betaFeedback

WorksEngineering

Multi-time-scale Control of Power Systems

Abstract

The power grid has been dominated by large synchronous generators and clearly separated control layers. Today, power-electronics energy conversion interfaces are rapidly being deployed calling for another look at system-level control hierarchies. This article examines how multi-time-scale modeling, feedback control, and feedback optimization can help reinterpret the traditional organically grown hierarchy of primary control, automatic generation control, and economic dispatch, and enable new approaches for control of contemporary power systems. Beginning with an overview of power system models and conventional operational practices, the article develops connections to modern control architectures that can coordinate heterogeneous resources, account for operational constraints, and exploit faster actuation without overlooking first-principles physics.

Power system operation and control has traditionally been organized across distinct spatial and temporal scales. From a spatial perspective, a large interconnected power system is partitioned into balancing areas (Figure 1(b)), which are electrically coupled through tie lines. Within each balancing area, a balancing authority, such as an independent system operator (ISO), regional transmission organization (RTO), or utility, is responsible for balancing generation and demand and maintaining operational constraints on key variables such as voltage and line power flows. Each balancing authority is also responsible for maintaining its net tie-line interchange near a scheduled value. Inter-area exchanges are established through interchange agreements, bilateral transactions, and, where wholesale markets exist, day-ahead and real-time market clearing.

Temporal scales of control and spatial organization into balancing areas

Figure 1. Spatial and temporal organization of bulk power system operation: (a) Frequency-control and operational mechanisms act over progressively broader spatial regions and slower time scales. The highlighted time scales are representative and depend on the resources, implementation, and operating conditions. (b) An interconnected transmission system is partitioned into balancing areas linked by tie lines.

From a temporal perspective, power imbalances are managed through a hierarchy of physical and control mechanisms (Figure 1(a)). Following a sudden increase in demand or a loss of generation, the stored kinetic energy in each synchronous generator provides an immediate inertial response, causing a deceleration in the generators’ rotation, and the network frequency begins to decline. Next, primary frequency control acts over the coming seconds to arrest the frequency excursion and stabilize the frequency at an off-nominal value. This is traditionally implemented through governors that regulate the flow of energy to the turbine driving the synchronous generator. Secondary frequency control, also known as automatic generation control (AGC), then adjusts the generator power set-points over tens of seconds to minutes to restore nominal frequency and the scheduled net interchanges. At still slower operational intervals, (re)dispatch processes based on economic dispatch (ED) and optimal power flow (OPF) update resource schedules, replenish regulation reserves, and coordinate economic objectives. This time-scale separation is the foundation of bulk power system operation: it allows stabilization, frequency regulation, and economic coordination to be addressed separately. From a control-theoretic standpoint, this layered structure can be formalized and analyzed using two-time-scale models and singular-perturbation methods [1, 2, 3]. Figure 2 shows an example of frequency evolution after a generation outage in the European transmission system (that occurred on December 8th, 2004); the figure exemplifies the actions of inertial response, primary control, and secondary control. The figure also highlights inter-area oscillations. For more information on this legacy layered architecture, the reader is referred to the textbooks [4, 5, 6, 7] and to the sidebar “History of Bulk Power System Control and Operations.”

Frequency evolution after a generation outage in the European transmission system

Figure 2. The figure is based on data and an original graphic by Walter Sattinger from Swissgrid AG. Presented publicly at ETH Zürich Seminar “Stromdrehscheibe Schweiz – Netzbetrieb im Zentrum Europas”, 2007 [8]. The time scales of the different responses after the outage are highlighted in shades of green. From left to right: inertial response, primary control (aptly also called frequency containment), and secondary frequency regulation to the setpoint. The inset highlights two distinct out-of-phase frequency measurements from Switzerland and Greece that showcase the (in this case excited) continental East-West inter-area oscillation mode. As a little known curiosity: the frequency setpoint is at 49.99 Hz (thus below the usual 50Hz) so that the myriads of clocks synchronized to the AC waveform can compensate for an accumulated drift.

The composition of present-day grids around the world is rapidly changing, (see Figure 3), issuing substantial new operational challenges. In particular, operators are witnessing an unprecedented increase in the integration of inverter-based resources (IBRs) interfacing energy storage systems, photovoltaics, wind, electrified transportation fleets, and data center loads. While internal models and controllers for synchronous generators are based on Newtonian mechanics and established schemes, inverters are programmable energy-conversion interfaces offering unprecedented flexibility in operation. Two categories of control schemes for IBRs have emerged to be commonplace: grid-following (GFL) and grid-forming (GFM) [14]. The distinction (which the article will dwell on in detail) relates to whether the internal controls autonomously synthesize a terminal voltage much like synchronous generators (i.e., GFM) or rely on a network-induced voltage for operation (i.e., GFL). Modeling, analysis, and control of continental-scale systems with a heterogeneous mix of resources that are characterized by significantly varied dynamic characteristics is a daunting task. As a concrete example, the fast response speeds of IBRs and oftentimes unknown operational behavior has meant that they are not integrated into higher (i.e., secondary and tertiary) layer controls. At the same time, growing classes of demand, including data centers, heat pumps, and electric mobility, are being connected across transmission and distribution networks. For example, data centers can constitute large, concentrated loads whose consumption may exhibit rapid and uncertain changes associated with computational activity; this may drive the network towards undesirable/infeasible operating configurations or dynamic instability. From both the generation and demand side, present-day changes increase the variability of net demand and redistribute (increasingly controllable) injections and consumption across the network.

Present and future grid architectures with synchronous generators, inverter-based resources, data centers, electrified heating, electric mobility, flexible loads, and energy storage

Figure 3. Modern grids increasingly integrate inverter-based resources, growing classes of demand, renewables, energy storage, electrified transportation, and data centers. The article highlights research questions related to integrating these resources within the control layers of Figure 1 and within plausible new control architectures.

Reliable operation under this evolving resource mix requires controls which take advantage of the capabilities of new resources while respecting their limits and operational requirements. For example, GFL and GFM inverters respond rapidly to disturbances and participate in primary/secondary frequency control and economic dispatch. Data centers and other flexible loads can likewise offer part of their consumption as a flexible resource, subject to workload and quality-of-service requirements [15, 16, 17, 18].

Integrating these resources into operational hierarchies must be accomplished systematically to ensure small-signal stability, large-disturbance stability, and satisfaction of operational constraints under uncertainty.

These observations lead to two broad and complementary research directions:

  • The first extends the existing layered operational paradigm by incorporating new resources and control methods within the primary, secondary, and tertiary hierarchies.

  • The second considers new control methods that re-assign selected functions across layers and may compress conventional time-scale separations in search of improved dynamic performance.

