Abstract

The rapid integration of power electronics converters has fundamentally altered the power grid's dynamic landscape, making modularity of operation and interoperability of heterogeneous devices two critical hurdles for power system reliability. In control language, these challenges can be paraphrased as decentralized certificates on the input/output behavior of every device, assured by local control, so that stability and guaranteed performance of the interconnected system emerge. For the power system application, such certificates should eventually be part of the rule book, the so-called grid code, and thus be generic and minimally restrictive for the control architecture of each device. Classical system-theoretic angles of attack to these questions go back to dissipativity concepts, which have historically been co-developed in automatic control, circuit theory, and power systems. Since standard dissipativity (e.g., passivity or small gain) criteria fall short in terms of conservatism, a range of more flexible and advanced tools have been developed to assure less conservative decentralized certificates guaranteeing stability under interconnection as well as dynamic performance following a disturbance. In this article, we review a range of methods that have been put forward to tackle these questions, compare and validate them, and point towards practically relevant research gaps which are amenable to control-theoretic approaches. Moreover, we provide a tutorial exposition of practically relevant power systems/electronics issues accessible to control engineers.

Power electronics (PE) converters have emerged as a critical, albeit profoundly complex, component of modern power systems. Serving as the indispensable grid interface for renewable energy sources, energy storage systems, high-voltage direct current transmission systems, and electronic loads such as electric vehicles and data centers, their presence is expanding at an unprecedented rate [1, 2]. For instance, wind and solar combined generated 30% of all EU electricity in 2025, officially surpassing fossil fuels (29%) for the first time in history; in 2026, solar generation surpassed coal-fired power to become China’s largest installed power source. Driven by this rapid integration of renewables, traditional power grids are fundamentally evolving into PE-dominated power systems.

The dynamic behavior of PE converters markedly differs from that of conventional fossil-fuel-based power plants. They have low inertia and weak capability to support the grid voltage and frequency, rely on multiple nested control loops to realize synchronization and power transfer, subject to tight state constraints, operating-point dependent behavior, and are distributed and often non-dispatchable [3, 4]. Moreover, the design principles and physical constraints of PE converters are different across different application scenarios, resulting in heterogeneous dynamics and performance under grid disturbances. For instance, the PE converters in photovoltaics aim to regulate the dc-link voltage, while the PE converters in energy storage systems focus on regulating active power. The heterogeneity, on the other hand, also comes from the variety of control strategies of converters such as the traditional grid-following (GFL) control and the emerging grid-forming (GFM) control [5, 6, 7, 8, 9]. The large-scale integration of heterogeneous PE converters has profoundly altered power system dynamics and posed major challenges for stability analysis and reliable operation. Indeed, many real-world grid accidents involve (though are not caused by) high PE penetrations, such as the 2019 power outage in the UK, the 2016 South Australian blackout, and the 2025 Iberian Peninsula blackout. Moreover, oscillation and instability events have been frequently observed in many wind farms worldwide and even in data centers, which are caused by the complex interaction Modern grid codes already impose passivity requirements on converters over specified frequency ranges to ensure stable grid integration.

between converters and the power grid [10, 11, 12].

Following such instability events, system operators often invest considerable effort in reproducing the observed phenomena retrospectively by meticulously tuning, identifying, and recalibrating electromagnetic transient (EMT) simulation models. Yet, they remain largely incapable of predicting or preventing these events a priori. This critical vulnerability stems from the fact that conventional stability analysis techniques, such as eigenvalue computation or the generalized Nyquist criterion, lack the scalability required for high-dimensional, PE-dominated power systems. Because the stability of such a grid is dictated by the closed-loop interactions between the power network and a large number of heterogeneous converters (each introducing a multitude of state variables), centralized full models become analytically and computationally intractable, and they are not even available due to data silos amongst the system operators and the vendors. More importantly, these monolithic models obscure the network interconnection, failing to explain how individual converters interact with the power network and why specific interactions trigger instability. It is therefore preferable to have model-agnostic interface specifications for enforcing interconnection stability, without centralized models and analysis.

On the control design side, PE converters have much higher controllability and flexibility than conventional synchronous machines, which, via appropriate design, can support system stability and prevent oscillations [13, 14, 15, 16]. However, the sheer scale, complexity of dynamic grid-device interactions, and model opacity render holistic stability guarantees elusive. Furthermore, centralized analysis tools provide virtually no actionable guidance on how individual converters should be locally controlled to ensure the stability of the global interconnected system.

To simultaneously overcome these analytical bottlenecks, data silos, and design hurdles, the concept of decentralized stability certificates has gained significant traction [17, 18, 19, 20, 21, 22, 23, 24, 25]. This line of research traces back to the seminal works by Moylan and Hill in the 1970s analyzing the stability of multi-machine power systems using dissipativity [26, 27]. By specifying rigorous bounds on the local input–output behavior of each device, decentralized stability certificates mathematically guarantee the stability and dynamic performance of the interconnected system. Under this paradigm, global stability analysis is reduced to verifying that each individual device satisfies a local criterion, a profoundly scalable approach that is indifferent to the network’s sheer size and can cope with only locally available device models. Concurrently, it offers explicit design guidelines: local controllers should simply be designed to adhere to these local certificates.

