betaFeedback

WorksComputer Science

Physics-Informed but Not Physics-Consistent: Error Geometry and Subspace Projection for Neural AC Power Flow

Abstract

Recent neural power-flow solvers, including emerging foundation models, achieve accurate voltage predictions, yet such accuracy does not necessarily imply physically consistent solutions. Even small complex voltage errors can yield large AC power-balance residuals. We study this accuracy-consistency gap across PIGNN-GC, GridSFM, gridfm-graphkit, and LUMINA on realistic 2224-bus Great Britain network (GBnetwork) scenarios, with cross-grid evaluation of GridSFM over 31 systems. Using a singular value decomposition (SVD) basis fitted to training AC power-flow solutions, we find that neural prediction errors contain substantial components outside the dominant solution subspace. To address this mismatch, calibrated solution-subspace projection (CSP) suppresses off-subspace prediction components after train-only bias calibration, reducing Mean PB by 67.0%, 37.8%, 40.5%, and 68.9% for PIGNN-GC, GridSFM, gridfm-graphkit, and LUMINA, respectively, relative to calibrated predictions, while improving voltage-magnitude accuracy in all four models. These results identify output-error geometry as an important factor in physics-consistent neural AC power flow. Code: https://github.com/Kimchangheon/neural-acpf-error-geometry

Schematic of calibrated solution-subspace projection

Figure 1. A low-dimensional subspace is derived from the training solutions. CSP first removes train-estimated bias and projects the corrected prediction onto this subspace, suppressing off-subspace errors and improving voltage accuracy and AC power-balance consistency.

Introduction

AC power flow (AC-PF) is a fundamental tool for steady-state power-system analysis [1]. It is repeatedly solved in congestion management [2] and contingency studies [3], and underlies optimal power flow (OPF) [4, 5] and state-estimation workflows [6]. The need for both computational efficiency and physical consistency has motivated neural surrogates including direct data-driven approximation [7, 8], physics-informed training [9, 10, 11], feasibility-seeking mechanisms [12, 13], and learned projection-based correction [14].

More recent cross-grid and foundation-model efforts—including GridSFM [15], gridfm-graphkit and GENCO [16, 17], and LUMINA [18]—extend this direction with global context and topology-aware representations of heterogeneous grid components [19] designed to operate across diverse grids and operating conditions [20].

However, accurate voltage prediction does not necessarily imply physical consistency [21, 22]. Physics-informed objectives can

reduce power-flow residuals [23, 24], but remain soft training objectives and do not by themselves enforce exact satisfaction of the nonlinear AC equations [25]. Consequently, neural surrogates with small voltage errors can still exhibit non-negligible power-balance violations. We refer to this discrepancy as the accuracy–consistency gap and ask which properties of the remaining prediction error govern its physical impact.

We hypothesize that error direction, rather than magnitude alone, is an important factor: similarly sized voltage errors can induce substantially different AC residuals depending on their orientation across buses. Recent work has examined directional effects of warm-start errors in the distinct context of Newton–Raphson (NR) convergence [26]. This motivates studying the geometry of neural-surrogate errors in the voltage-state space.

Goodwin et al. [27] characterized the differential geometry of the AC-PF solution manifold, while Park et al. [28] and Chevalier et al. [29] demonstrated low-dimensional structure in AC-OPF and PF solutions, respectively. Motivated by this evidence of low-dimensional solution structure, we ask whether the relationship between neural prediction errors and a training solution subspace can be quantified to explain physical inconsistency, and whether this structure can be exploited to reduce power-balance violations.

To address these questions, we make three contributions. (i) We decompose calibrated prediction errors of four neural surrogates into in- and off-subspace components using a low-rank singular value decomposition (SVD) basis fitted to training AC-PF solutions, and show through fixed-norm interventions and local Jacobian analysis that off-subspace errors are substantially more residual-sensitive. (ii) Building on this finding, we propose calibrated solution-subspace projection (CSP), a lightweight post-hoc output correction that uses only training data, removes systematic bias, and suppresses off-subspace prediction components without retraining. (iii) We evaluate CSP on frozen PIGNN-GC, GridSFM, gridfm-graphkit, and LUMINA models on the 2224-bus GBnetwork, where it lowers AC power-balance residuals and voltage-magnitude error in all four models and provides a better initialization for one Newton update. We further assess its generality on 30 additional systems and its robustness under topology and load-distribution shifts.