The article examines both directions. It is important to stress that these are not mutually exclusive; different resources, services, and regions may adopt them to different degrees. However, both directions raise challenging control engineering questions centered around model approximations, network stability and robustness, transient performance, constraint satisfaction, and distributed control implementations.

Article Perspective and Scope

This article offers a tutorial and perspective on multi-timescale modeling and control for frequency regulation in power systems with heterogeneous resources. It develops a common model-based framework for examining both incremental extensions of current practice and more substantial changes to control architectures. A central theme is that architectural and dynamic modeling choices cannot be separated from one another: a controller can safely exploit faster actuation only when the design model acknowledges the physical dynamics, network coupling, and constraints that are relevant to operation.

The organization of the article is summarized in Figure 5. The section “Modeling the Grid: From EMT to Control-Oriented Models” first describes a modeling hierarchy ranging from high-fidelity electromagnetic-transient (EMT) models down to a simplified linear ODE describing the network dynamics with primary control. The EMT model captures all network dynamics, including fast transients, while the simplified model retains only the aspects needed to describe the dynamics of primary frequency control. The section “Two-time-scale Models and Methods for Secondary Frequency Control” then introduces AGC, and uses singular-perturbation arguments to make explicit the assumptions under which AGC dynamics can be viewed independently of detailed primary-control dynamics.

Organization of the article from the traditional power-system modeling hierarchy, to research opportunities, to illustrative new control methods and architectures

Figure 5. Organization of the article from the traditional power-system modeling hierarchy, to research opportunities, to illustrative new control methods and architectures.

The sections “Research Opportunities Within the Existing Layered Architecture” and “Research Opportunities Beyond the Existing Layered Architecture” frame the two broad and complementary directions previously mentioned: extending the existing layered paradigm, and developing new architectures that reorganize selected control tasks. Their topics include AGC participation by IBRs and data centers, systematic design of primary frequency control, plant-level modeling and resource limits, transmission-distribution coordination, and compression of time scales. A discussion on potential reverse engineering approaches, where feedback laws can sometimes be fruitfully reinterpreted as solving an optimization problem is provided; this is followed by a discussion on how “feedback optimization” methods [19, 20, 21, 22, 23, 24, 25, 26] can provide

History of Bulk Power System Control and Operations

Stories surrounding the genesis of electrification as they relate to the battle between Nikola Tesla’s alternating- and Thomas Edison’s direct-current based designs are well known. The history of the development of architectural layers examined in this article, i.e., primary, secondary, and tertiary control, does not enjoy the same level of familiarity and renown. In fact, the developments here are equally engaging and they feature equally prominent scientists and engineers. They are also dotted with victories attributable to innovations crossing disciplinary technical boundaries and fraught with several missteps with grave consequences given the scale and importance of electric infrastructure. To develop an appreciation for the innovations and interventions we outline in this article, it is insightful to ponder on how the technologies, timescales, and architectures of the contemporary grid as illustrated in Figure 1 came to be. A necessarily abridged and incomplete history follows.

Primary control is tied to the action of governors that regulate frequency as (the inverse) function of active power within synchronous generators; a control action termed droop control. The enabling and underlying technology dates back to fly-ball governors invented by Christiaan Huygens in the 17th century and adopted for steam engines my James Watt in the 18th century. Droop control enables synchronization in interconnected energy-conversion systems. Early adopters and operators appear to have been curious about why it all worked [9]; rigorous analytical justifications for synchronization came much later and are tied to inferences gleaned from significant research in the celebrated Kuramoto model [10]. Grid-forming inverters adopt droop control at their core. Seminal research in this space appears only in the late 20th century with foundational work attributed to power-electronics experts, Mukul Chandorkar, Deepak Divan, and Rambabu Adapa [11]. Early AC systems engaged parallel connected generators to serve load, but they required significant manual intervention and operator expertise to maintain stable operation. Large-scale interconnected grids were enabled by the development of automatic generation control in the early-to-mid 20th century by Nathan Cohn and Robert Brandt [12]. This distributed secondary-control scheme is sandwiched between real-time (primary) control and slower time-scale (tertiary) optimization. It appears to have organically emerged out of the need to balance economic optimality with steady-state performance and the concomitant desire to expand interconnections. Developments in tertiary control are not covered in this account since this layer is not examined in depth in our effort. Algorithmic innovations in this layer are tied to companion developments in control theory, linear algebra, and optimization methods, see, e.g., [13].

Conceptual evolution from independent local systems to interconnected control areas

Figure S1. Conceptual evolution from independent local systems (top) to interconnected control areas (bottom).

principled forward engineering ways to design new architectures.

The next section examines four concrete examples that arise from the research opportunities. The first replaces the conventional AGC allocation rule with feedback optimization while maintaining the separation between secondary and tertiary operation. The second uses feedback optimization to coordinate secondary regulation and economic redispatch. The third uses disturbance feedback to bring selected secondary actions onto the time scale of the system dynamics with primary control. The fourth one described how aggregations of resources forming virtual power plants can be coordinated. Remarks with a grand research challenge conclude the article.

Power system modeling and control is a broad topic, and this article is, by no means, exhaustive and self contained. The technical development in this article focuses on transmission systems, active power, and frequency dynamics. Voltage and reactive power dynamics are, of course, considered in the higher-fidelity modeling hierarchy, but voltage-control architectures are not developed in the reduced models presented in the article. Detailed converter switching, protection, distribution-system operation, market design, and the procurement and compensation of flexibility are also outside the scope, although links to open research opportunities are provided. Distribution-connected resources are represented through aggregate injections or loads at transmission buses.

Reading notes. Two types of highlighted, self-contained notes support readers seeking different levels of technical detail. Modeling notes record assumptions, limitations, and technical details, whereas Derivations provide intermediate mathematical steps. Both can be skipped without breaking the main narrative. Sidebars provide longer, self-contained tutorials or technical developments and are referenced where they support the main text.

Notation. The sets of real and complex numbers are denoted by R\mathbb{R} and C\mathbb{C}, respectively; R+n:={v∈Rn:vi≥0, i=1,…,n}\mathbb{R}^{n}_{+} := \{v \in\mathbb{R}^{n} : v_i \ge0,\ i = 1,\ldots,n\}, and N:={0,1,…}\mathbb{N} := \{0,1,\ldots\}. The superscript ⊤\top denotes transpose. For column vectors x1,…,xmx_1,\ldots,x_m, col⁡(x1,…,xm):=[x1⊤ ⋯ xm⊤]⊤\operatorname{col}(x_1,\ldots,x_m) := [x_1^\top\ \cdots\ x_m^\top]^\top denotes vertical stacking. Indexed stacking follows the stated index ordering. The operators diag⁡\operatorname{diag} and blkdiag⁡\operatorname{blkdiag} construct diagonal and block-diagonal matrices, respectively, and ⊗\otimes denotes the Kronecker product. The symbols InI_n, 1n\mathbf{1}_n, and eie_i denote the nn-dimensional identity matrix, the vector of ones, and the iith standard basis vector; ∥⋅∥\|\cdot\| denotes the Euclidean norm. For real symmetric matrices, A≻BA \succ B and A⪰BA \succeq B mean that A−BA-B is positive definite and positive semidefinite, respectively. Vector inequalities are component-wise. For a complex scalar vv, v∗v^* denotes its conjugate, Re(v)\mathop{\mathrm{Re}}(v) and Im(v)\mathop{\mathrm{Im}}(v) denote its real and imaginary parts.