Ultimately, such modular, ideally little conservative, and minimally restrictive certificates are envisioned to form the technical foundation of future grid codes in PE-dominated power systems, ensuring the modularity and interoperability of heterogeneous devices. In fact, these ideas (particularly passivity) have drawn great attention from the power industry and have been included in some grid codes. For instance, NERC requires that GFM converters should present a non-negative resistance and present a passive characteristic to the grid within a wide frequency range (0-300 Hz) to prevent adverse interactions [28]; UNIFI requires that GFM converters should be passive from approximately 4 Hz to 40 Hz and have low gain from 10 Hz to 40 Hz [29]; Fingrid requires that GFM converters shall present a positive resistance to the grid within frequency ranges 0–47 Hz and 53-250 Hz to prevent adverse interactions [30].

Classic dissipativity conditions, such as passivity and small gain, are examples of decentralized stability certificates, which are popular in analyzing converter dynamics [31, 32, 33]. However, these two conditions could be conservative and difficult for converters to directly satisfy in the whole frequency range [18, 34]. To this end, a range of more flexible and advanced tools have been developed to reduce the conservatism. The so-called small-phase theorem, as a counterpart to the small-gain theorem, was established in [35, 36], which extends the passivity condition and reduces its conservatism. The small-phase theorem builds upon the concept of matrix phases, which is defined using the numerical range and requires that the numerical range does not include the origin, i.e., the matrix is sectorial. The passivity condition is a special case of the small-phase theorem, where the matrix phases are constrained within ±90∘\pm90^\circ. Moreover, the small-phase theorem can be combined with gain information, leading to a mixed small gain-phase theorem, which provides more flexibility in analyzing system stability [37, 38]. Advancing this trajectory, recent literature [19, 39, 40] has demonstrated that the Davis-Wielandt (DW) shell, an elegant mathematical tool dating back to the 1950s [41, 42, 43], enables a unified and even more generalized set of decentralized certificates. Operating as a 3-dimensional (3D) geometric extension of the 2D numerical range, the DW shell explicitly captures both the phase and gain characteristics of a complex matrix and enables stability analysis from a geometric perspective. We will further demonstrate in this article how the DW shell is compatible with scaled relative graphs (SRGs) and integral quadratic constraints (IQCs) which have been leveraged for power system analysis [20, 44, 45].

In the remainder of this article, we elaborate how the DW shell enables decentralized stability certificates and bridge this advanced concept with established results like passivity, small gain, small phase, SRGs, and IQCs. The interpretability, computational tractability, and conservatism of different certificates will be compared and discussed. We give a tutorial presentation of complex PE-dominated power system models from the perspective of structured closed-loop interactions so that they are accessible to control theorists and engineers. Furthermore, we demonstrate how these decentralized certificates facilitate scalable stability and dynamic performance analysis and guarantee interoperability in PE-dominated power systems from both parametric and non-parametric (model-free) perspectives. We begin by revisiting the classical concept of dissipativity.

Dissipativity for Decentralized Stability Certificates

Dissipativity provides a general framework for characterizing how a dynamical system stores, dissipates, and exchanges energy with other systems. The particular relevance of dissipativity to PE-dominated power systems stems from its compositionality: a stability certificate can be established from local subsystem conditions without explicitly analyzing the full interconnected system. This makes dissipativity particularly attractive for large-scale systems consisting of heterogeneous power converters and networks. In “Dissipativity and Passivity in Circuits and Power Systems: A Historical Perspective”, we review the development and application of dissipativity and passivity theory in circuit theory and power system stability analysis.

Dissipativity and Passivity for Nonlinear Systems

Consider a nonlinear system

x˙=f(x,u),y=h(x,u),\dot{x}=f(x,u),\quad y=h(x,u),

where uu and yy denote the inputs and outputs, respectively. Let w(u,y)w(u,y) be a supply rate that characterizes the “instantaneous power” supplied to the system. The system is said to be dissipative with respect to ww if there exists a nonnegative storage function V(x)V(x) such that, along all system trajectories,

V˙(x)≤w(u,y).(1)\dot{V}(x)\leq w(u,y). \tag*{(1)}

Thus, the storage function V(x)V(x) measures the energy accumulated in the subsystem, while the supply rate accounts for the energy exchanged through its input-output ports.

Passivity is the special case of dissipativity, where

w(u,y)=uTy,(2)w(u,y)=u^{\mathsf{T}}y, \tag*{(2)}

leading to V˙(x)≤uTy\dot{V}(x)\leq u^{\mathsf{T}}y.

Dissipativity further allows the supply rate to encode margins of passivity. A commonly used form is

w(u,y)=uTy−νuTu−ρyTy,(3)w(u,y)=u^{\mathsf{T}}y-\nu u^{\mathsf{T}}u-\rho y^{\mathsf{T}}y, \tag*{(3)}

where ν\nu and ρ\rho are the input-feedforward passivity (IFP) and output-feedback passivity (OFP) indices, respectively [47]. Positive indices quantify a strict passivity margin, whereas negative indices characterize a shortage of passivity. This provides a useful quantitative description of how much non-passive behavior a subsystem can exhibit before interconnection stability is compromised.