Error Geometry and CSP

AC power-balance consistency and calibration

For an NN-bus grid, let x=[V,θ]∈R2Nx = [V, \theta] \in\mathbb{R}^{2N} denote the voltage state, with V=V⊙ejθV = V \odot e^{\mathrm{j}\theta}. Given operating condition uu, a surrogate predicts x^=fϕ(u)\hat{x} = f_\phi(u), from which (P,Q)(P,Q) are recomputed using the network admittance model. For setpoints (Pset,Qset)(P^{\mathrm{set}}, Q^{\mathrm{set}}), we define

r(x^;u)=[ΔPΔQ]=[Pset−PQset−Q],PB=ΔP2+ΔQ2.r(\hat{x};u) = \begin{bmatrix} \Delta P \\ \Delta Q \end{bmatrix} = \begin{bmatrix} P^{\mathrm{set}} - P \\ Q^{\mathrm{set}} - Q \end{bmatrix}, \qquad \mathrm{PB} = \sqrt{\Delta P^2 + \Delta Q^2}.

PB uses ΔP\Delta P at PV/PQ and ΔQ\Delta Q at PQ buses, zero elsewhere; prescribed PV/slack magnitudes and the slack angle are restored before scoring. Mean/Max PB aggregate all bus–scenario pairs on a common 100-MVA per unit (p.u.) base.

Before geometric analysis, we remove train-only prediction bias:

b^=Es∈tr[x^s−xs⋆],x^C=x^−b^,\hat{b} = \mathbb{E}_{s \in\mathrm{tr}}[\hat{x}_s - x_s^\star], \qquad \hat{x}^{C} = \hat{x} - \hat{b},

where ss indexes scenarios, ⋆\star denotes the converged NR reference, and CC denotes calibration. b^\hat{b} is frozen at test time; angle bias is estimated as the per-bus circular mean of wrapped prediction errors.

Error geometry and training solution subspace projection

From training Newton–Raphson solutions, let XV,Xθ∈RStr×NX_V, X_\theta\in\mathbb{R}^{S_{\mathrm{tr}} \times N} stack centered magnitudes and circularly centered angles:

XV=WVΣVUVT,Xθ=WθΣθUθT,Pk=UkUkT,(1)X_V = W_V \Sigma_V U_V^{\mathsf{T}}, \qquad X_\theta= W_\theta\Sigma_\theta U_\theta^{\mathsf{T}}, \qquad P_k = U_k U_k^{\mathsf{T}}, \tag*{(1)}

where Uk=diag⁡(UV,k,Uθ,k)U_k = \operatorname{diag}(U_{V,k}, U_{\theta,k}) contains the leading kk state-space directions per channel; k=16k = 16 denotes 16 per channel.

For calibrated error e=x^C−x⋆e = \hat{x}^{C} - x^\star,

e∥=Pke,e⊥=(I−Pk)e,x^−x⋆=b^+e∥+e⊥.(2)e^{\parallel} = P_k e, \qquad e^{\perp} = (I-P_k)e, \qquad\hat{x} - x^\star= \hat{b} + e^{\parallel} + e^{\perp}. \tag*{(2)}

Here, b^\hat{b} is the train-estimated mean bias, while e∥e^{\parallel} and e⊥e^{\perp} partition the remaining error into in- and off-subspace components.

Around a converged state with fixed topology and bus types,

r(x⋆+e;u)=r(x⋆;u)+J(x⋆;u)e+O(∥e∥2),(3)r(x^\star+ e;u) = r(x^\star;u) + J(x^\star;u)e + O(\lVert e\rVert^2), \tag*{(3)}

where r(x⋆;u)=0r(x^\star;u)=0 and JJ is the AC residual Jacobian; hence equal-norm errors can yield different residuals by orientation.