For a differentiable function ff, ∇f(x)\nabla f(x) denotes its column gradient. For a differentiable map g:Rn→Rmg:\mathbb{R}^n \to\mathbb{R}^m, ∂g/∂x\partial g/\partial x denotes its Jacobian, with (i,j)(i,j)th entry ∂gi/∂xj\partial g_i/\partial x_j. For a nonempty closed convex set S⊆RnS \subseteq\mathbb{R}^n, the Euclidean projection is proj⁡S(v):=arg⁡min⁡y∈S12∥y−v∥2\operatorname{proj}_S(v) := \mathop{\arg\min}_{y\in S} \frac{1}{2}\|y-v\|^2. For x∈Sx \in S, its normal cone is NS(x):={v∈Rn:v⊤(y−x)≤0 for all y∈S}N_S(x) := \{v \in\mathbb{R}^n : v^\top(y-x) \le0\text{ for all }y \in S\}. For a≤ba \le b, scalar saturation is defined by sat⁡[a,b](v):=min⁡{b,max⁡{a,v}}\operatorname{sat}_{[a,b]}(v) := \min\{b,\max\{a,v\}\}; saturation onto a box is applied componentwise.

Modeling the grid: from EMT to control-oriented models

Dynamical models used for analysis and control design must balance physical fidelity, analytical tractability, and operational relevance. At one extreme, EMT models capture fast switching dynamics, inverter controls, and detailed network effects, including line dynamics [27, 28, 29, 30]. However, they are typically too complex for network-level stability analysis, and unnecessarily detailed for primary- and secondary-control timescales [14]. At the other extreme, simplified grid models (e.g., the ubiquitous swing equations) are amenable to theoretical analysis, allowing one to construct Lyapunov functions, design controllers, and draw detailed conclusions about stability and performance as a function of device and network parameters. However, such models over-approximate or outright omit essential phenomena on time scales of interest.

The tension between model fidelity and tractability is especially relevant for the multi-time-scale analysis and control problems studied in this article. The analysis and design of primary and secondary frequency controllers rely on the availability of multi-time-scale grid models, with a partition of states into “fast” and “slow” – as in classical singular-perturbation approaches [2], [31], [32]– as well as approximations of electrical models [33], [34]. Electromagnetic transients, inverter inner controls, synchronization loops, electromechanical frequency dynamics, turbine-governor dynamics, primary control, AGC, economic dispatch, and online optimization all evolve on different, and sometimes overlapping, time scales in modern power grids [31, 35]. Therefore, a modeling hierarchy is required before any control design and/or analysis can be attempted. Which dynamic effects should be considered depends on the phenomenon under study and on how stability properties propagate through the modeling hierarchy. As concrete examples:

  • a study of inverter-current limiting or synchronization may need to keep averaged converter dynamics, while omitting switching dynamics, and treating primary control action as constant.

  • a study of AGC may need modeling of the primary frequency control dynamics, while omitting faster converter modes and network transients, and holding economic dispatch routines constant.

A useful workflow involves separating design models from validation models. Design models are necessarily lower order; they capture dominant electromechanical and power-flow dynamics, and can be used to develop intuition, facilitate stability analysis, and guide control design. Validation of stability criteria or control designs can then be performed with higher-fidelity EMT simulations that include detailed device, control, and network dynamics. During validation, one may find that certain omitted dynamics were more important than originally thought; these dynamics can then be accounted for in the lower-fidelity models, and the design and analysis steps can be repeated.

High-fidelity Models

A high-fidelity power transmission system model includes dynamics for synchronous generators and their associated control systems, device-level models for IBRs, loads, ancillary control equipment such as voltage compensators, and network dynamics describing how terminal voltages, currents, and power injections are coupled. Abstractly, such a model can often be written as a system of nonlinear differential-algebraic equations (DAEs) of the form

x˙dev=fdev(xdev,xnet,za,u,d),x˙net=fnet(xdev,xnet,za,u,d),0=g(xdev,xnet,za,u,d),y=h(xdev,xnet,za,u,d).(1)\begin{aligned} \dot{x}_{\mathrm{dev}} &= f_{\mathrm{dev}}(x_{\mathrm{dev}},x_{\mathrm{net}},z_a,u,d),\\ \dot{x}_{\mathrm{net}} &= f_{\mathrm{net}}(x_{\mathrm{dev}},x_{\mathrm{net}},z_a,u,d),\\ 0 &= g(x_{\mathrm{dev}},x_{\mathrm{net}},z_a,u,d),\\ y &= h(x_{\mathrm{dev}},x_{\mathrm{net}},z_a,u,d). \tag*{(1)} \end{aligned}

where the vector xdevx_{\mathrm{dev}} collects device and controller states, such as generator rotor angles and frequencies, turbine-governor states, excitation-system states, inverter internal-controller states (including, e.g., PLL states, voltage- and current-loop controller states), and dynamic load states. Depending on the modeling framework, network variables may appear either among the dynamic states xnetx_{\mathrm{net}} or the algebraic variables zaz_a. In the former case, xnetx_{\mathrm{net}} collects dynamic network states such as line currents, filter currents, and bus-capacitor voltages; see sidebar “Dynamic Network Models.” In the latter case, zaz_a collects terminal voltage phasors, algebraic current injections, algebraic power-flow variables, and network constraints in phasor-domain or quasi-steady models; see sidebar “The Power Flow Equations and DC Power Flow.” The vector uu in (1) denotes control inputs or setpoints, including commands issued by AGC, economic dispatch, or other controllers, dd denotes exogenous disturbances and operating condition changes, such as load variations and contingencies, and yy denotes available measurements.

The model (1) should be thought of as capturing the point of view of an (arguably idealized) omniscient grid operator, for whom the lower-level dynamics are fixed, with control inputs to be used for higher-level operational objectives; this is the view we take throughout this article. Additionally, the representation (1) is deliberately broad: its purpose here is not to prescribe any particular high-fidelity model, but to emphasize that bulk grid dynamics integrate together device-level dynamics and network models. In general, (1) is a large-scale nonlinear DAE, whose state dimension can easily reach tens of thousands for a realistic transmission network. Detailed network and device-level models for IBRs, forming the dynamics in (1a), are described in, e.g., [14, 33, 36, 37, 38, 39], while standard textbooks provide detailed models for conventional generators, inverters, and networks [4, 5, 6, 39, 40].