More generally, a quadratic supply rate can be written as

w(u,y)=[yu]T[QSSTR][yu],(4)w(u,y)= \begin{bmatrix} y\\ u \end{bmatrix}^{\mathsf{T}} \begin{bmatrix} Q & S\\ S^{\mathsf{T}} & R \end{bmatrix} \begin{bmatrix} y\\ u \end{bmatrix}, \tag*{(4)}

where the matrices QQ, SS, and RR define the desired dissipativity property (also termed QSR-dissipativity), including dissipativity and passivity indices as special cases. The QSR-dissipativity can also be linked to the well-known small-gain property. Specifically, choosing Q=IQ=I, S=0S=0, R=γ2IR=\gamma^{2}I yields the supply rate w(u,y)=γ2uTu−yTyw(u,y)=\gamma^{2}u^{\mathsf{T}}u-y^{\mathsf{T}}y. If the system is dissipative with respect to this supply rate, its L2L_{2} gain is bounded above by γ\gamma; see “Connection Between Dissipativity and Small-Gain Property” for further details.

The dissipativity framework also relates to the integral quadratic constraint (IQC) framework, which is described in “How are IQCs Connected to Dissipativity and DW Shell Separation?”. In particular, the quadratic supply rate in (4) corresponds to an IQC when written as the integral of w(u,y)w(u,y). The main additional flexibility of IQCs is that the quadratic form can be frequency-dependent, i.e.,

∫−∞∞[y(jω)u(jω)]HΠ(jω)[y(jω)u(jω)] dω≥0,(5)\int_{-\infty}^{\infty} \begin{bmatrix} y(\mathrm{j}\omega)\\ u(\mathrm{j}\omega) \end{bmatrix}^{\mathsf{H}} \Pi(\mathrm{j}\omega) \begin{bmatrix} y(\mathrm{j}\omega)\\ u(\mathrm{j}\omega) \end{bmatrix} \,\mathrm{d}\omega\geq0, \tag*{(5)}

where Π(jω)\Pi(\mathrm{j}\omega) is an IQC multiplier, and H\mathsf{H} denotes the conjugate transpose of a complex matrix. Thus, IQCs naturally extend quadratic dissipativity when frequency-dependent input-output characteristics or structured uncertainties need to be captured.

Passivity for Linear Systems

For a linear time-invariant (LTI) system

x˙=Ax+Bu,y=Cx+Du,\dot{x}=Ax+Bu,\quad y=Cx+Du,

its passivity can first be formulated directly in the time domain through a quadratic storage function

V(x)=12xTPx,P=PT⪰0.V(x)=\frac{1}{2}x^{\mathsf{T}}Px,\quad P=P^{\mathsf{T}}\succeq0.

For the supply rate in (2), the passivity inequality (1) can be converted into a linear matrix inequality (LMI) in PP. Specifically,

\begin{bmatrix} A^{\mathsf{T}}P+PA & PB-C^{\mathsf{T}}\\ B^{\mathsf{T}}P-C & -(D+D^{\mathsf{T}}) \end{bmatrix}\preceq0. \tag*{(6)}\end{bmatrix}

Hence, passivity can be certified computationally through convex feasibility conditions.

For LTI systems, passivity also admits a frequency-domain description. In particular, the Kalman–Yakubovich–Popov (KYP) lemma [47 Lemma 6.2] establishes, under standard assumptions, the equivalence between (6) and the frequency-domain positive-realness condition of the transfer function G(s)G(s) from uu to yy, which requires

G(jω)+G(jω)H⪰0,∀ω∈R.(7)G(\mathrm{j}\omega)+G(\mathrm{j}\omega)^{\mathsf{H}}\succeq0,\quad\forall\omega\in\mathbb{R}. \tag*{(7)}

DISSIPATIVITY AND PASSIVITY IN CIRCUITS AND POWER SYSTEMS: A HISTORICAL PERSPECTIVE

Passivity theory originated from circuit theory and was developed into a general systems theory, laying the foundation for its subsequent application to power system stability and control. In the 19th century, circuit theory established the physical distinction between energy storage in inductors and capacitors versus energy dissipation in resistors. During the first half of the 20th century, passive network theory and positive-real functions provided a mathematical framework for characterizing passive electrical networks [S1]. In the 1970s, Willems formalized dissipative dynamical systems using storage functions and supply rates [S2], [S3], followed by Hill and Moylan’s work on their input-output and state-space properties, which clarified the relationship between dissipativity and stability in interconnected feedback systems [S4]. In parallel, passivity-based control (PBC) developed as a systematic control methodology, with early contributions by Ortega and Spong in the late 1980s [S5] and subsequent applications to electrical systems through energy shaping and damping injection.