Motivated by this orientational sensitivity, CSP first removes b^\hat{b} and then projects onto the dominant training-solution directions:

x^CSP=xˉtr+Pk(x^−b^−xˉtr)(4)\hat{x}^{\mathrm{CSP}} = \bar{x}_{\mathrm{tr}} + P_k\left(\hat{x} - \hat{b} - \bar{x}_{\mathrm{tr}}\right) \tag*{(4)}

where xˉtr\bar{x}_{\mathrm{tr}} is the training-solution mean; both xˉtr\bar{x}_{\mathrm{tr}} and PkP_k remain fixed at test time. Projection can remove prediction error but also discard valid reference variation. Let eC=x^C−x⋆e^{C} = \hat{x}^{C} - x^\star and eCSP=x^CSP−x⋆e^{\mathrm{CSP}} = \hat{x}^{\mathrm{CSP}} - x^\star. Since PkP_k is orthogonal,

∥eCSP∥22−∥eC∥22=∥(I−Pk)(x⋆−xˉtr)∥22−∥(I−Pk)eC∥22.(5)\lVert e^{\mathrm{CSP}}\rVert_2^2 - \lVert e^{C}\rVert_2^2 = \lVert(I-P_k)(x^\star-\bar{x}_{\mathrm{tr}})\rVert_2^2 - \lVert(I-P_k)e^{C}\rVert_2^2. \tag*{(5)}

Hence, CSP improves state accuracy when the removed off-subspace prediction-error energy exceeds the discarded reference variation.

CSP is a lightweight, data-driven post-hoc output correction rather than a projection onto the nonlinear AC-feasible set; it therefore does not guarantee exact feasibility, but can improve physical consistency when the removed off-subspace components are residual-sensitive under the local AC Jacobian.

Experiments and Results

Our primary study uses 37,022 converged pandapower Newton–Raphson operating points on the 2224-bus GBnetwork, split 1:1:1 for training/validation/test. The dataset combines global load/generation scaling with independent load P/QP/Q and active-generation perturbations; the backbone topology and PV–voltage control schedule remain fixed. We evaluate PIGNN-GC, our global-context extension of PIGNN-AttnL5 [25] retaining its line-search, GridSFM [15], gridfm-graphkit [16], and LUMINA [18]; GridSFM is also evaluated cross-grid on 31 systems.

All models are trained from scratch using model-specific stable initialization, and CSP is evaluated within each frozen model. gridfm-graphkit uses its released architecture/configuration without a pretrained checkpoint. Both GridSFM and LUMINA retain their released backbones and are adapted from AC-OPF to AC-PF by fixing generator dispatch, predicting only voltage states with PF-specific residuals, and applying known-variable masking. All models use pre-solution pandapower [1, 30] internal PPC-derived inputs. Training and inference use one NVIDIA H100 96-GB GPU; inference timing uses the largest memory-fitting batch to maximize GPU utilization. Calibration statistics and solution bases use training data only. From k∈{4,8,16,32,64}k \in\{4, 8, 16, 32, 64\}, validation Mean PB selects k⋆=16k^\star= 16 without degrading calibrated voltage-magnitude RMSE and is frozen for test and distribution-shift experiments. Unless otherwise stated, mechanistic, ablation, and cross-grid analyses use model seed 42, whereas Tables 1 and 3 aggregate seeds 41–43.

Voltage RMSE alone can be small even when a model largely predicts a static per-bus profile rather than following scenario-dependent voltage variation [15]. To isolate this scenario-dependent response, we center each bus as V~is=Vis−Vˉi\tilde{V}_{is}=V_{is}-\bar{V}_i and V^~is=V^is−V^ˉi\tilde{\hat{V}}_{is}=\hat{V}_{is}-\bar{\hat{V}}_i, and report

Rw2=corr⁡2(V~is,V^~is),aw=Cov⁡(V~is,V^~is)Var⁡(V~is).(6)R_w^2 = \operatorname{corr}^2(\tilde{V}_{is},\tilde{\hat{V}}_{is}), \qquad a_w = \frac{\operatorname{Cov}(\tilde{V}_{is},\tilde{\hat{V}}_{is})}{\operatorname{Var}(\tilde{V}_{is})}. \tag*{(6)}

Rw2R_w^2 is the squared correlation between the within-bus-centered prediction and reference across all bus–scenario pairs, while awa_w measures the scale of the predicted variation relative to the true variation.

Off-subspace error and directional sensitivity.

