Enhancing Grid Stability with Synchronverter-Based Control for Grid-Side Converters in Wind Power Systems

Abstract

This paper proposes a new synchronverter control strategy for wind turbine grid-side converters, aimed at bolstering grid resilience by providing essential inertial frequency support without the need for additional energy storage components. The strategy harnesses the inherent energy storage capability of the DC-link capacitor to emulate the dynamic behavior of a synchronous generator, effectively contributing to grid inertia. A dual-controller architecture is implemented, consisting of a slow PI controller to maintain DC voltage stability and a fast protection mechanism to prevent overvoltage and undervoltage excursions. Critically, the control scheme facilitates controlled reductions of up to 10% in the DC-link voltage, generating a power reserve that can be strategically deployed for inertia emulation while preserving safe operating limits. The efficacy of the proposed method is validated through simulations of a representative three-turbine wind power plant, incorporating coordinated operation via virtual friction for inter-machine damping and local-global control strategies. Results showcase the superior performance of the proposed strategy compared to conventional grid-following control, emphasizing its potential to significantly improve grid stability and address the increasing challenges posed by high renewable energy penetration.

Introduction

Electrical power systems (EPS) are transitioning due to the gradual replacement of fossil-fuel-based generation with renewable energy sources such as wind power [1, 2, 3]. This transformation has introduced critical challenges, particularly reducing system inertia resulting from replacing traditional synchronous machines with inverter-based renewable generation. Reduced inertia compromises frequency stability, particularly in systems with high renewable penetration [4, 5]. Consequently, to ensure grid reliability and resilience, it is imperative to develop advanced technical solutions and regulations for integrating distributed energy resources (DERs) into the grid [6].

Traditionally, frequency control has relied on the inertial response of synchronous machines, active power regulation via governors, and load-shedding mechanisms. However, these methods become less effective in isolated grids or systems with significant renewable energy penetration [3]. Wind turbines (WTs) have emerged as potential contributors to frequency support due to their ability to store kinetic energy, offering a straightforward inertial response. Despite this, traditional approaches, such as frequency droop and

virtual inertia control, face limitations in managing mechanical power effectively [3]. Moreover, restoring turbines to maximum power point tracking (MPPT) post-frequency events can induce further frequency drops, aggravating grid instability [5].

Deloading strategies, where wind turbines operate below their optimal points to reserve energy for frequency support, offer another option for providing power reserves [7, 8]. However, this strategy imposes mechanical stress, reducing turbine lifespan and efficiency. This underscores the necessity for innovative control methods that avoid deloading while enhancing system stability.

Recent advancements in power electronics have highlighted the potential of grid-forming converters to address these challenges. Synchronverter-based control, which enables converters to emulate synchronous generator dynamics, has emerged as a promising strategy. Studies such as [9, 10] have demonstrated the effectiveness of synchronverter control in improving frequency stability in doubly fed induction generator (DFIG) systems. The foundational principles of synchronverter control have been established in prior studies [11, 12], where both the rotor-side converter and the grid-side converter are operated as synchronverters. The rotor-side converter is tasked with maintaining the DC link voltage, while the grid-side converter regulates the maximum power point tracking (MPPT).

Grid-forming inverters, integrated with advanced synchronverter control strategies, further enhance system stability. For instance, [13, 14] emphasized their critical role in providing current-limiting functionalities and maintaining grid resilience. Experimental validations in [15] confirmed the effectiveness of synchronverter-based controls in addressing power quality and stability challenges.

This paper proposes a novel synchronverter-based control for permanent magnet synchronous generator (PMSG) wind turbines, focusing on the grid-side converter. The proposed control integrates virtual friction for inter-machine damping and dual-layer DC voltage regulation to emulate inertia, as outlined in [16].

The paper is structured as follows: Section II provides an overview of PMSG-based wind turbines. Section III details the proposed synchronverter-based control strategy, emphasizing DC voltage regulation. Section IV presents simulation studies and case analyses validating the proposed method. Finally, § 5 concludes with insights and future research directions.

