in Heat and Mass Transfer 172 (2026) 110284.DOI
- [13]S. Zeng, B. Kanargi, P. S. Lee, Experimental and numerical investigation of a mini channel forced air heat sink designed by topology optimization, International Journal of Heat and Mass Transfer 121 (2018) 663–679.
- [14]A. Zou, R. Chuan, F. Qian, W. Zhang, Q. Wang, C. Zhao, Topology optimization for a water-cooled heat sink in micro-electronics based on pareto frontier, Applied Thermal Engineering 207 (2022) 118128.DOI
- [15]L. Xie, Y. Zhang, M. Ge, Y. Zhao, Topology optimization of heat sink based on variable density method, Energy Reports 8 (2022) 718–726.DOI
- [16]C. Zhao, T. Lu, Analysis of microchannel heat sinks for electronics cooling, International Journal of Heat and Mass Transfer 45 (24) (2002) 4857–4869.DOI
- [17]D.-K. Kim, S. J. Kim, Averaging approach for microchannel heat sinks subject to the uniform wall temperature condition, International Journal of Heat and Mass Transfer 49 (3-4) (2006) 695–706.DOI
- [18]G. V. Kewalramani, A. Agrawal, S. K. Saha, Modeling of microchannel heat sinks for electronic cooling applications using volume averaging approach, International Journal of Heat and Mass Transfer 115 (2017) 395–409.DOI
- [19]G. M. Harpole, J. E. Enfinger, et al., Micro-channel heat exchanger optimization, in: Proceeding of the 7th IEEE SEMI-THERM Symposium, IEEE, 1991, pp. 59–63.
- [20]R. Mandel, A. Shooshtari, M. Ohadi, A “2.5-d” modeling approach for single-phase flow and heat transfer in manifold microchannels, International Journal of Heat and Mass Transfer 126 (2018) 317–330.DOI
- [21]H. Kamal, A. Dewan, Analysis of interrupted rectangular microchannel heat sink with high aspect ratio, Journal of Applied Fluid Mechanics 10 (2017) 117–126.DOI
- [22]M. P. Bendsøe, O. Sigmund, et al., Topology optimization: theory, methods, and applications, Vol. 2, Springer Berlin, 2004.
- [23]T. Borrvall, J. Petersson, Topology optimization of fluids in stokes flow, International journal for numerical methods in fluids 41 (1) (2003) 77–107.DOI
- [24]L. H. Olesen, F. Okkels, H. Bruus, A high-level programming-language implementation of topology optimization applied to steady-state navier–stokes flow, International Journal for Numerical Methods in Engineering 65 (7) (2006) 975–1001.DOI
- [25]Y. Deng, Z. Liu, P. Zhang, Y. Liu, Y. Wu, Topology optimization of unsteady incompressible navier–stokes flows, Journal of Computational Physics 230 (17) (2011) 6688–6708.DOI
- [26]C. B. Dilgen, S. B. Dilgen, D. R. Fuhrman, O. Sigmund, B. S. Lazarov, Topology optimization of turbulent flows, Computer Methods in Applied Mechanics and Engineering 331 (2018) 363–393.DOI
- [27]E. M. Dede, Multiphysics topology optimization of heat transfer and fluid flow systems, in: proceedings of the COMSOL Users Conference, Vol. 715, 2009.
- [28]K. Yaji, T. Yamada, S. Kubo, K. Izui, S. Nishiwaki, A topology optimization method for a coupled thermal–fluid problem using level set boundary expressions, International Journal of Heat and Mass Transfer 81 (2015) 878–888.
- [29]C.-H. Chen, K. Yaji, Topology optimization for microchannel heat sinks with nanofluids using an eulerian–eulerian approach, International Journal of Heat and Mass Transfer 243 (2025) 126870.arxiv.org/abs/2501.16749
- [30]J. H. Haertel, K. Engelbrecht, B. S. Lazarov, O. Sigmund, Topology optimization of a pseudo 3d thermofluid heat sink model, International Journal of Heat and Mass Transfer 121 (2018) 1073–1088.DOI
- [31]S. Zeng, P. S. Lee, Topology optimization of liquid-cooled microchannel heat sinks: An experimental and numerical study, International Journal of Heat and Mass Transfer 142 (2019) 118401.
- [32]S. Yan, F. Wang, J. Hong, O. Sigmund, Topology optimization of microchannel heat sinks using a two-layer model, International Journal of Heat and Mass Transfer 143 (2019) 118462.DOI
- [33]J. Zhao, M. Zhang, Y. Zhu, R. Cheng, L. Wang, Topology optimization of planar cooling channels using a three-layer thermofluid model in fully developed laminar flow problems, Structural and Multidisciplinary Optimization 63 (6) (2021) 2879–2809.DOI
- [34]J. Zhao, M. Zhang, Y. Zhu, R. Cheng, L. Wang, Topology optimization of turbulent forced convective heat sinks using a multi-layer thermofluid model, Structural and Multidisciplinary Optimization 64 (6) (2021) 3835–3859.DOI
- [35]K. Jia, B. Zhang, Y. Xu, F. Zhao, J. Zhu, L. Gao, Z. Zhang, X. Lu, C. Ma, X. Long, Multilayer topology optimization of microfluidic heat sinks using non-newtonian fluid for electronics cooling, Applied Mathematical Modelling (2026) 116809.DOI
- [36]S.-M. Kim, I. Mudawar, Analytical heat diffusion models for different micro-channel heat sink cross-sectional geometries, International Journal of Heat and Mass Transfer 53 (19-20) (2010) 4002–4016.DOI
- [37]Y. S. Muzychka, M. M. Yovanovich, Laminar flow friction and heat transfer in non-circular ducts and channels: Part i—hydrodynamic problem, in: Compact Heat Exchangers: A Festschrift on the 60th Birthday of Ramesh K. Shah, 2002, pp. 123–130.
- [38]S. Churchill, R. Usagi, A general expression for the correlation of rates of transfer and other phenomena, AIChE Journal 18 (6) (1972) 1121–1128.DOI
- [39]R. K. Shah, A. L. London, Laminar flow forced convection in ducts: a source book for compact heat exchanger analytical data, Academic press, 2014.
- [40]P.-S. Lee, S. V. Garimella, D. Liu, Investigation of heat transfer in rectangular microchannels, International journal of heat and mass transfer 48 (9) (2005) 1688–1704.DOI
- [41]F. Delplace, Laminar flow of newtonian liquids in ducts of rectangular cross-section a model for both physics and mathematics, Open Access J. Math. Theor. Phys. 1 (5) (2018) 198–201.DOI
- [42]Y. S. Muzychka, M. M. Yovanovich, Laminar flow friction and heat transfer in non-circular ducts and channels: Part ii—thermal problem, in: Compact Heat Exchangers: A Festschrift on the 60th Birthday of Ramesh K. Shah, 2002, pp. 131–139.