Off-subspace error: Off-subspace error is substantial across models and is positively associated with Mean PB. Although the rank-16 basis explains 98.8%/99.7% of training voltage-magnitude/angle variation, the median scenario-wise fractions of total squared error lying outside the respective subspaces are 26.3/55.0/56.8/27.1% for magnitude and 10.3/2.7/39.6/31.7% for angle, for PIGNN-GC/GridSFM/gridfm-graphkit/LUMINA, respectively. After accounting for differences in total error norms, scenarios with larger off-subspace fractions have higher Mean PB, with partial Spearman correlations of .659/.635/.594/.833 for magnitude and .789/.906/.809/.860 for angle (all 95% CIs exclude zero).

Table 1. GBnetwork results at k=16k = 16. All models report mean ±\pm standard deviation over three model seeds. CC denotes calibration, P16P_{16} projection, and CSP16_{16} their composition. Inference time is GPU-synchronized forward execution plus the corresponding output transform, reported per scenario.

ModelOutputVV RMSE ↓\downarrowθ\theta RMSE (°) ↓\downarrowRw2↑R_w^2 \uparrowawa_wMean PB ↓\downarrowMax PB ↓\downarrowInference (ms/scen.)
Per-bus meanBaseline.023416.847.000.000.120845.88–
PIGNN-GCRaw.02850±\pm.002321.108±\pm.175.671±\pm.050.546±\pm.072.31592±\pm.03240195.89±\pm52.5410.034±\pm.023
CC.01393±\pm.00105.777±\pm.161.671±\pm.050.546±\pm.072.16661±\pm.02352190.00±\pm37.5310.028±\pm.023
P16P_{16}.01624±\pm.002541.091±\pm.166.829±\pm.045.541±\pm.071.07594±\pm.004225.07±\pm.8510.036±\pm.023
CSP16_{16}.01222±\pm.00134.835±\pm.141.829±\pm.045.541±\pm.071.05497±\pm.002573.93±\pm.0710.034±\pm.032
GridSFMRaw.02868±\pm.016522.294±\pm.302.768±\pm.151.724±\pm.149.26867±\pm.130049.10±\pm4.0225.045±\pm.207
CC.01086±\pm.004031.781±\pm.055.768±\pm.151.724±\pm.149.08251±\pm.010937.29±\pm3.5325.015±\pm.096
P16P_{16}.01814±\pm.011452.244±\pm.325.936±\pm.032.724±\pm.149.07630±\pm.019425.08±\pm.4925.087±\pm.279
CSP16_{16}.00782±\pm.003071.807±\pm.053.936±\pm.032.724±\pm.149.05136±\pm.001434.94±\pm.4224.577±\pm.091
gridfm-graphkitRaw.00892±\pm.00154.385±\pm.042.905±\pm.030.811±\pm.045.09282±\pm.0176319.82±\pm8.655.917±\pm.019
CC.00753±\pm.00118.367±\pm.042.905±\pm.030.811±\pm.045.07685±\pm.0130718.88±\pm8.695.730±\pm.004
P16P_{16}.00617±\pm.00099.503±\pm.018.959±\pm.008.801±\pm.044.04593±\pm.001565.36±\pm.565.723±\pm.011
CSP16_{16}.00606±\pm.00090.496±\pm.021.959±\pm.008.801±\pm.044.04571±\pm.001355.08±\pm.185.779±\pm.012
LUMINARaw.02653±\pm.000312.703±\pm.313.443±\pm.014.346±\pm.0121.29896±\pm.85056664.19±\pm448.007.548±\pm.369
CC.01780±\pm.000201.442±\pm.060.443±\pm.014.346±\pm.012.21432±\pm.0118620.65±\pm15.827.380±\pm.155
P16P_{16}.01898±\pm.000492.160±\pm.268.906±\pm.012.338±\pm.012.07641±\pm.001285.47±\pm.567.981±\pm.868
CSP16_{16}.01570±\pm.000241.282±\pm.058.906±\pm.012.338±\pm.012.06662±\pm.000744.61±\pm.197.891±\pm.567

Table 1.