Control-oriented Models

Control-oriented models for primary control can be derived from (1) through successive elimination of dynamic and algebraic variables. A standard procedure consists of three steps: 1) network approximation, 2) device model reduction, and 3) network-device interconnection and (when desired) reduction. We develop these steps below, culminating in a reduced-order linear ODE model for primary frequency-control dynamics on a time scale of seconds.

Network approximation and DC power flow

The electromagnetic network dynamics (described in detail in the sidebar “Dynamic Network Models”) are much faster than the classical electromechanical and control dynamics of primary and secondary control in synchronous generator-dominated networks. The dynamic network equations can, therefore, be replaced by their equilibrium conditions leading to a purely algebraic network model. The most commonly used algebraic model is the power flow equations; see sidebar “The Power Flow Equations and DC Power Flow.” The DC power flow is a linearized, reduced, and decoupled version of the more general power flow equations enabling the examination of transmission-level frequency dynamics. It specifies the linear relationship

piinj=∑j∈Nibij(θi−θj),(2)p_i^{\mathrm{inj}}=\sum_{j\in\mathcal{N}_i}b_{ij}(\theta_i-\theta_j), \tag*{(2)}

between active power injections and voltage angles, where bij>0b_{ij}>0 is the (negative) susceptance of line (i,j)(i,j) and Ni\mathcal{N}_i Design models capture the dynamics essential for control synthesis, and validation models are used to assess the controllers in simulation.

denotes the set of neighbors of bus ii. In matrix form,

pinj=Bdcθ,(3)p^{\mathrm{inj}} = B_{\mathrm{dc}}\theta, \tag*{(3)}

where Bdc=BdcTB_{\mathrm{dc}} = B_{\mathrm{dc}}^{\mathsf{T}} is the susceptance matrix, also referred to as the susceptance-weighted network Laplacian or Kirchhoff matrix [41].

Reduced-order device models

Detailed device dynamics are now replaced by reduced-order models that capture the dominant electromechanical states relevant for primary frequency dynamics. This is described for (i) synchronous generators, (ii) grid-forming inverters, (iii) grid-following inverters, and (iv) controllable and non-controllable loads, modeled as active power demands. Hereafter, the deviation from the electrical radian synchronous frequency ω0\omega_0 at bus ii is denoted as

Ωi:=ωi−ω0.(4)\Omega_i := \omega_i - \omega_0. \tag*{(4)}

In a later section, the article will cover primary and secondary frequency control; within this control framework, ω0\omega_0 is the nominal frequency to which the network is expected to settle with secondary control (for example, see the dotted line in Figure 2 for that particular example of transmission system).

Synchronous generators. Each synchronous generator is represented by the classical swing equation coupled with a first-order turbine-governor model:

θ˙i=Ωi,(5)\dot{\theta}_i = \Omega_i, \tag*{(5)}
MisgΩ˙i=−DisgΩi+pisg−piinj(6)M_i^{\mathrm{sg}}\dot{\Omega}_i = -D_i^{\mathrm{sg}}\Omega_i + p_i^{\mathrm{sg}} - p_i^{\mathrm{inj}} \tag*{(6)}
τisgp˙isg=−pisg+pˉisg−KisgΩi,(7)\tau_i^{\mathrm{sg}}\dot{p}_i^{\mathrm{sg}} = -p_i^{\mathrm{sg}} + \bar{p}_i^{\mathrm{sg}} - K_i^{\mathrm{sg}}\Omega_i, \tag*{(7)}

where θi\theta_i is the voltage angle, Misg:=2Hisg/ω0>0M_i^{\mathrm{sg}} := 2H_i^{\mathrm{sg}}/\omega_0 > 0 is the inertia coefficient, HisgH_i^{\mathrm{sg}} is the inertia constant, Disg≥0D_i^{\mathrm{sg}} \ge0 is the damping coefficient, pisgp_i^{\mathrm{sg}} is the mechanical power, τisg>0\tau_i^{\mathrm{sg}} > 0 is the turbine-governor time constant, pˉisg\bar{p}_i^{\mathrm{sg}} is the mechanical-power setpoint (subsequently, we discuss how this is tied to secondary controllers such as AGC and feedback optimization), and Kisg≥0K_i^{\mathrm{sg}} \ge0 is the governor gain. The active-power injection piinjp_i^{\mathrm{inj}} is determined by the DC power-flow equation (15). This model captures inertial response through MisgM_i^{\mathrm{sg}}, damping through DisgD_i^{\mathrm{sg}}, and delayed primary-frequency response through the governor state pisgp_i^{\mathrm{sg}}. Some remarks are provided in sidebar “Model Approximation for Generators and Inverters”.

Grid-forming inverters. On the time scales of primary and secondary frequency control, each GFM inverter can be represented by the following swing-equivalent droop model, as summarized in the sidebar “Model Approximation for Generators and Inverters”:

References

  1. [1]P. V. Kokotovic, R. E. O’Malley Jr, and P. Sannuti, “Singular perturbations and order reduction in control theory—an overview,” Automatica, vol. 12, no. 2, pp. 123–132, 1976.
  2. [2]G. Peponides, P. V. Kokotovic, and J. H. Chow, “Singular perturbations and time scales in nonlinear models of power systems,” IEEE Transactions on Circuits and Systems, vol. 29, no. 11, pp. 758–767, 1982.
  3. [3]P. W. Sauer, “Time-scale features and their applications in electric power system dynamic modeling and analysis,” in American Control Conference. IEEE, 2011, pp. 4155–4159.
  4. [4]P. Kundur, Power System Stability and Control. New York, NY: McGraw-Hill, 1994.
  5. [5]J. Machowski, J. W. Bialek, J. Bialek, and J. R. Bumby, Power system dynamics and stability. John Wiley & Sons, 1997.
  6. [6]P. W. Sauer, M. A. Pai, and J. H. Chow, Power System Dynamics and Stability: With Synchronous Measurement and Power System Toolbox, 2nd ed. Wiley-IEEE Press, 2017.
  7. [7]A. J. Wood, B. F. Wollenberg, and G. B. Sheblé, Power Generation, Operation, and Control, 3rd ed. Wiley, 2013.
  8. [8]W. Sattinger, “Stromdrehschiebe Schweiz—Netzbetrieb im Zentrum Europas,” Seminar presentation, ETH Zürich, Switzerland, 2007, The original figure has been adapted to highlight the different frequency containment and restoration purposes. Author F. Dörfler has been granted a non-exclusive and non-transferable right of use for the graphic and adaptations. [Online]. Available: https://www.lsa.ethz.ch/news/stromdrehschiebe_ch_eth_lsa_09_05_07.pdf
  9. [9]J. Cohn, The Grid: Biography of an American Technology. Cambridge, MA: MIT Press, 2017.
  10. [10]F. Dörfler and F. Bullo, “Synchronization and transient stability in power networks and nonuniform Kuramoto oscillators,” SIAM Journal on Control and Optimization, vol. 50, no. 3, pp. 1616–1642, 2012.
  11. [11]M. Chandorkar, D. Divan, and R. Adapa, “Control of parallel connected inverters in standalone ac supply systems,” IEEE Transactions on Industry Applications, vol. 29, no. 1, pp. 136–143, 1993.DOI
  12. [12]N. Cohn, Control of Generation and Power Flow on Interconnected Power Systems. New York: J. Wiley, 1966.
  13. [13]J. Cohn, J. D. Molzahn, and S. Dhople, “Calculating the grid: A late 20th century story of innovation, transition, and reciprocity in electrification and computing,” IEEE Annals of the History of Computing, 2026.DOI
  14. [14]F. Dörfler and D. Groß, “Control of low-inertia power systems,” Annual Review of Control, Robotics, and Autonomous Systems, vol. 6, no. 1, pp. 415–445, 2023.
  15. [15]A. Wierman, Z. Liu, I. Liu, and H. Mohsenian-Rad, “Opportunities and challenges for data center demand response,” in International Green Computing Conference, 2014.DOI
  16. [16]P. Colangelo, A. K. Coskun, J. Megrue, C. Roberts, S. Sengupta, V. Sivaram, E. Tiao, A. Vijaykar, C. Williams, D. C. Wilson et al., “Ai data centres as grid-interactive assets,” Nature Energy, vol. 11, no. 2, pp. 254–261, 2026.
  17. [17]F. Acun, C. Hankendi, E. Levine, H. Reynolds, J. Bardwick, and A. K. Coskun, “Investigating power consumption flexibility of ai data centers for demand response participation,” 2026.DOI
  18. [18]Y. Zhang, A. Tsiligkaridis, I. C. Paschalidis, and A. K. Coskun, “Data center and load aggregator coordination towards electricity demand response,” Sustainable Computing: Informatics and Systems, vol. 42, p. 100957, 2024.DOI
  19. [19]A. Jokic, M. Lazar, and P.-P. J. Van Den Bosch, “On constrained steady-state regulation: Dynamic KKT controllers,” IEEE Transactions on Automatic Control, vol. 54, no. 9, pp. 2250–2254, 2009.
  20. [20]F. D. Brunner, H.-B. Dürr, and C. Ebenbauer, “Feedback design for multi-agent systems: A saddle point approach,” in IEEE Conference on Decision and Control, 2012, pp. 3783–3789.DOI
  21. [21]M. Colombino, F. Dall’Anese, and A. Bernstein, “Online optimization as a feedback controller: Stability and tracking,” IEEE Transactions on Control of Network Systems, vol. 7, no. 1, pp. 422–432, 2020.
  22. [22]A. Hauswirth, S. Bogdaní, G. Hug, and F. Dörfler, “Timescale separation in autonomous optimization,” IEEE Transactions on Automatic Control, vol. 66, no. 2, pp. 611–624, 2020.
  23. [23]L. S. P. Lawrence, J. W. Simpson-Porco, and E. Mallada, “Linear-convex optimal steady-state control,” IEEE Transactions on Automatic Control, vol. 66, no. 11, pp. 5377–5385, 2021.
  24. [24]Y. Tang, K. Dvijotham, and S. Low, “Real-time optimal power flow,” IEEE Transactions on Smart Grid, vol. 8, no. 6, pp. 2963–2973, 2017.
  25. [25]G. Bianchini, J. Cortés, J. I. Poveda, and E. Dall’Anese, “Time-varying optimization of lti systems via projected primal-dual gradient flows,” IEEE Transactions on Control of Network Systems, vol. 9, no. 1, pp. 474–486, 2021.
  26. [26]A. Hauswirth, Z. He, S. Bolognani, G. Hug, and F. Dörfler, “Optimization algorithms as robust feedback controllers,” Annual Reviews in Control, vol. 57, p. 100941, 2024.
  27. [27]J. D. Lara, R. Henriquez-Auba, D. Ramasubramanian, S. Dhople, D. S. Callaway, and S. Sanders, “Revisiting power systems time-domain simulation methods and models,” IEEE Transactions on Power Systems, vol. 39, no. 2, pp. 2421–2437, 2023.DOI
  28. [28]M. Xiong, B. Wang, D. Vaidhynathan, J. Maack, M. J. Reynolds, A. Hoke, K. Sun, D. Ramasubramanian, V. Verma, and J. Tan, “An open-source parallel EMT simulation framework,” Electric Power Systems Research, vol. 235, p. 110734, 2024.
  29. [29]W. Wang, S. Dong, W. Liu, V. R. Motakatla, P. Basnet, and X. Fang, “Co-simulation of PSS/E, OpenDSS, and PSCAD for power systems stability analysis with inverter-based resources,” in North American Power Symposium. IEEE, 2025.DOI
  30. [30]S. Filizadeh, J. Belanger, F. Fernandez, P. Forsyth, J. Mahseredjian, J. Morales, and G. Lietz, “Electromagnetic transient modeling and simulation of large power systems: Emt simulators for the future grid,” IEEE Power and Energy Magazine, vol. 23, no. 4, pp. 53–65, 2025.DOI