At the circuit level, passivity has a direct physical interpretation in terms of port power and energy dissipation. With the passive sign convention, the instantaneous power entering a circuit is p(t)=vT(t)i(t)p(t) = \mathbf{v}^{\mathsf{T}}(t)\mathbf{i}(t), where v(t)\mathbf{v}(t) and i(t)\mathbf{i}(t) denote the port voltage and current, respectively. For an idealized circuit, the energy balance can be expressed as V˙(x)=p(t)−pdiss(t)≤p(t)\dot{V}(x) = p(t) - p_{\mathrm{diss}}(t) \le p(t), where V(x)V(x) is the stored energy and pdiss(t)≥0p_{\mathrm{diss}}(t) \ge0 is the dissipated power. More generally, passivity requires that the rate of change of stored energy does not exceed the supplied power, as expressed by the input-output condition in (2). For circuit impedance models in the frequency domain, passivity requires the real part of the impedance (or its Hermitian part in multi-input multi-output systems) to be positive semidefinite at all frequencies as in (7). This property is known as positive-realness in control theory and commonly referred to as positive resistance in power electronics.

The physical interpretation of passivity in circuits and its suitability for analyzing interconnected systems have motivated its application to power system stability. For example, Harnefors et al. investigated input-admittance shaping to improve the passivity of grid-connected converters [S7], while Pates and Mallada [23], Spanias and Lestas [S8], and Monshizadeh and Lestas [S9] developed decentralized stability criteria based on positive-realness and related input-output properties. To quantify the degree of passivity, Yang et al. adopted output-differential passivity indices [S10] to derive stability conditions for power systems with heterogeneous nonlinear bus dynamics, while He et al. established an output-feedback passivity (OFP) index for grid-connected converters and used the network’s input-feedforward passivity (IFP) property to derive decentralized stability conditions [46].

Furthermore, Häberla et al. established decentralized parametric stability certificates by leveraging dynamic loop-shifting techniques to compensate for the lack of passivity in the network dynamics [S11]. More general energy inequalities are captured by dissipativity theory: Moylan and Hill applied this framework to multimachine power-system stability [26], while QSR-dissipativity has been used in decentralized control of nonlinear DC microgrids under plug-and-play operations [S12]. In the frequency domain, integral quadratic constraints (IQCs) provide a flexible framework for stability assessment, enabling to unify existing stability criteria and reduce conservatism in the analysis of power-electronic-dominated power systems [44], [45], [S13], [S14]. This progress reflects the continued development of decentralized stability analysis toward less restrictive conditions that accommodate heterogeneous component dynamics and complex network interconnections.

Connection Between Dissipativity and Small-Gain Property

In the dissipativity framework, a finite L2L_2-gain property can be established via the quadratic supply rate. Let us define the supply rate as

w(u,y)=γ2uTu−yTy,(8)w(u,y)=\gamma^2u^\mathsf{T}u-y^\mathsf{T}y, \tag*{(8)}

with γ>0\gamma>0. Suppose the system is dissipative with respect to this supply rate. That is, there exists a nonnegative storage function V(x)V(x) (let V(x(0))=0V(x(0))=0) such that for all T≥0T\geq0,

V(x(T))≤∫0T(γ2uTu−yTy) dt.(9)V(x(T))\leq\int_0^T\left(\gamma^2u^\mathsf{T}u-y^\mathsf{T}y\right)\,\mathrm{d}t. \tag*{(9)}

Since V(x(T))≥0V(x(T))\geq0, rearranging the dissipativity inequality yields

∫0TyTy dt≤γ2∫0TuTu dt−V(x(T))≤γ2∫0TuTu dt.(10)\int_0^T y^\mathsf{T}y\,\mathrm{d}t\leq\gamma^2\int_0^T u^\mathsf{T}u\,\mathrm{d}t-V(x(T))\leq\gamma^2\int_0^T u^\mathsf{T}u\,\mathrm{d}t. \tag*{(10)}

Taking the limit as T→∞T\to\infty and applying the monotone convergence theorem to the left-hand side, we obtain

∥y∥2≤γ∥u∥2.(11)\lVert y\rVert_2\leq\gamma\lVert u\rVert_2. \tag*{(11)}

Therefore, dissipativity with respect to the quadratic supply rate w(u,y)=γ2uTu−yTyw(u,y)=\gamma^2u^\mathsf{T}u-y^\mathsf{T}y serves as a sufficient condition for the system to have a finite L2L_2 gain γ\gamma.

For two subsystems with gains γ1\gamma_1 and γ2\gamma_2,

V˙i≤γi2uiTui−yiTyi,i=1,2,(12)\dot{V}_i\leq\gamma_i^2u_i^\mathsf{T}u_i-y_i^\mathsf{T}y_i,\qquad i=1,2, \tag*{(12)}

we consider the feedback interconnection as in Figure 2: u1=−y2u_1=-y_2, u2=y1u_2=y_1. Introducing positive multipliers λ1,λ2>0\lambda_1,\lambda_2>0 and defining

Figure 2. A standard closed-loop feedback-interconnected system G(s)#H(s)G(s)\#H(s).