Fixed-norm intervention. At fixed error norm, suppressing off-subspace error consistently lowers Relative Mean PB across all four surrogates, whereas suppressing in-subspace error has the opposite effect (Figure 2), isolating error orientation from error magnitude. We test this with an oracle diagnostic using the known reference state, varying the voltage-magnitude error orientation at fixed ℓ2\ell_2 norm:

Fixed-norm directional intervention plots

Figure 2. Fixed-norm directional intervention on GBnetwork, with Relative Mean PB normalized at α=1\alpha= 1.

e~(α)=∥eV∥2eV∥+αeV⊥∥eV∥+αeV⊥∥2(7)\tilde{e}(\alpha)=\lVert e_V\rVert_2\frac{e_V^{\parallel}+\alpha e_V^{\perp}}{\lVert e_V^{\parallel}+\alpha e_V^{\perp}\rVert_2} \tag*{(7)}

where phase angles remain at their calibrated predictions. Decreasing α\alpha suppresses off-subspace error; the control analogously suppresses the in-subspace component by exchanging eV∥e_V^{\parallel} and eV⊥e_V^{\perp}.

Jacobian sensitivity. Off-subspace directions are substantially more residual-sensitive than in-subspace directions under the local AC Jacobian, consistent with the fixed-norm intervention. Using directional gain g(d)=∥Jd∥2/∥d∥2g(d)=\lVert Jd\rVert_2/\lVert d\rVert_2, 32 random direction pairs at each of 128 held-out operating points yield a median paired off-/in-subspace gain ratio of 1,563×\times. The same gain contrast appears in the actual calibrated prediction errors: the ratios of median off- to in-subspace gains are 22.81×\times, 575.83×\times, 4.69×\times, and 6.51×\times for PIGNN-GC, GridSFM, gridfm-graphkit, and LUMINA, respectively. The observed error regime is consistent with the first-order expansion in Eq. (3), with median linearized-to-nonlinear residual-change ratios between 0.996 and 1.009 across all four models.

Solution subspace specificity.

Our matched-basis comparison shows that preserving the same amount of reference-state variation is insufficient for low PB, indicating that the specific state-space directions retained by the basis are important. We compare SVD16_{16} with graph-Laplacian and spatial low-pass controls, each tuned using training references to match the V/θV/\theta variation retained by SVD16_{16}. On the test set, all three preserve nearly identical reference variation (Table 2), yet the alternatives yield substantially larger PB for both projected references and corrected predictions.

BasisRef. var. retained (%)Ref. PBPred. PB
SVD (16/16)98.789/99.683.0415.0569
Laplacian matched (1750/2122)98.819/99.68826.1526.22
Spatial matched (β=.357/.208\beta= .357/.208)98.801/99.6846.206.22

Table 2. Matched basis comparison on GBnetwork for PIGNN-GC. Parentheses denote V/θV/\theta ranks or smoothing strengths.

Post-training CSP correction

Table 1 compares Raw, CC, P16P_{16}, and CSP16_{16} across the four frozen surrogates. Relative to CC, CSP reduces Mean PB by 67.0%, 37.8%,

ends_mid=1 40.5%, and 68.9%, respectively, while lowering voltage-magnitude RMSE in all four models. Projection improves Rw2R_w^2 with little change in awa_w; angle accuracy is model dependent. Raw and CSP16 inference times are comparable.

Magnitude-only, angle-only, and full projection show model-dependent effects of angle projection. PIGNN-GC achieves the lowest PB with full CSP, whereas GridSFM performs best with magnitude-only projection. For gridfm-graphkit, adding angle projection reduces Mean/Max PB from .0612/18.23 to .0457/5.08, but degrades angle RMSE from .367° to .496°. For LUMINA, it reduces Mean/Max PB from .1939/38.53 to .0660/4.51 while improving angle RMSE from 1.374° to 1.215°. Thus, better physical consistency from angle projection need not imply better angle accuracy.

These model-dependent accuracy changes are explained by Eq. (5). For magnitude, the removed off-subspace prediction-error energy exceeds the discarded reference variation across all four models. For angle, the balance differs across models: in gridfm-graphkit, angle projection discards more valid reference variation than model error and therefore worsens angle RMSE, whereas the opposite holds for LUMINA.

Complementarity with one-step Newton refinement.

CSP provides a consistently better initialization for one-step Newton refinement, improving both state accuracy and post-update physical consistency across all four models. Starting from CC or CSP16_{16}, we apply one Newton update (NR1) to non-slack angles and PQ voltage magnitudes, with validation-selected damping factor; η=1\eta= 1 is selected for all models, with no linear-solve failures. Relative to CC initialization, CSP lowers magnitude and angle RMSE in all models and reduces post-update Mean PB by 21.1–96.4% (Table 3).