Permanent Magnet Synchronous Generators (PMSG)-Based Wind Turbines

The capacity of wind turbines has significantly increased, evolving from kilowatt-scale systems to multi-megawatt installations. [17] This steady increase in power level and grid penetration has driven the development of advanced generators, power converter systems, and control solutions to ensure seamless grid integration. Among the most prominent designs, the direct-drive permanent magnet synchronous generator (PMSG) concept has gained significant traction, primarily due to its elimination of the gearbox [7, 17]. PMSG-based wind power systems represent a pivotal trend in modern wind generation technologies [7, 17, 18].

The AC–DC–AC converter topology is widely regarded as the optimal solution for two primary objectives: maximizing power extraction from wind and delivering high-quality electricity to the grid [7, 17, 18]. Full-scale power converters in PMSG-based wind turbines are particularly advantageous, as they fully decouple the turbine from grid disturbances and provide the potential for grid support. These converters offer high reliability and superior power quality and may eliminate the need for bulky grid-side transformers, thereby reducing the weight and volume of the nacelle [17, 19].

A typical PMSG-based wind turbine features a back-to-back converter configuration, comprising a machine-side converter (MSC), a DC-link capacitor, and a grid-side converter (GSC), as illustrated in Figure 1.

Figure 1. A typical configuration of a direct-drive PMSG-based wind power.

Control of machine (generator)-side (MSC)/grid-side (GSC) converters

The machine-side converter typically employs field-oriented control (FOC) for generator speed regulation. This strategy involves an outer speed control loop and an inner current control loop, often implemented using PI controllers in the synchronous reference frame [20]. The q-axis stator current component governs the electromagnetic torque, while the d-axis current is set to zero to maximize torque for a given current magnitude [21, 22].

The grid-side converter commonly uses a voltage-oriented control (VOC) strategy to regulate DC-link voltage and ensure balanced, unity power factor operation at the point of common coupling (PCC). VOC also employs dual-loop control, with an outer voltage loop and an inner current loop, enabling instantaneous decoupling of active and reactive current components in the synchronous reference frame [21]. This approach ensures fast transient response, high steady-state performance, and minimal power ripple. Traditionally, the MSC manages the power flow from the generator, while the GSC maintains the DC-link voltage and controls the power flow to the grid in compliance with grid requirements [17].

Proposed Control Strategy for Synconverter-Based Grid-Side Converter

The proposed control strategy employs a grid-forming (GFM) approach, ensuring autonomous synchronization and robustness against network disturbances [23]. This overcomes the reliance of traditional grid-following (GFL) controls on external grid conditions for synchronization.

Modern grid codes demand that power electronic devices provide frequency support mechanisms such as droop control and inertia emulation. This necessitates the adoption of GFM features in power converters. The Virtual Synchronous Machine (VSM) approach has emerged as a widely studied technique for meeting these requirements, enabling power converters to emulate the dynamics of synchronous generators. This facilitates inertia and frequency support, enhancing grid stability and enabling the seamless integration of renewable energy sources [24, 25].

Model of Synconverter

Figure 2 illustrates a simplified representation of the grid-side converter of a wind turbine based on PMSG. Active and reactive power setpoints (PrefP_{ref} and QrefQ_{ref}) serve as inputs to the synconverter, which generates control signals for the pulse-width modulation (PWM) unit to operate the power converter.

Figure 2. The simplified power circuit of an inverter.

The synconverter model implemented in this study is based on the framework described in [25], adapted for the grid-side converter of a wind turbine equipped with a PMSG. This model effectively replicates the dynamic behavior of a synchronous generator, allowing for frequency support using the energy stored in the DC-link capacitor, eliminating the need for dedicated energy storage hardware.

Integration of Virtual Friction

To further enhance the stability of interconnected wind turbines, the Virtual Friction (VF) mechanism is integrated into the synconverter model. VF is a control strategy that improves damping in VSMs by introducing an additional torque that counteracts frequency deviations. Unlike traditional damping methods (e.g., frequency droop and damper windings), VF relies on real-time communication between VSMs to calculate a global reference: the center of inertia (COI) frequency ωc\omega_c.

The COI frequency is calculated as a weighted average of the frequencies of all interconnected VSMs [26]:

ωc=∑k=1nωjJk∑k=1nJk(1)\omega_c = \frac{\sum_{k=1}^{n} \omega_j J_k}{\sum_{k=1}^{n} J_k} \tag*{(1)}

Here Jk>0J_k > 0 is the moment of inertia of VSM kk.