V=λ1V1+λ2V2,(13)V=\lambda_1V_1+\lambda_2V_2, \tag*{(13)}

gives

V˙≤(λ2γ22−λ1)y1Ty1+(λ1γ12−λ2)y2Ty2.(14)\dot{V}\leq(\lambda_2\gamma_2^2-\lambda_1)y_1^\mathsf{T}y_1+(\lambda_1\gamma_1^2-\lambda_2)y_2^\mathsf{T}y_2. \tag*{(14)}

Hence, the interconnected system is dissipative with a nonpositive supply rate if there exist λ1,λ2>0\lambda_1,\lambda_2>0 such that

λ2γ22<λ1,λ1γ12<λ2.(15)\lambda_2\gamma_2^2<\lambda_1,\qquad\lambda_1\gamma_1^2<\lambda_2. \tag*{(15)}

Such positive multipliers exist if and only if

γ1γ2<1,(16)\gamma_1\gamma_2<1, \tag*{(16)}

which is precisely the classical small-gain condition.

Under a common dissipativity framework, passivity and small gain differ primarily in their choice of supply rate: passivity uses the port-power supply uTyu^\mathsf{T}y, whereas small gain uses the quadratic supply γ2uTu−yTy\gamma^2u^\mathsf{T}u-y^\mathsf{T}y.

Another connection between passivity and the small-gain condition can be established through the scattering transformation, beyond the choice of different supply rates in dissipativity theory. Specifically, for a passive transfer function G(s)G(s), the positive-real condition, G(jω)+G(jω)H⪰0G(\mathrm{j}\omega)+G(\mathrm{j}\omega)^\mathsf{H}\succeq0, ∀ω∈R\forall\omega\in\mathbb{R}, is equivalent to the small-gain condition ∥(I−G(jω))(I+G(jω))−1∥≤1\lVert(I-G(\mathrm{j}\omega))(I+G(\mathrm{j}\omega))^{-1}\rVert\leq1, ∀ω∈R\forall\omega\in\mathbb{R}. Graphically speaking, the scattering transformation maps the positive-realness condition into a unit-disc constraint, thereby establishing a direct link between passivity-based and small-gain-based stability analysis.

Thus, passivity can also be interpreted as a positive-realness property in the frequency domain, also colloquially called positive resistance in power systems and electronics lingo.

This dual interpretation is particularly useful for PE converters. Time-domain passivity naturally connects with Lyapunov analysis and nonlinear models, whereas frequency-domain positive-realness provides an intuitive interpretation in terms of impedance or admittance characteristics. In this sense, passivity forms a bridge between energy-based nonlinear stability analysis and impedance-based frequency-domain analysis.

For a linear system G(s)G(s), the passivity indices can likewise be defined and computed in the frequency domain [48 p. 28], in addition to the time-domain definition in terms of the supply rate w(u,y)w(u,y) in (12). For a stable linear system G(s)G(s), its input-feedforward passivity (IFP) index is given by