  31. [31]I. Subotić, D. Groß, M. Colombino, and F. Dörfler, “A Lyapunov framework for nested dynamical systems on multiple scales with application to converter-based power systems,” IEEE Transactions on Automatic Control, vol. 66, no. 12, pp. 5909–5924, 2020.
  32. [32]J. H. Chow, J. R. Winkelman, M. A. Pai, and P. W. Sauer, “Singular perturbation analysis of large-scale power systems,” International Journal of Electrical Power & Energy Systems, vol. 12, no. 2, pp. 117–126, 1990.DOI
  33. [33]O. Ajala, N. Baeckeland, B. Johnson, S. Dhople, and A. Domínguez-García, “Model reduction and dynamic aggregation of grid-forming inverter networks,” IEEE Transactions on Power Systems, vol. 38, no. 6, pp. 5475–5490, 2022.DOI
  34. [34]M. K. Singh, D. Venkatramanan, and S. Dhople, “Towards optimal primary- and secondary-control design for networks with generators and inverters,” in 58th Annual Allerton Conference on Communication, Control, and Computing. IEEE, 2022, pp. 1–6.arxiv.org/abs/2210.05841
  35. [35]J. A. Taylor, S. V. Dhople, and D. S. Callaway, “Power systems without fuel,” Renewable and Sustainable Energy Reviews, vol. 57, pp. 1322–1336, 2016.
  36. [36]M. D. Ilić, “From hierarchical to open access electric power systems,” Proceedings of the IEEE, vol. 95, no. 5, pp. 1060–1084, 2007.DOI
  37. [37]J. D. Lara, R. Henriquez-Auba, M. Bossart, D. S. Callaway, and C. Barrows, “Powersimulationsdynamics.jl—an open source modeling package for modern power systems with inverter-based resources,” arXiv preprint arXiv:2308.02921, 2023.arxiv.org/abs/2308.02921
  38. [38]N. Pogaku, M. Prodanovic, and T. C. Green, “Modeling, analysis and testing of autonomous operation of an inverter-based microgrid,” IEEE Transactions on Power Electronics, vol. 22, no. 2, pp. 613–625, 2007.DOI
  39. [39]A. Yazdani and R. Iravani, Voltage-sourced converters in power systems: modeling, control, and applications. John Wiley & Sons, 2010.
  40. [40]A. R. Bergen, Power systems analysis. Pearson Education India, 2009.
  41. [41]F. Dörfler, J. W. Simpson-Porco, and F. Bullo, “Electrical networks and algebraic graph theory: Models, properties, and applications,” Proceedings of the IEEE, vol. 106, no. 5, pp. 977–1005, 2018.DOI
  42. [42]D. K. Molzahn and I. A. Hiskens, A Survey of Relaxations and Approximations of the Power Flow Equations. Foundations & Trends, 2019.
  43. [43]J. W. Simpson-Porco, “A theory of solvability for lossless power flow equations – Part II: Conditions for radial networks,” IEEE Transactions on Control of Network Systems, vol. 5, no. 3, pp. 1373–1385, 2018.DOI
  44. [44]Task Force on Turbine-Governor Modeling, “Dynamic models for turbine-governors in power system studies,” IEEE Power & Energy Society, Technical Report PES-TR1, Jan. 2013. [Online]. Available: https://resourcecenter.ieee.org/publications/technical-reports
  45. [45]J. Schiffer, D. Zonetti, R. Ortega, A. M. Stanković, T. Sezi, and J. Raisch, “A survey on modeling of microgrids—from fundamental physics to phases and voltage sources,” Automatica, vol. 74, pp. 135–150, 2016.
  46. [46]F. Milano and A. Ortega, “Frequency divider,” IEEE Transactions on Power Systems, vol. 32, no. 2, pp. 1493–1501, 2016.
  47. [47]I. Ponce and F. Milano, “Complex frequency divider,” Electric Power Systems Research, vol. 234, p. 110662, 2024.DOI
  48. [48]D. Groß, “Compensating network dynamics in grid-forming control,” in 58th Annual Allerton Conference on Communication, Control, and Computing. IEEE, 2022.
  49. [49]V. Häberle, X. He, L. Huang, F. Dörfler, and S. Low, “Decentralized parametric stability certificates for grid-forming converter control,” IEEE Transactions on Control of Network Systems, 2026.
  50. [50]R. Pates and E. Mallada, “Robust scale-free synthesis for frequency control in power systems,” IEEE Transactions on Control of Network Systems, vol. 6, no. 3, pp. 1174–1184, 2019.
  51. [51]K. D. Smith, S. Jafarpour, and F. Bullo, “Transient stability of droop-controlled inverter networks with operating constraints,” IEEE Transactions on Automatic Control, vol. 67, no. 2, pp. 633–645, 2021.
  52. [52]A. Inaripast and D. Groß, “Networked dynamics with application to frequency stability of grid-forming power-limiting droop control,” IEEE Transactions on Control of Network Systems, 2025.
  53. [53]J. W. Simpson-Porco and N. Monshizadeh, “Diagonal stability of systems with rank-1 interconnections and application to automatic generation control in power systems,” IEEE Transactions on Control of Network Systems, vol. 3, no. 3, pp. 1518–1530, Sep. 2022.
  54. [54]D. Apostolopoulou, P. W. Sauer, and A. D. Domínguez-García, “Automatic generation control and its implementation in real time,” in 2014 47th Hawaii international conference on system sciences. IEEE, 2014, pp. 244–252.
  55. [55]H. Jung, S. Helman, M. K. Singh, and S. Dhople, “Inferences from numerical model reduction & aggregation of power-system dynamics featuring primary & secondary control,” in IEEE Power & Energy Society General Meeting. IEEE, 2024.DOI
  56. [56]F. C. Schweppe, M. C. Caramanis, R. D. Tabors, and R. E. Bohn, Spot pricing of electricity. Springer Science & Business Media, 2013.
  57. [57]S. Baros, Y. C. Chen, and S. V. Dhople, “Examining the economic optimality of automatic generation control,” IEEE Transactions on Power Systems, vol. 36, no. 5, pp. 4611–4620, 2021.DOI
  58. [58]H. K. Khalil, Nonlinear Systems, 2nd ed. Upper Saddle River, NJ: Prentice Hall, 2002.
  59. [59]D. Del Vecchio and J.-J. E. Slotine, “A contraction theory approach to singularly perturbed systems,” IEEE Transactions on Automatic Control, vol. 58, no. 3, pp. 752–757, 2012.
  60. [60]L. Cothren, F. Bullo, and E. Dall’Anese, “Online feedback optimization and singular perturbation via contraction theory,” SIAM Journal on Control and Optimization, vol. 64, no. 3, pp. 1482–1506, 2026.
  61. [61]Electric Power Research Institute, “Model user guide for generic renewable energy system models,” Electric Power Research Institute, Palo Alto, CA, USA, Tech. Rep. 3002027129, Oct. 2023.