By using remote frequency information, VF applies an additional damping torque to the swing equation of each VSM, proportional to the deviation of the virtual rotor frequency from ωc\omega_c. This approach significantly reduces inter-machine oscillations, ensuring stable power output even during large frequency transients. Moreover, VF can emulate viscous friction in a synchronous generator, with the friction torque acting solely on the synchronverter rotor.

Fig. 3 illustrates the calculation of the damping torque TdT_d for the VSMs. The VF torque is defined as F⋅(ω−ωc)F\cdot(\omega-\omega_c), where FF is the VF coefficient. This damping ensures that frequency deviations among turbines are minimized, even during significant frequency events, maintaining active power output within acceptable limits and ensuring stable operation of the VSMs under dynamic conditions [27].

Figure 3. Simplified block diagram of the VF in a VSM [26].

The integration of VF and COI calculation relies on real-time communication between turbines, a feature that has proven critical for managing dynamic interactions in multi-turbine configurations [26]. By combining local droop control with global VF-based damping, this strategy achieves superior performance in both isolated and grid-connected scenarios, aligning with the requirements of modern renewable energy systems.

DC Voltage Regulation

The control strategy proposed for the GSC of wind turbines employs a VSM-based approach to enable frequency support without additional hardware. By leveraging the inherent flexibility of the DC-link, the system allows controlled variations in the wind turbine's total output power within a narrow range, creating an energy reserve for inertia emulation. In this study, the DC-link voltage is designed to operate within predefined limits, enabling the VSMs to emulate inertia effectively. This approach builds upon the model outlined in [16], ensuring both frequency stability and safe operation under dynamic grid conditions.

To achieve this, a dual-layer DC voltage control mechanism is implemented. The first layer consists of a slow DC voltage control loop based on a conventional proportional-integral (PI) control that regulates the DC voltage over longer timescales. This slow control ensures long-term stability by gradually restoring the voltage to its reference value after disturbances. It leverages the energy stored in DC-link capacitors for inertia emulation, adjusting the active power setpoint (PrefP_{\mathrm{ref}}) of the VSM based on the tracking error. This approach prevents abrupt changes, avoids counteracting the inertial response, and minimizes voltage excursions.

In addition, a fast voltage protection mechanism prevents DC voltage excursions beyond permissible thresholds. This mechanism directly modifies the output current controllers (OCCs) of the VSM, bypassing the slower dynamics of the PI controller. When the DC voltage drops below a lower threshold (VlowV_{\mathrm{low}}) or exceeds an upper threshold (VhighV_{\mathrm{high}}), the mechanism dynamically limits the reference current (IrefI_{\mathrm{ref}}) in the VSM to constrain the active power flow.

The protection scheme operates by adjusting the reference current IrefI_{\mathrm{ref}} based on DC voltage conditions. The active current component (IaI_a), is calculated as the projection of the virtual current (IvirtI_{\mathrm{virt}}) onto the grid voltage vector (VV), normalized by the magnitude of the voltage:

Ia=V∣V∣⟨Ivirt,V⟩∣V∣(2)I_a = \frac{V}{\lvert V\rvert}\frac{\langle I_{\mathrm{virt}},V\rangle}{\lvert V\rvert} \tag*{(2)}

Here, the term ⟨Ivirt,V⟩\langle I_{\mathrm{virt}},V\rangle represents the inner product between IvirtI_{\mathrm{virt}} and VV. The reactive current component (IrI_r) is then obtained as the difference between the virtual current and its active current, Ir=Ivirt−IaI_r=I_{\mathrm{virt}}-I_a. To address rapid DC voltage fluctuations, the mechanism incorporates voltage-dependent adjustments, defined as:

iv=⟨Ivirt,V⟩∣V∣(3)i_v=\frac{\langle I_{\mathrm{virt}},V\rangle}{\lvert V\rvert} \tag*{(3)}

where ivi_v can be decomposed into its positive and negative components. That is iv+=max⁡{iv,0}i_v^+=\max\{i_v,0\} and iv−=max⁡{−iv,0}i_v^-=\max\{-i_v,0\}, respectively. These components are subsequently used to compute the modified reference current.