References

  1. [1]F. Milano, F. Dörfler, C. Hug, D. J. Hill, and G. Verbič, “Foundations and challenges of low-inertia systems,” in 2018 power systems computation conference (PSCC). IEEE, 2018, pp. 1–25.
  2. [2]B. Kropski, B. Johnson, Y. Zhang, V. Georgian, P. Denholm, B.-M. Hodge, and B. Hannegan, “Achieving a 100% renewable grid: Operating electric power systems with extremely high levels of variable renewable energy,” IEEE Power and energy magazine, vol. 15, no. 2, pp. 61–73, 2017.
  3. [3]X. Wang and F. Blaabjerg, “Harmonic stability in power electronic-based power systems: Concept, modeling, and analysis,” IEEE Transactions on Smart Grid, vol. 10, no. 3, pp. 2858–2870, 2018.
  4. [4]O. Ellabban, H. Abu-Rub, and F. Blaabjerg, “Renewable energy resources: Current status, future prospects and their enabling technology,” Renewable and sustainable energy reviews, vol. 39, pp. 748–764, 2014.
  5. [5]J. Rocaert, A. Luna, F. Blaabjerg, and P. Rodriguez, “Control of power converters in ac microgrids,” IEEE transactions on power electronics, vol. 27, no. 11, pp. 4734–4749, 2012.
  6. [6]B. Wen, D. Boroyevich, R. Burgos, P. Mattavelli, and Z. Shen, “Impedance-based analysis of grid-synchronization stability for three-phase paralleled converters,” IEEE Transactions on power electronics, vol. 31, no. 1, pp. 26–38, 2015.
  7. [7]R. H. Lasseter, Z. Chen, and D. Pattabiraman, “Grid-forming inverters: A critical asset for the power grid,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 8, no. 2, pp. 925–935, 2019.
  8. [8]L. Huang, H. Xin, Z. Li, P. Ju, H. Yuan, Z. Lan, and Z. Wang, “Grid-synchronization stability analysis and loop shaping for PLL-based power converters with different reactive power control,” IEEE Transactions on Smart Grid, vol. 11, no. 1, pp. 501–516, 2020.
  9. [9]H. Xin, C. Liu, X. Chen, Y. Wang, E. Prieto-Araujo, and L. Huang, “How many grid-forming converters do we need? a perspective from small signal stability and power grid strength,” IEEE Transactions on Power Systems, vol. 40, no. 1, pp. 623–635, 2024.
  10. [10]H. Liu, X. Xie, J. He, T. Xu, Z. Yu, C. Wang, and C. Zhang, “Subsynchronous interaction between direct-drive PMSG based wind farms and weak AC networks,” IEEE Transactions on Power Systems, vol. 32, no. 6, pp. 4708–4720, 2017.
  11. [11]Y. Cheng, L. Fan, J. Rose, S.-H. Huang, J. Schmall, X. Wang, X. Xie, J. Shair, J. R. Ramamurthy, N. Modi, C. Li, C. Wang, S. Shah, B. Pal, Z. Miao, A. Isaacs, J. Manseridjian, and J. Zhou, “Real-world subsynchronous oscillation events in power grids with high penetrations of inverter-based resources,” IEEE Transactions on Power Systems, vol. 38, no. 1, pp. 316–330, 2023.
  12. [12]“Characteristics and risks of emerging large loads,” Large Loads Task Force, North American Electric Reliability Corporation (NERC), White Paper, 2025.
  13. [13]C. Yang, L. Huang, H. Xin, and P. Ju, “Placing grid-forming converters to enhance small signal stability of PLL-integrated power systems,” IEEE Trans. Power Systems, vol. 36, no. 4, pp. 3563–3573, 2020.
  14. [14]X. Wang, Y. W. Li, F. Blaabjerg, and P. C. Loh, “Virtual-impedance-based control for voltage-source and current-source converters,” IEEE Transactions on Power Electronics, vol. 30, no. 12, pp. 7019–7037, 2015.
  15. [15]B. K. Poolla, D. Groß, and F. Dörfler, “Placement and implementation of grid-forming and grid-following virtual inertia and fast frequency response,” IEEE Transactions on Power Systems, vol. 34, no. 4, pp. 3035–3046, 2019.
  16. [16]F. Ma, H. Xin, D. Wu, Y. Liu, and X. Chen, “Assessing small-signal grid strength of 100% inverter-based power systems,” IEEE Transactions on Power Delivery, vol. 39, no. 5, pp. 2784–2796, 2024.
  17. [17]L. Huang, H. Xin, and F. Dörfler, “H∞-control of grid-connected converters: Design, objectives and decentralized stability certificates,” IEEE Transactions on Smart Grid, vol. 11, no. 5, pp. 3805–3816, 2020.
  18. [18]L. Huang, D. Wang, X. Wang, H. Xin, P. Ju, K. H. Johansson, and F. Dörfler, “Gain and phase: Decentralized stability conditions for power electronics-dominated power systems,” IEEE Transactions on Power Systems, vol. 39, no. 6, pp. 7240–7256, 2024.
  19. [19]C. Feng and F. You, “Unified decentralized small-signal stability criterion for grid-connected converters,” IEEE Transactions on Power Systems, 2025.
  20. [20]E. Barón-Prada, A. Anta, and F. Dörfler, “On decentralized stability conditions using scaled relative graphs,” IEEE Control Systems Letters, vol. 9, pp. 691–696, 2025.
  21. [21]Z. Wang, S. Chatterjee, S. Geng, R. Pates, and E. Mallada, “Decentralized stability certificates in ibr-dominated grids: The role of the network state,” 2026. [Online]. Available: https://arxiv.org/abs/2607.01643
  22. [22]J. Niehues, R. Delabays, A. Büttner, and F. Hellmann, “Small-signal stability of power systems with voltage droop,” IEEE Transactions on Power Systems, vol. 41, no. 2, pp. 1429–1440, 2026.
  23. [23]R. Pates and E. Mallada, “Robust scale-free synthesis for frequency control in power systems,” IEEE Transactions on Control of Network Systems, vol. 6, no. 3, pp. 1174–1184, 2019.