ModelStartVV RMSE (10−310^{-3})θ\theta RMSE (°)Mean PB (10−310^{-3})
PIGNN-GCCC1.80±.121.80\pm.12.119±.013.119\pm.0132.84±.462.84\pm.46
CSP16_{16}1.17±.101.17\pm.10.073±.009.073\pm.0091.48±.131.48\pm.13
GridSFMCC11.86±6.7711.86\pm6.77.681±.380.681\pm.3802.50±1.542.50\pm1.54
CSP16_{16}.97±.20.97\pm.20.059±.013.059\pm.0131.22±.291.22\pm.29
gridfm-graphkitCC.943±.232.943\pm.232.0843±.0236.0843\pm.0236.941±.325.941\pm.325
CSP16_{16}.496±.085.496\pm.085.0277±.0041.0277\pm.0041.742±.080.742\pm.080
LUMINACC13.71±9.2313.71\pm9.23.671±.038.671\pm.03846.08±64.1546.08\pm64.15
CSP16_{16}1.040±.0161.040\pm.016.0802±.0031.0802\pm.00311.653±.0361.653\pm.036

Table 3. One Newton update from calibrated or CSP16_{16} outputs on GBnetwork. VV RMSE and Mean PB are reported in 10−310^{-3}. Values are means ±\pm standard deviations over three model seeds.

The benefit is particularly pronounced for LUMINA: CC + NR1 shows a large one-seed overshoot despite a successful linear solve, whereas CSP16_{16} initialization remains consistent across seeds.

Cross-grid breadth and distribution shift

Cross-grid breadth. CSP reduces GridSFM Mean PB across all 31 systems (Figure 3), spanning 4–9,241 buses and sub-kV to 750-kV levels. The set includes 28 pandapower/PYPOWER-format systems from IEEE, PEGASE, RTE, and GB benchmark families, plus three Common Information Model (CIM)-based networks. For each system, calibration and subspace statistics are fitted from its training data,

GridSFM power-balance consistency across 31 grids

Figure 3. Grid-by-grid physical consistency of GridSFM before and after CSP16_{16} across 31 systems ordered by bus count. Mean PB is shown on a logarithmic scale.

ConditionVV RMSERw2R_w^2 ↑awa_wMeanMed.p95p99Max
Control.01281.01281.8476.8476.4866.4866.0581.0581.0131.0131.2665.2665.5462.54623.583.58
NN–1 (T).01314.01314.8391.8391.4750.4750.0600.0600.0131.0131.2713.2713.5632.563233.1633.16
NN–2 (T).01288.01288.8458.8458.4870.4870.0617.0617.0132.0132.2713.2713.5721.572127.4527.45
GBcorr (T).01966.01966.4819.4819.4025.4025.1003.1003.0231.0231.4512.4512.9746.97467.007.00
GBcorr (R).01620.01620.5150.5150.4247.4247.0680.0680.0174.0174.3031.3031.6415.64154.994.99

Table 4. PIGNN-GC with fixed-rank CSP16_{16} under topology and operating-distribution shifts. T transfers the control calibration and basis, whereas R refits both on condition-matched training data.

using nominal k=16k = 16 per channel and the available SVD components on smaller systems. PV-voltage setpoints vary for most systems, but are fixed for GBnetwork with conflicting controllers.

Topology and spatial shifts. CSP remains stable in most statistics under NN–1/NN–2 topology shifts, with degradation concentrated in isolated worst-case violations, whereas GBcorr causes a broader performance drop. Under the topology shifts, voltage accuracy, tracking, and bulk PB remain close to control, with larger maxima motivate worst-case assessment beyond average error. GBcorr applies correlated, spatially varying load scaling across 14 zones while preserving total demand and generation settings. Transferring both calibration and basis gives Mean PB of 0.1003 p.u.; refitting calibration alone reduces this to 0.0944, basis alone to 0.0740, and both to 0.068. Although the transferred/refitted bases retain 93.55%/98.53% of GBcorr magnitude variation, projecting converged GBcorr references yields Mean PBs of 0.0868/0.0438 p.u., respectively. This reference-only diagnostic isolates the effect of basis transfer from surrogate error and helps explain the improvement from basis refitting.