Iref=Ia+Ir=V∣V∣iv+β++V∣V∣iv−β−+Ir(4)I_{\mathrm{ref}}=I_a+I_r=\frac{V}{\lvert V\rvert}i_v^+\beta^+ + \frac{V}{\lvert V\rvert}i_v^-\beta^- + I_r \tag*{(4)}

Here β+\beta^+ and β−\beta^- are dynamic limitation factors that scale the adjustments based on the DC voltage from its nominal range. As shown in Figure 4, these factors define three distinct operating zones. In the nominal range, both β+\beta^+ and β−\beta^- are one, and no corrective actions are required. In the transition zones, near the voltage thresholds, the factors vary linearly to apply smooth corrective adjustments. Finally, in the protection zones, the limitation factors saturate to their maximum values to strictly constrain the reference current and safeguard against over-voltage or under-voltage conditions.

Figure 4. The limitation factor β\beta as a function of the DC voltage.

Figure 5 illustrates the phasor relationships between the grid voltage v=vd+jvqv=v_d+\mathrm{j}v_q, the output current i=id+jiqi=i_d+\mathrm{j}i_q, and the internal virtual voltage of the VSM, under different power flow conditions. Figure 5(a) shows the case where the converter injects active power, with the dqdq reference frame aligned to the virtual rotor, highlighting how the active current component IaI_a is modulated through the limitation factor β+\beta^+, where β+∈[0,1]\beta^+\in[0,1]. Conversely, Figure 5(b) illustrates the scenario where the converter absorbs active power.

Figure 5. Phasor diagram of the output current ii, the grid voltage vv and the internal virtual voltage of the VSM: (a) when the inverter injects active power, (b) when the inverter absorbs active power.

By integrating the slow PI controller with the fast voltage protection mechanism, this dual-layer strategy achieves robust DC voltage regulation. The approach balances long-term stabilization with immediate corrective actions, enabling the system to provide effective inertia emulation and grid support while safeguarding against voltage excursions.

It is important to note that, for the wind turbine, the VSM-based control is applied exclusively to the GSC. Additionally, it is assumed that no power flows from the grid to the wind turbine, meaning the DC-link capacitor is charged solely by the energy transferred from the turbine to the grid. As a result, our control strategy focuses specifically on the inverter's behavior during power injection, as shown in Figure 5(a), and on the influence of the limitation factor β+\beta^{+} in shaping the system’s dynamic response.

Case Studies

To evaluate the performance of the proposed control, we consider a simplified grid of a 15 MW synchronous generator (SG), an 8 MW aggregated load, and a 6 MW wind power plant (WPP) consisting of three 2 MW permanent magnet synchronous generator wind turbines (PMSG-WTs) as shown in Figure 6. The synchronous generator operates at 690 V, 50 Hz, and 1800 rpm, with an inertia constant of H=1H = 1 s, and is equipped with a conventional speed governor and a constant voltage excitation system. Although the specific prime mover is not explicitly modeled, the configuration is representative of conventional thermal generation units such as gas turbines or steam turbines and thus provides a realistic benchmark for evaluating the dynamic interaction between synchronous and converter-based generation.

Power system with integration of a wind power plan (WPP)

Figure 6. Power system with integration of a wind power plan (WPP).

Each wind turbine is connected to the grid through a back-to-back converter topology, with the grid-side converter being the focus of the control strategy analysis. Two control approaches are compared: (i) a conventional grid-following (GFL) control based on a phase-locked loop (PLL) and current control loop [27], and (ii) the proposed synchronverter-based control.

The DC-link capacitor is rated at Cdc=200C_{dc} = 200 mF, with a nominal voltage of Vdcnom=1200V_{dc nom} = 1200 V. The operational limits are defined as Vmax=1.10V_{max} = 1.10 p.u. and Vmin=0.90V_{min} = 0.90 p.u., with warning thresholds at Vhigh=1.05V_{high} = 1.05 p.u. and Vlow=0.95V_{low} = 0.95 p.u.

The synchronverter control parameters are designed for a 2 MW base system at 690 V RMS, following the methodology in [25, 26], with a virtual inertia constant Hv=0.15H_v = 0.15 s and a virtual friction F=5F = 5.