  24. [24]A. Gorbunov, J. C.-H. Peng, J. W. Bialek, and P. Vorobev, “Identification of stability regions in inverter-based microgrids,” IEEE Transactions on Power Systems, vol. 37, no. 4, pp. 2613–2623, 2021.
  25. [25]P. Vorobev, S. Chevalier, and K. Turitsyn, “Decentralized stability rules for microgrids,” in 2019 American Control Conference (ACC). IEEE, 2019, pp. 2596–2601.DOI
  26. [26]P. Moylan and D. Hill, “Stability tests for multimachine power systems,” IFAC Proceedings Volumes, vol. 10, no. 1, pp. 70–74, 1977.
  27. [27]——, “Stability criteria for large-scale power systems,” IEEE Transactions on Automatic Control, vol. 23, no. 2, pp. 143–149, 1978.
  28. [28]A. Hoke, A. Isaacs, L. Unruh et al., “White paper: Grid forming functional specifications for bps-connected battery energy storage systems,” North American Electric Reliability Corporation (NERC), 2023.
  29. [29]B. Kropski, “Unifi specifications for grid-forming inverter-based resources: Version 3,” Technical Report, National Laboratory of the Rockies (NLR), Golden, CO (United States), Tech. Rep., 2026.
  30. [30]“Specific study requirements for grid energy storage systems,” Fingrid, Jun, 2023.
  31. [31]L. Harnefors, X. Wang, A. G. Yepes, and F. Blaabjerg, “Passivity-based stability assessment of grid-connected VSCs—an overview,” IEEE Journal of emerging and selected topics in Power Electronics, vol. 4, no. 1, pp. 116–125, 2015.
  32. [32]L. Harnefors, A. G. Yepes, A. Vidal, and J. Doval-Gandoy, “Passivity-based controller design of grid-connected vscs for prevention of electrical resonance instability,” IEEE Transactions on Industrial Electronics, vol. 62, no. 2, pp. 702–710, 2015.
  33. [33]F. Chen, S. Z. Khong, L. Harnefors, X. Wang, D. Wang, H. Sandberg, L. Zhao, M. Routimo, J. Kukkola, K. C. Sou, and K. H. Johansson, “An extended frequency-domain passivity theory for mimo dynamics specifications of voltage-source inverters,” IEEE Transactions on Power Electronics, vol. 40, no. 2, pp. 2943–2957, 2025.
  34. [34]F. Chen, X. Wang, L. Harnefors, S. Z. Khong, D. Wang, L. Zhao, K. C. Sou, M. Routimo, J. Kukkola, H. Sandberg et al., “Limitations of using passivity index to analyze grid-inverter interactions,” IEEE Transactions on Power Electronics, vol. 39, no. 11, pp. 14465–14477, 2024.
  35. [35]W. Chen, D. Wang, S. Z. Khong, and L. Qiu, “A phase theory of multi-input multi-output linear time-invariant systems,” SIAM Journal on Control and Optimization, vol. 62, no. 2, pp. 1235–1260, 2024.DOI
  36. [36]D. Wang, W. Chen, S. Z. Khong, and L. Qiu, “On the phases of a complex matrix,” Linear Algebra and its Applications, vol. 593, pp. 152–179, 2020.arxiv.org/abs/1904.07211
  37. [37]D. Zhao, W. Chen, and L. Qiu, “When small gain meets small phase,” arXiv preprint arXiv:2201.06041, 2022.arxiv.org/abs/2201.06041
  38. [38]L. Woolcock and R. Schmid, “Mixed gain/phase robustness criterion for structured perturbations with an application to power system stability,” IEEE Control Systems Letters, vol. 7, pp. 3193–3198, 2023.DOI
  39. [39]L. Huang, L. Luo, R. Leng, H. Xin, D. Wang, and F. Dörfler, “Geometric decentralized stability certificate for power systems based on projecting DW shells,” arXiv preprint arXiv:2508.17033, 2025.arxiv.org/abs/2508.17033
  40. [40]R. Leng, L. Huang, L. Luo, H. Xin, X. Wang, and F. Dörfler, “Geometric decentralized stability certificate of power electronics-dominated power systems covering variable operating points,” 2026. [Online]. Available: https://arxiv.org/abs/2607.10335
  41. [41]B. Davis, “The shell of a hilbert-space operator,” Acta Sci. Math. (Szeged), vol. 29, no. 1-2, pp. 69–86, 1968.
  42. [42]H. Wielandt et al., “On eigenvalues of sums of normal matrices,” Pacific J. Math., vol. 5, no. 4, pp. 633–638, 1955.DOI
  43. [43]I. Lestas, “Large scale heterogeneous networks, the davis–wielandt shell, and graph separation,” SIAM Journal on Control and Optimization, vol. 50, no. 4, pp. 1753–1774, 2012.DOI
  44. [44]L. Hallinan and I. Lestas, “Decentralised plug-and-play stability conditions for ac grids-part i,” arXiv preprint arXiv:2609.07315, 2026.arxiv.org/abs/2609.07315
  45. [45]X. Liu, L. Huang, H. Chen, and H. Xin, “Scalable small-signal stability assessment of power systems based on frequency-domain quadratic constraints,” arXiv preprint arXiv:2609.35424, 2026.arxiv.org/abs/2609.35424
  46. [46]X. He and F. Dörfler, “Passivity and decentralized stability conditions for grid-forming converters,” IEEE Transactions on Power Systems, vol. 39, no. 3, pp. 5447–5450, 2024.
  47. [47]H. K. Khalil, Nonlinear Systems, 3rd ed. Englewood Cliffs, NJ, USA: Prentice-Hall, 2002.
  48. [48]J. Bao and P. L. Lee, Process control: the passive systems approach. Springer, 2007.
  49. [49]D. J. Hill and T. Liu, “Dissipativity, stability, and connections: Progress in complexity,” IEEE Control Systems Magazine, vol. 42, no. 2, pp. 88–106, 2022.DOI