CONCLUSION

This work identifies output-error geometry as an important factor in the gap between voltage accuracy and physical consistency in neural AC power-flow surrogates. Across four architecturally diverse neural surrogates, we show that small voltage errors can contain off-subspace components that induce large AC power-balance violations. Building on this insight, calibrated solution-subspace projection suppresses these components, reducing voltage-magnitude error and power-balance residuals without retraining; the residual reduction extends to 30 additional grids. These results suggest that error direction, not only magnitude, should inform surrogate evaluation and design. They also motivate extending physics-consistent neural surrogates toward broader power-system analysis, estimation, and optimization.

References

References

  1. [1]R. D. Zimmerman, C. E. Murillo-Sánchez, and R. J. Thomas, “MATPOWER: Steady-state operations, planning, and analysis tools for power systems research and education,” IEEE Transactions on Power Systems, vol. 26, no. 1, pp. 12–19, Feb. 2011.DOI
  2. [2]Timon Conrad, Marco Pröll, David Riebesel, and Johann Jäger, “Framework for congestion management using particle swarm optimisation,” in Proc. 61st Int. Universities Power Engineering Conf. (UPEC), 2026.
  3. [3]V. Bolz, J. Rueß, and A. Zell, “Data-driven graph convolutional neural networks for power system contingency analysis,” in Proc. IEEE Int. Conf. Acoust., Speech Signal Process. (ICASSP), 2023, pp. 1–5.DOI
  4. [4]S. M. Frank, I. Steponavice, and S. Rebennack, “Optimal power flow: A bibliographic survey I: Formulations and deterministic methods,” Energy Systems, vol. 3, no. 3, pp. 221–258, 2012.
  5. [5]D. Owerko, F. Gama, and A. Ribeiro, “Optimal power flow using graph neural networks,” in Proc. IEEE Int. Conf. Acoust., Speech Signal Process. (ICASSP), 2020, pp. 5930–5934.arxiv.org/abs/1910.09658
  6. [6]G. Cheng, Y. Lin, A. Abur, A. Gómez-Expósito, and W. Wu, “A survey of power system state estimation using multiple data sources: PMUs, SCADA, AMI, and beyond,” IEEE Transactions on Smart Grid, vol. 15, no. 1, pp. 1129–1151, 2024.
  7. [7]B. Donon, R. Clément, B. Donnot, A. Marot, I. Guyon, and M. Schoenauer, “Neural networks for power flow: Graph neural solver,” Electric Power Systems Research, vol. 189, pp. 106547, 2020.DOI
  8. [8]N. Lin, S. Orfandoudakis, N. Ordonez Cardenas, J. S. Giraldo, and P. P. Vergara, “PowerFlowNet: Power flow approximation using message passing graph neural networks,” International Journal of Electrical Power & Energy Systems, vol. 160, pp. 110112, 2024.arxiv.org/abs/2311.03415
  9. [9]D. Owerko, F. Gama, and A. Ribeiro, “Unsupervised optimal power flow using graph neural networks,” in Proc. IEEE Int. Conf. Acoust., Speech Signal Process. (ICASSP), 2024, pp. 6885–6889.
  10. [10]B. Jiang, C. Qin, and Q. Wang, “An unsupervised physics-informed neural network method for AC power flow calculations,” IEEE Transactions on Power Systems, vol. 40, no. 5, pp. 4407–4410, 2025.
  11. [11]T. Wen, W. Wang, J. Chen, and Z. Wang, “Power flow surrogate for power systems with high renewable penetration via a physics-informed graph attention network,” Energies, vol. 19, no. 13, pp. 2972, 2026.DOI
  12. [12]H. T. Nguyen and P. L. Donti, “FSNet: Feasibility-seeking neural network for constrained optimization with guarantees,” in Advances in Neural Information Processing Systems, 2025, vol. 38, pp. 44366–44404.arxiv.org/abs/2506.00362
  13. [13]P. L. Donti, D. Rolnick, and J. Z. Kolter, “DC3: A learning method for optimization with hard constraints,” in International Conference on Learning Representations, 2021.arxiv.org/abs/2104.12225