Simulations are conducted in MATLAB/Simulink under identical operating conditions for both control strategies. The first simulation scenario examines the system’s response to a gradual increase in wind speed, from Vw=10V_w = 10 m/s to Vw=12V_w = 12 m/s, beginning at t=5t = 5 s with a 3-second linear ramp. This scenario assesses the controllers’ ability to regulate the DC-link voltage under variable wind power injection—a common challenge in renewable energy systems.

Figure 7(a) shows the active power output of a single wind turbine under both control strategies. The results indicate similar dynamic behavior across turbines, with the proposed control effectively responding to the power injection variation caused by the wind speed change. Figure 7(b) presents the corresponding DC voltage profiles. The synchronverter-based control maintains the DC voltage within the defined boundaries, while the conventional GFL control exhibits a slower response, although it still manages to track the wind power variation.

Active power output and corresponding DC-link voltage response

Figure 7. (a) Active power output of a single wind turbine under different control strategies; (b) Corresponding DC-link voltage response.

To further evaluate the robustness of the proposed control under grid disturbances, a second scenario introduces a contingency event at t=5t = 5, simulating a sudden load increase that results in a frequency drop when the wind turbine is operating under a Vw=12V_w = 12 m/s. Figure 8(a) shows the active power of one WT under each control strategy, here we can see a rapid inertial power injection by our proposed control, reaching a peak of Pwt=1.048P_{wt} = 1.048 p.u. at t=5.06t = 5.06 s, which helps counteract the frequency deviation.

Active power output and DC-link voltage response under different control strategies

Figure 8. (a) Active power output of DC-link voltage response under different control strategies, (b) DC link voltage response under different control strategies.

Figure 8(b) illustrates the DC-link voltage response during the disturbance. As the converter delivers inertial support, the voltage momentarily drops to the lower threshold of 0.9 p.u., but quickly recovers to its nominal value, demonstrating the controller’s ability to manage energy exchange effectively without compromising voltage stability.

The frequency response comparison, illustrated in Figure 9, shows that the proposed control achieves a lower frequency nadir (fmin=49.09f_{min} = 49.09 Hz at t=5.31t = 5.31 s) compared to the GFL control (fmin=49.30f_{min} = 49.30 Hz at t=5.28t = 5.28 s), indicating a more effective contribution to frequency support during transient events. This improvement is particularly relevant in low-inertia systems, where converter-based generation must increasingly take on the role of frequency regulation traditionally provided by synchronous machines.

Comparison of system frequency response

Figure 9. Comparison of system frequency response.

Overall, the simulation results confirm that the synchronverter-based control strategy not only enhances DC-link voltage regulation under variable wind conditions but also provides effective virtual inertia support during grid disturbances. This leads to improved frequency stability and dynamic performance, making it a promising solution for integrating converter-interfaced renewable energy sources in weak or isolated power systems.

Conclusions

This study has demonstrated the effectiveness of a synchronverter-based control strategy for PMSG wind turbines in enhancing grid stability and frequency support. By leveraging the energy stored in the DC-link capacitor and incorporating virtual friction mechanisms, the proposed approach enables inertia emulation and inter-machine damping, contributing to a more resilient and stable power system. Notably, this is achieved without the need for additional hardware, offering a cost-effective and practical solution for renewable energy integration. While the results are promising, validation is currently limited to a specific grid setup. Future work will extend the analysis to diverse grid conditions and include experimental testing to assess real-world feasibility and the trade-offs of DC-link voltage reduction.

Further research will address scalability, integration with other renewable technologies, and comparative studies with alternative inertia emulation strategies. Additionally, coordinated control with synchronous generators will be explored to improve frequency response and load sharing in high-renewable systems.

Acknowledgment

The work of A. Valadez is supported by the European Union’s Horizon Europe research and innovation program under the Marie Sklodowska-Curie training network ModConFlex, contract number 101073558.