  50. [50]F. Zhao, X. Wang, and T. Zhu, “Low-frequency passivity-based analysis and damping of power-synchronization controlled grid-forming inverter,” IEEE Journal of Emerging and Selected Topics in Power Electronics, vol. 11, no. 2, pp. 1542–1554, 2022.DOI
  51. [51]D. Wang, X. Mao, W. Chen, and L. Qiu, “On the phases of a semi-sectorial matrix and the essential phase of a laplacian,” Linear Algebra and its Applications, vol. 676, pp. 441–458, 2023.DOI
  52. [52]D. Zhang, X. Yang, A. Ringh, and L. Qiu, “The phantom of Davis-Wielandt shell: A unified framework for graphical stability analysis of MIMO LTI systems,” arXiv preprint arXiv:2507.19918, 2025.arxiv.org/abs/2507.19918
  53. [53]V. Häberle, X. He, L. Huang, F. Dörfler, and S. Low, “Decentralized parametric stability certificates for grid-forming converter control,” IEEE Trans. Control of Network Systems, 2026.arxiv.org/abs/2503.05403
  54. [54]S. Skogestad and I. Postlethwaite, Multivariable feedback control: analysis and design. John Wiley & sons, 2005.
  55. [55]F. Dörfler and F. Bullo, “Kron reduction of graphs with applications to electrical networks,” IEEE Transactions on Circuits and Systems I: Regular Papers, vol. 60, no. 1, pp. 150–163, 2012.arxiv.org/abs/1102.2950
  56. [56]C.-K. Li and Y.-T. Poon, “Davis–wielandt shells of normal operators,” Acta Scientiarum Mathematicarum (Szeged), vol. 75, no. 1–2, pp. 289–297, 2009.DOI
  57. [57]E. Baron-Prada, J. P. J. Krebberk, A. Anta, and F. Dörfler, “Scaled graph containment for feedback stability: Soft-hard equivalence and conic regions,” arXiv preprint arXiv:2604.05567, 2026.
  58. [58]X. Wang, L. Harnefors, and F. Blaabjerg, “Unified impedance model of grid-connected voltage-source converters,” IEEE Trans. Power Electronics, vol. 33, no. 2, pp. 1775–1787, 2017.DOI
  59. [59]Y. Li, Y. Gu, and T. C. Green, “Revisiting grid-forming and grid-following inverters: A duality theory,” IEEE Trans. Power Systems, vol. 37, no. 6, pp. 4541–4554, 2022.arxiv.org/abs/2105.13094
  60. [60]L. Luo, L. Huang, H. Chen, R. Leng, Z. Hou, K. Zhuang, and H. Xin, “Impacts of heterogeneous grid-forming devices on power system dynamics quantified by shells,” arXiv preprint arXiv:2608.21984, 2026.
  61. [61]W. Dong, H. Xin, D. Wu, and L. Huang, “Small signal stability analysis of multi-infeed power electronic systems based on grid strength assessment,” IEEE transactions on Power Systems, vol. 34, no. 2, pp. 1393–1403, 2018.
  62. [62]H. Gao, L. Huang, H. Xin, Z. Li, and P. Ju, “Analysis of frequency and voltage strength in power electronics-dominated power systems based on characteristic subsystems,” IEEE Transactions on Power Systems, 2026.DOI
  63. [63]V. Häberle, L. Huang, X. He, E. Prieto-Araujo, R. S. Smith, and F. Dorfler, “Mimo grid impedance identification of three-phase power systems: Parametric vs. nonparametric approaches,” in 2023 62nd IEEE Conference on Decision and Control (CDC). IEEE, 2023, pp. 542–548.arxiv.org/abs/2305.00192
  64. [64]M. Abdalmotay, V. Häberle, X. He, and F. Dörfler, “Ultrafast grid impedance identification in dq-asymmetric three-phase power systems,” arXiv preprint arXiv:2510.12338, 2025.
  65. [65]P. Kundur, Power System Stability and Control. McGraw-Hill, 1994.
  66. [66]Z. Siahaan, E. Mallada, and S. Geng, “Decentralized stability criteria for grid-forming control in inverter-based power systems,” in 2024 IEEE Power & Energy Society General Meeting. IEEE, 2024, pp. 1–5.DOI
  67. [67]J. D. Watson and I. Lestas, “Control of interlinking converters in hybrid ac/dc grids: Network stability and scalability,” IEEE Transactions on Power Systems, vol. 36, no. 1, pp. 769–780, 2020.DOI
  68. [68]D. Grob, “Compensating network dynamics in grid-forming control,” in 2022 58th Annual Allerton Conference on Communication, Control, and Computing (Allerton), 2022, pp. 1–8.
  69. [69]K. Dey and A. Kulkarni, “Passivity of electrical power networks modelled using rectangular and polar variables,” in 2022 22nd National Power Systems Conference (NPSC). IEEE, 2022, pp. 407–412.DOI
  70. [70]—, “Passivity-based decentralized criteria for small-signal stability of power systems with converter-interfaced generation,” IEEE Transactions on Power Systems, vol. 38, no. 3, pp. 2820–2833, 2022.
  71. [71]M. Colombino, D. Grob, J.-S. Brouillon, and F. Dörfler, “Global phase and magnitude synchronization of coupled oscillators with application to the control of grid-forming power inverters,” IEEE Transactions on Automatic Control, vol. 64, no. 11, pp. 4496–4511, 2019.arxiv.org/abs/1710.00694
  72. [72]X. He, L. Huang, I. Subotić, V. Häberle, and F. Dörfler, “Quantitative stability conditions for grid-forming converters with complex droop control,” IEEE Transactions on Power Electronics, vol. 39, no. 9, pp. 10834–10852, 2024.

Paper details

vlnc:W_y5a83tzr
Version
v1 · latest
Published
Fresh — added to the Hub within the last 30 days
Added
License
CC BY 4.0
Usage

views · 1

downloads · 0

A view counts once per browser per day, a download each time the PDF is requested.

  • Engineering

Not recorded for this paper

View statement
Looking for related papers…
Contents