  14. [14]M. Chzhen and P. L. Donti, “Improving feasibility via fast autoencoder-based projections,” in International Conference on Learning Representations (ICLR), 2026.arxiv.org/abs/2604.03489
  15. [15]W. Yang, A. Britto Mattos Lima, T. V. Spina, S. Fowers, B. Zhang, and C. White, “GridFM: A foundation model for AC optimal power flow,” May 2026, Microsoft Research technical white paper.arxiv.org/abs/2609.30173
  16. [16]GridFM Team, “gridfm-graphkit,” Python package, version 0.9.0, 2026.
  17. [17]A. Puech et al., “GENCO—a unified neural solver embedded in a development framework for steady-state grid analysis,” arXiv preprint arXiv:2608.09921, 2026.arxiv.org/abs/2608.09921
  18. [18]Y. Li et al., “LUMINA: Foundation models for topology transferable ACOPF,” in ICLR 2026 Workshop on Foundation Models for Science: Real-World Impact and Science-First Design, 2026, arXiv:2603.04300.arxiv.org/abs/2603.04300
  19. [19]S. de Jongh, G. Gielnik, F. Mueller, L. Schmit, M. Suriyah, and T. Leibfried, “Physics-informed geometric deep learning for inference tasks in power systems,” Electric Power Systems Research, vol. 211, pp. 108362, 2022.DOI
  20. [20]R. Karim et al., “Parameter-efficient domain adaptation of physics-informed self-attention based GNNs for AC power flow prediction,” in Proc. Eur. Signal Process. Conf. (EUSIPCO), 2026, pp. 1941–1945.arxiv.org/abs/2602.18227
  21. [21]A. Ma, S. Ghamizi, A. Bojchevski, P. Zhang, and J. Cao, “SafePowerGraph: A safety-aware benchmarking framework for scalable graph neural networks in power flow and optimal power flow,” Energy and AI, vol. 25, pp. 100819, 2026.DOI
  22. [22]M. Shamseldein, “A hybrid GNN-LSE method for fast, robust, and physically-consistent AC power flow,” Electric Power Systems Research, vol. 252, pp. 112380, 2026.DOI
  23. [23]R. Nellikkath and S. Chatzivasileiadis, “Physics-informed neural networks for AC optimal power flow,” Electric Power Systems Research, vol. 212, pp. 108412, Nov. 2022.DOI
  24. [24]X. Hu, H. Hu, S. Verma, and Z.-L. Zhang, “Physics-guided deep neural networks for power flow analysis,” IEEE Transactions on Power Systems, vol. 36, no. 3, pp. 2082–2092, May 2021.DOI
  25. [25]C. Kim et al., “Physics-informed GNN for medium-high voltage AC power flow with edge-aware attention and line search correction operator,” in Proc. IEEE Int. Conf. Acoust., Speech Signal Process. (ICASSP), 2026.DOI
  26. [26]Shourya Bose, Helgi Hilmarsson, and Dhruv Suri, “Newton’s lantern: A reinforcement learning framework for fine-tuning ac power flow warm start models,” arXiv preprint arXiv:2605.11102, 2026.arxiv.org/abs/2605.11102
  27. [27]A. Goodwin, J. Maack, and D. Sigler, “Power flow geometry and approximation,” IEEE Transactions on Power Systems, vol. 41, no. 2, pp. 982–993, 2026.DOI
  28. [28]S. Park, W. Chen, T. W. K. Mak, and P. Van Hentenryck, “Compact optimization learning for AC optimal power flow,” IEEE Transactions on Power Systems, vol. 39, no. 2, pp. 4350–4359, Mar. 2024.arxiv.org/abs/2301.08840
  29. [29]Samuel Chevalier, Luca Schenato, and Luca Daniel, “Accelerated probabilistic power flow in electrical distribution networks via model order reduction and neumann series expansion,” IEEE Transactions on Power Systems, vol. 37, no. 3, pp. 2151–2163, 2022.arxiv.org/abs/2010.14995
  30. [30]L. Thurner et al., “pandapower—an open-source python tool for convenient modeling, analysis, and optimization of electric power systems,” IEEE Transactions on Power Systems, vol. 33, no. 6, pp. 6510–6521, Nov. 2018.DOI

Paper details

vlnc:W_7ahq6b7c
Version
v1 · latest
Published
Fresh — added to the Hub within the last 30 days
Added
License
CC BY 4.0
Usage

views · 0

downloads · 0

A view counts once per browser per day, a download each time the PDF is requested.

  • Computer Science

Not recorded for this paper

View statement
Looking for related papers…
Contents