References

  1. [1]B. Fani, G. Shahgholian, H. Haes Alhelou, and P. Siano, “Inverter-based islanded microgrid: A review on technologies and control,” e-Prime - Advances in Electrical Engineering, Electronics and Energy, vol. 2, p. 100068, 2022, Doi: 10.1016/j.prime.2022.100068.DOI
  2. [2]H. Pishbahar, F. Blaabjerg, and H. Saboori, “Emerging grid-forming power converters for renewable energy and storage resources integration — A review,” *Sustainable Energy Technologies and Assessments*, vol. 60, p. 103538, 2023, Doi: 10.1016/j.seta.2023.103538.DOI
  3. [3]X. Ding, W. Lin, J. Xu, Y. Sun, L. Yao, and B. Mao, “Coordinated frequency control for isolated power systems with high penetration of DFIG-based wind power,” *CSEE Journal of Power and Energy Systems*, vol. 10, no. 4, pp. 1399–1414, 2024, doi: 10.17775/CSEEJ PES.2021.08230.
  4. [4]B. Hartmann, I. Vokony, and I. Táczi, “Effects of decreasing synchronous inertia on power system dynamics—Overview of recent experiences and marketisation of services,” *Int. Trans. Electr. Energy Syst.*, vol. 29, no. 12, p. e12128, 2019, doi: 10.1002/2050-7038.12128.DOI
  5. [5]X. Liu, Y. Liu, J. Liu, Y. Xiang, and X. Yuan, “Optimal planning of AC-DC hybrid transmission and distributed energy resource system: Review and prospects,” *CSEE Journal of Power and Energy Systems*, vol. 5, no. 3, pp. 409–422, 2019, doi: 10.17775/CSEEJPES.2019.03.00007.DOI
  6. [6]B. Mohandes, M. S. El Moursi, N. D. Hatzigiargyriou, and S. El Khatib, “A review of power system flexibility with high penetration of renewables,” *IEEE Trans. Power Syst.*, vol. 34, no. 4, pp. 3140–3155, 2019, doi: 10.1109/TPWRS.2019.2897727.DOI
  7. [7]T. Ackermann, Wind Power in Power Systems. 2nd ed. Hoboken, NJ: Wiley, 2012.
  8. [8]Y. Bao, J. Xu, S. Liao, Y. Sun, X. Li, Y. Jiang, D. Ke, J. Yang, and X. Peng, “Field verification of frequency control by energy-intensive loads for isolated power systems with high penetration of wind power,” *IEEE Trans. Power Syst.*, vol. 33, no. 6, pp. 6098–6108, 2018, doi: 10.1109/TPWRS.2018.2796798.DOI
  9. [9]J. D. Araújo-de-Oliveira, F. K. de-Araújo-Lima, F. G. Nogueira, F. L. Tofoli, and C. G. Castelo Branco, "Stability analysis and application of a synchronverter-based control approach to DFIG-based wind energy conversion systems," *Electric Power Systems Research*, vol. 232, p. 110403, 2024. DOI: 10.1016/j.epsr.2024.110403.DOI
  10. [10]J. D. A. de Oliveira, F. K. de A. Lima, F. L. Tofoli, and C. G. C. Branco, "Synchronverter-based frequency control technique applied in wind energy conversion systems based on the doubly-fed induction generator," *Electric Power Systems Research*, vol. 214, p. 108820, 2023. Doi: 10.1016/j.epsr.2022.108820.
  11. [11]Z. Ma and Q.-C. Zhong, “Synchronverter-based control strategy for back-to-back converters in wind power applications,” *IFAC Proceedings Volumes*, vol. 45, no. 21, pp. 349–354, 2012, 8th Power Plant and Power System Control Symposium. [Online]. Doi: 10.3182/20120902-4-FR-2032.00062.DOI
  12. [12]Q.-C. Zhong, Z. Ma, W.-L. Ming, and G. C. Konstantopoulos, "Grid-friendly wind power systems based on the synchronverter technology," *Energy Conversion and Management*, vol. 89, pp. 719–726, 2015. DOI: 10.1016/j.enconman.2014.10.027.DOI
  13. [13]W. Schulze, P. Weber, M. Suriyah, and T. Leibfried, "Grid-forming synchronverter-based control method with current limiting method for grid-side converters of converter-based generation plants," in 21st Wind & Solar Integration Workshop (WIW 2022), vol. 2022, pp. 394–401, 2022. DOI: 10.1049/icp.2022.2802.
  14. [14]R. H. Lasseter, Z. Chen, y D. Pattabiraman, “Grid-forming inverters: A critical asset for the power grid,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp. 925–935, Jun. 2020, doi: 10.1109/JESTPE.2019.2930803.DOI