  62. [62]S. G. Shamir, V. M. Venkatasubramanian, and G. Torresan, “Impact of communication delay and sampling on small-signal stability of IBR-rich power systems,” International Journal of Electrical Power & Energy Systems, vol. 174, p. 111502, 2026.
  63. [63]Y. Lin, J. H. Eto, B. B. Johnson, J. D. Flicker, R. H. Lasseter, H. N. Villegas Pico, G.-S. Seo, B. J. Pierre, and A. Ellis, “Research roadmap on grid-forming inverters,” National Renewable Energy Laboratory (NREL), Golden, CO (United States), Tech. Rep., 2020.DOI
  64. [64]PJM Interconnection, PJM Manual 12: Balancing Operations, PJM Interconnection, 2026, revision 57, effective April 22, 2026. [Online]. Available: https://www.pjm.com/-/media/Dotcom/documents/manuals/m12.pdf
  65. [65]B. Marinescu, O. Gomes-Bellmunt, F. Dörfler, H. Schulte, and L. Sigrist, “Dynamic virtual power plant: A new concept for grid integration of renewable energy sources,” IEEE Access, vol. 10, pp. 104980–104995, 2022.
  66. [66]V. Häberle, M. W. Fisher, E. Prieto-Araujo, and F. Dörfler, “Control design of dynamic virtual power plants: An adaptive divide-and-conquer approach,” IEEE Transactions on Power Systems, vol. 37, no. 5, pp. 4040–4053, 2021.
  67. [67]“Model user guide for generic renewable energy system models,” Electric Power Research Institute, Palo Alto, CA, USA, Technical Update 3002027129, Oct. 2023. [Online]. Available: https://restservice.epri.com/publicdownload/00000003002027129/0/Product
  68. [68]L. Fan, Z. Miao, D. Ramasubramanian, and H. Ding, “Operational challenges of solar PV plus storage power plants and modeling recommendations,” IEEE Open Access Journal of Power and Energy, vol. 10, pp. 477–489, 2023.DOI
  69. [69]L. Fan, Z. Miao, and D. Ramasubramanian, “IBR power plant frequency
  70. [70]control design consideration,” IEEE Transactions on Sustainable Energy, vol. 15, no. 4, pp. 2405–2416, 2024.
  71. [71]K. Gu, J. Chen, and V. L. Kharitonov, Stability of time-delay systems. Springer Science & Business Media, 2003.
  72. [72]H. Luo, I. A. Hiskens, and Z. Hu, “Stability analysis of load frequency control systems with sampling and transmission delay,” IEEE Transactions on Power Systems, vol. 35, no. 5, pp. 3603–3615, 2020.
  73. [73]M. Lin, A. Wierman, L. L. Andrew, and E. Thereska, “Online dynamic capacity provisioning in data centers,” in Annual Allerton Conference on Communication, Control, and Computing. IEEE, 2011, pp. 1159–1163.DOI
  74. [74]Y. Zhang, D. C. Wilson, I. C. Paschalidis, and A. K. Chawla, “HPC data center participation in demand response: An adaptive policy with QoS assurance,” IEEE Transactions on Sustainable Computing, vol. 7, no. 1, pp. 157–171, 2022.
  75. [75]S. S. Suggilam, C. Zhao, E. Dall’Anese, Y. C. Chen, and S. V. Dhople, “Optimizing DER participation in inertial and primary-frequency response,” IEEE Transactions on Power Systems, vol. 33, no. 5, pp. 5194–5205, 2018.
  76. [76]C. Zhao, U. Topcu, N. Li, and S. H. Low, “Design and stability of load-side primary frequency control in power systems,” IEEE Transactions on Automatic Control, vol. 59, no. 5, pp. 1177–1189, 2014.DOI
  77. [77]C. Zhao and S. H. Low, “Optimal decentralized primary frequency control in power networks,” in Proceedings of the 53rd IEEE Conference on Decision and Control, 2014, pp. 2467–2473.arxiv.org/abs/1403.6046
  78. [78]F. Paganini and E. Mallada, “Global analysis of synchronization performance for power systems: Bridging the theory-practice gap,” IEEE Transactions on Automatic Control, vol. 65, no. 7, pp. 3007–3022, 2020.arxiv.org/abs/1905.06948
  79. [79]Y. Jiang, R. Pates, and E. Mallada, “Dynamic droop control in low-inertia power systems,” IEEE Transactions on Automatic Control, vol. 66, no. 8, pp. 3518–3533, 2021.
  80. [80]A. D. Ames, S. Coogan, M. Egerstedt, G. Notomista, K. Sreenath, and P. Tabuada, “Control barrier functions: Theory and applications,” in Proceedings of the European Control Conference, 2019, pp. 3420–3431.
  81. [81]E. Dall’Anese, “Local safety filters for networked systems via two-time-scale design,” IEEE Control Systems Letters, 2026.
  82. [82]Y. Zhang and J. Cortés, “Distributed transient frequency control for power networks with stability and performance guarantees,” Automatica, vol. 105, pp. 274–285, 2019.
  83. [83]S. Golestan, J. M. Guerrero, and J. C. Vasquez, “Three-phase PLLs: A review of recent advances,” IEEE Transactions on Power Electronics, vol. 32, no. 3, pp. 1894–1907, 2017.DOI
  84. [84]K. Sawant, B. K. Dev, E. Dall’Anese, D. Ramasubramanian, and S. Dhople, “Integrated real-time economic dispatch and optimal automatic generation control,” in IEEE Power & Energy Society General Meeting, 2026.DOI
  85. [85]S. H. Low, F. Paganini, and J. C. Doyle, “Internet congestion control,” IEEE Control Systems Magazine, vol. 22, no. 1, pp. 28–43, 2002.
  86. [86]F. Facchinei and C. Kanzow, “Generalized Nash equilibrium problems,” 4or, vol. 5, no. 3, pp. 173–210, 2007.
  87. [87]N. Li, C. Zhao, and L. Chen, “Connecting automatic generation control and economic dispatch from an optimization view,” IEEE Transactions on Control of Network Systems, vol. 3, no. 3, pp. 254–264, 2015.
  88. [88]L. Chen and S. You, “Reverse and forward engineering of frequency control in power networks,” IEEE Transactions on Automatic Control, vol. 62, no. 9, pp. 4631–4638, 2017.
  89. [89]H. Le Cadre, I. Mezghani, and A. Papavasiliou, “A game-theoretic analysis of transmission-distribution system operator coordination,” European Journal of Operational Research, vol. 274, no. 1, pp. 317–339, 2019.DOI
  90. [90]D. Ding and M. R. Jovanović, “Global exponential stability of primal-dual gradient flow dynamics based on the proximal augmented lagrangian: A Lyapunov-based approach,” in IEEE Conference on Decision and Control. IEEE, 2020, pp. 4836–4841.
  91. [91]S. Boyd, N. Parikh, E. Chu, B. Peleato, and J. Eckstein, “Distributed optimization and statistical learning via the alternating direction method of multipliers,” Foundations and Trends® in Machine learning, vol. 3, no. 1, pp. 1–122, 2011.