  15. [15]Z. Dekali, L. Baghli, T. Lubin, and A. Boumediene, “Grid Side Inverter Control for a Grid Connected Synchronous Generator Based Wind Turbine Experimental Emulator,” European Journal of Electrical Engineering, vol. 23, no. 1, pp. 1–7, Feb. 2021. DOI: 10.18280/ejee.230101.DOI
  16. [16]F. Reißner and G. Weiss, “Control of a HVDC transmission system with virtual synchronous machines providing virtual inertia,” (Submitted)
  17. [17]S. M. Tripathi, A. N. Tiwari, and D. Singh, “Grid-integrated permanent magnet synchronous generator based wind energy conversion systems: A technology review,” Renewable and Sustainable Energy Reviews, vol. 51, pp. 1288–1305, 2015, doi: 10.1016/j.rser.2015.06.060.DOI
  18. [18]J. A. Baroudi, V. Dinavahi, and A. M. Knight, “A review of power converter topologies for wind generators,” Renewable Energy, vol. 32, no. 14, pp. 2369–2385, 2007, doi: 10.1016/j.renene.2006.12.002.DOI
  19. [19]Z. Q. Zhu and J. Hu, “Electrical machines and power-electronic systems for high-power wind energy generation applications: Part II—power electronics and control systems,” COMPEL - The International Journal for Computation and Mathematics in Electrical and Electronic Engineering, vol. 32, no. 1, pp. 34–71, 2013, doi: 10.1108/03321641311293740.DOI
  20. [20]E. Levi, "FOC: Field-Oriented Control," in The Industrial Electronics Handbook, 2nd ed., B. M. Wilamowski and J. D. Irwin, Eds. Boca Raton, FL, USA: CRC Press, 2011, ch. 29.
  21. [21]N. Freire, J. Estima, and A. Cardoso, “A comparative analysis of PMSG drives based on vector control and direct control techniques for wind turbine applications,” Przegląd Elektrotechniczny, vol. 88, no. 1a, pp. 184–187, 2012.
  22. [22]M. Allagui, O. B. K. Hasnaoui, and J. Belhadj, “A 2MW direct drive wind turbine, vector control and direct torque control techniques comparison,” J. Energy South. Afr., vol. 25, no. 2, pp. 117–126, Jun. 2014, doi: 10.17159/2413-3051/2014/v25i2a2679.DOI
  23. [23]R. H. Lasseter, Z. Chen, and D. Pattabiraman, “Grid-forming inverters: A critical asset for the power grid,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp. 925–935, Jun. 2020, doi: 10.1109/JESTPE.2019.2930803.DOI
  24. [24]Q. C. Zhong and G. Weiss, “Synchronverters: Inverters that mimic synchronous generators,” IEEE Transactions on Industrial Electronics, vol. 58, no. 4, pp. 1259–1267, Apr. 2011, doi: 10.1109/TIE.2010.2048839.DOI
  25. [25]Z. Kustanovich, S. Shivatri, H. Yin, F. Reissner, and G. Weiss, “Synchronverters with fast current loops,” IEEE Transactions on Industrial Electronics, vol. 70, no. 11, pp. 11357–11367, Nov. 2023, doi: 10.1109/TIE.2022.32292275.DOI
  26. [26]F. Reißner, V. Mallemaci, F. Mandrile, I. R. Bojoi, and G. Weiss, “Virtual friction subjected to communication delays in a microgrid of virtual synchronous machines,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 11, no. 4, pp. 3910–3923, Aug. 2023, doi: 10.1109/JESTPE.2023.3276019
  27. [27]Gagnon, R., & Brochu, J. (n.d.). Wind Farm - Synchronous Generator and Full Scale Converter (Type 4) Average Model. Hydro-Québec. Retrieved from https://www.mathworks.com/help/sps/ug/wind-farm-synchronous-generator-and-full-scale-converter-type-4-average-model.html

Paper details

vlnc:W_a8dkqykx
Version
v1 · latest
Published
Fresh — added to the Hub within the last 30 days
Added
License
CC BY 4.0
Usage

views · 0

downloads · 0

A view counts once per browser per day, a download each time the PDF is requested.

  • Engineering

Not recorded for this paper

View statement
Looking for related papers…
Contents