  92. [92]A. Allibhoy and J. Cortés, “Control-barrier-function-based design of gradient flows for constrained nonlinear programming,” IEEE Transactions on Automatic Control, vol. 69, no. 6, pp. 3499–3514, 2023. E. Dall’Anese and A. Simonetto, “Optimal power flow pursuit,” IEEE Transactions on Smart Grid, vol. 9, no. 2, pp. 942–952, 2016.
  93. [93]L. Gan and S. H. Low, “An online gradient algorithm for optimal power flow on radial networks,” IEEE Journal on Selected Areas in Communications, vol. 34, no. 3, pp. 625–638, Mar. 2016. [Online]. Available: http://dx.doi.org/10.1109/JSAC.2016.2525598
  94. [94]A. Hauswirth, A. Zanardi, S. Bolognani, F. Dörfler, and G. Hug, “Online Optimization in Closed Loop on the Power Flow Manifold,” in 12th IEEE PES PowerTech, Jul. 2017. [Online]. Available: http://people.ee.ethz.ch/~bsaverio/papers/Powertech17.pdfDOI
  95. [95]L. Ortmann, A. Hauswirth, I. Caduff, F. Dörfler, and S. Bolognani, “Experimental validation of feedback optimization in power distribution grids,” Electric Power Systems Research, vol. 189, p. 106782, Dec. 2020. [Online]. Available: http://dx.doi.org/10.1016/j.epsr.2020.106782
  96. [96]L. Ortmann, C. Rubin, A. Scozzafava, J. Lehmann, S. Bolognani, and F. Dörfler, “Deployment of an online feedback optimization controller for reactive power flow optimization in a distribution grid,” in 2023 IEEE PES Innovative Smart Grid Technologies Europe (ISGT EUROPE). IEEE, Oct. 2023, pp. 1–6. [Online]. Available: http://dx.doi.org/10.1109/ISGTEUROPE56780.2023.10408057
  97. [97]L. Ortmann, J. Maeght, P. Panciatici, F. Dörfler, and S. Bolognani, “Subtransmission grid control via online feedback optimization,” Applied Energy, vol. 404, p. 127142, 2025. [Online]. Available: https://doi.org/10.1016/j.apenergy.2025.127142
  98. [98]Z. Jiang, S. Bolognani, and G. Belgioioso, “Voltage support procurement in transmission grids: Incentive design via online bilevel games,” in IEEE Conference on Decision and Control, 2025, pp. 7292–7298.arxiv.org/abs/2508.05378
  99. [99]Z. Jiang, F. Dörfler, and S. Bolognani, “Incentive-Based Load Curtailment with Limited Information: A Bilevel Zero-Order Learning Approach,” in PowerUp Conference, 2026.DOI
  100. [100]J. Llanos, D. E. Olivares, J. W. Simpson-Porco, M. Kazerani, and D. Saez, “A novel distributed control strategy for optimal dispatch of isolated microgrids considering congestion,” IEEE Transactions on Smart Grid, vol. 10, no. 6, pp. 6595–6606, Nov. 2019.DOI
  101. [101]J. Wang and N. Elia, “A control perspective for centralized and distributed convex optimization,” in IEEE Conference on Decision and Control. IEEE, 2011.DOI
  102. [102]A. Cherukuri, B. Gharesifard, and J. Cortés, “Saddle-point dynamics: conditions for asymptotic stability of saddle points,” SIAM Journal on Control and Optimization, vol. 55, no. 1, pp. 486–511, 2017.
  103. [103]Y. Xia and J. Wang, “On the stability of globally projected dynamical systems,” Journal of Optimization Theory and Applications, vol. 106, no. 1, pp. 129–150, 2000.
  104. [104]Z. Tang, E. Ekomwenrenren, J. W. Simpson-Porco, E. Farantatos, M. Patel, A. Haddadi, and H. Hooshyar, “Data-driven extension of “measurement-based fast coordinated voltage control for transmission grids”,” IEEE Transactions on Power Systems, vol. 38, no. 1, pp. 948–951, Jan. 2023.
  105. [105]M. Picallo, L. Ortmann, S. Bolognani, and F. Dörfler, “Adaptive real-time grid operation via online feedback optimization with sensitivity estimation,” Electric Power Systems Research, vol. 212, p. 108405, 2022.
  106. [106]S. Menta, A. Hauswirth, S. Bolognani, G. Hug, and F. Dörfler, “Stability of dynamic feedback optimization with applications to power systems,” in Annual Allerton Conference on Communication, Control, and Computing. IEEE, 2018, pp. 136–143.
  107. [107]J. W. Simpson-Porco, “Low-gain stabilizers for linear-convex optimal steady-state control,” in Proceedings of the IEEE Conference on Decision and Control, 2022, pp. 2552–2559.
  108. [108]F. Jakob and A. Ianelli, “A generalized plant perspective on linear-convex feedback optimization,” 2026.arxiv.org/abs/2606.14471
  109. [109]A. Colot, Y. Chen, B. Cornélusse, J. Cortés, and E. Dall’Anese, “Optimal power flow pursuit via feedback-based safe gradient flow,” IEEE Transactions on Control Systems Technology, vol. 33, no. 2, pp. 658–670, 2024.
  110. [110]G. Belgioioso, D. Liao-McPherson, M. H. de Badyn, S. Bolognani, J. Lygeros, and F. Dörfler, “Sampled-data online feedback equilibrium seeking: Stability and tracking,” in IEEE Conference on Decision and Control. IEEE, 2021, pp. 2702–2708.DOI
  111. [111]L. Cothren, G. Bianchin, S. Dean, and E. Dall’Anese, “Perception-based sampled-data optimization of dynamical systems,” IFAC-PapersOnLine, vol. 56, no. 2, pp. 5083–5088, 2023.
  112. [112]E. Ekomwenrenren, Z. Tang, J. W. Simpson-Porco, E. Farantatos, M. Patel, and H. Hooshyar, “Hierarchical coordinated fast frequency control using inverter-based resources,” IEEE Transactions on Power Systems, vol. 36, no. 6, pp. 4992–5005, Nov. 2021.
  113. [113]E. Ekomwenrenren, J. W. Simpson-Porco, E. Farantatos, M. Patel, A. Haddadi, and L. Zhu, “Data-driven fast frequency control using inverter-based resources,” IEEE Transactions on Power Systems, vol. 39, no. 4, pp. 5755–5768, Jul. 2024.
  114. [114]J. Schiffer, J. W. Simpson-Porco, and A. Parisio, “Control in low-inertia power and integrated energy systems,” in Encyclopedia of Systems and Control Engineering, first edition ed., Z. Ding, Ed. Elsevier, 2024.
  115. [115]N. Yousefi and J. W. Simpson-Porco, “Removing time-scale separation in feedback-based optimization via estimators,” in European Control Conference, 2026, to appear.

Paper details

vlnc:W_gr4faezu
Version
v1 · latest
Published
Fresh — added to the Hub within the last 30 days
Added
License
CC BY 4.0
Usage

views · 0

downloads · 0

A view counts once per browser per day, a download each time the PDF is requested.

  • Engineering

AI

View statement
Looking for related papers…
Contents