An Accurate Modulation-Assisted Method for Phasor Estimation Under Decaying DC Offsets

Abstract

Decaying DC (DDC) offsets severely compromise the accurate estimation of current phasors immediately following power grid fault occurrence. Consequently, conventional full-cycle discrete Fourier transform (FCDFT) algorithms experience decaying oscillatory magnitude errors, potentially causing distance relays to malfunction. This paper introduces a modulation-assisted technique designed to precisely eliminate the DDC components from fault current signals. By multiplying the fault signal with a high-frequency carrier and applying consecutive sliding Fourier projections, the proposed method effectively isolates the DDC signal while entirely rejecting higher-order harmonic interference. It utilizes a direct algebraic solution derived from a robust forward-difference operation across just three sequential projections to estimate and extract the DDC parameters. Furthermore, the algorithm seamlessly processes both single and multiple DDC components by dynamically tracking them as one equivalent first-order mode. Extensive evaluations are conducted to validate the proposed method accuracy. The proposed algorithm limits the maximum overshoot (MO) to 0.62% (0.59% for k≥8k \geq 8) for the evaluated DDC cases, and to 2.47% (0.95% at 20 dB for k=8k = 8) under noisy conditions.

Introduction

Index Terms— phasor estimation, decaying dc offset, discrete Fourier transform, modulation, relaying, fault current.

Fast and accurate estimation of the fundamental fault-current phasor is a basic requirement of modern power-system protection. Distance, directional, differential, and over-current relays use current phasors to identify the faulted element and issue a secure trip command within a few cycles. The discrete Fourier transform (DFT) is widely employed for this purpose because it has a simple implementation, a fixed computational burden, and exact rejection of integer harmonics under nominal-frequency steady-state conditions. However, its performance deteriorates during the first few cycles following a transmission line fault. Fault currents generally contain harmonics, measurement noise, and one or more exponentially decaying dc (DDC) components. Because a DDC is nonperiodic within the DFT window, it is not orthogonal to the fundamental-frequency basis functions and produces a decaying oscillatory error in the estimated magnitude and phase [1, 2, 3, 4, 5]. This transient error can delay relay convergence and cause relay overreach or underreach.

The DDC observed by a protection relay may have more than one physical origin. The primary component is produced by the transient response of the faulted power network; its initial magnitude depends mainly on the fault-inception angle, whereas its time constant is governed by the post-fault resistance-to-inductance ratio. A second component may be introduced by the transient response of the current transformer (CT). The primary and CT-induced components can have substantially different amplitudes and decay rates, particularly during high-current faults and CT saturation. The problem is also time critical: the DDC may persist beyond the decision interval of a high-speed relay, while waiting for its natural decay defeats the purpose of fast phasor estimation [3], [6], [7]. An effective estimator should therefore suppress both single- and multiple-DDC components without sacrificing harmonic rejection, noise tolerance, or convergence speed.

Existing DDC-mitigation methods can be broadly classified according to whether they preprocess the current waveform, correct the DFT output, or explicitly identify multiple exponential modes. In the first class, the DDC is suppressed before phasor calculation. The digital mimic filter is a representative solution and can substantially reduce the offset before the current is applied to the DFT [8]. Nevertheless, its response depends on the agreement between the selected and actual DDC time constants, which vary with the fault condition. In addition, it may also amplify noise and high-frequency transients. Adaptive mimic filtering reduces the time-constant-mismatch problem but introduces an additional parameter-adaptation stage [9]. Other preprocessing approaches use empirical-mode decomposition, intrinsic time-scale decomposition, recursive wavelets, or complex-frequency filters [10, 11, 12, 13]. Although these methods can attenuate DDC effect before phasor extraction, their decomposition, reconstruction, or auxiliary-filtering requirements are less direct than those of a conventional DFT relay.

The second class modifies the DFT calculation or estimates the leakage introduced by an assumed DDC model. Simplified Fourier-domain corrections use relations among consecutive samples or DFT outputs to compensate for the exponential term [1], [2]. Related modified-DFT formulations combine half- or full-cycle outputs, odd and even sample sets, or selected spectral components to suppress the offset-induced error [14]. Online parameter-estimation methods infer the decay factor and remove its contribution from the measured phasor [15], while analytical and fast-approval formulations seek to shorten the transient interval using compact sample combinations [4], [16], [17]. High-frequency modulation has also been used to move DDC information away from zero frequency and then recover the fundamental phasor through modified DFT operations [6], [18]. These methods can significantly improve the conventional DFT when the adopted signal model is satisfied. The method in [19] segments a one-cycle window into subsets and applies DFT to construct a complex equation system incorporating the fundamental frequency phasor alongside two decaying DC offsets. However, the computational complexity is high for the algorithm.

Window length is a central design variable in these formulations. Subcycle estimators respond early but weaken noise averaging and may forfeit full-cycle harmonic rejection [20]. Weighted least square and adaptive-window estimators provide flexibility at the cost of a larger signal model or parameter-selection mechanism [21, 22, 23, 24]. Conversely, full-cycle integration preserves useful Fourier properties but introduces observation delay. Taylor approximation simplifies the estimation equations, although its truncation error depends on the decay-time range and sampling interval. Frequency-deviation-aware formulations address another error source but require additional estimation stages [25]. These tradeoffs become more consequential when the primary and CT-induced offsets have widely separated decay rates [6], [7], [26].

The explicit treatment of two or more DDC modes has consequently received increasing attention. A modulation-based DFT method estimates the primary and secondary DDC components by combining successive outputs of one-cycle averaging filters and removes their contributions from the conventional DFT result [6]. A differential-equation formulation decomposes the fault current into modal components and permits the moving-window length to be selected according to the required compromise between accuracy and delay [27]. Selective interval integration estimates the system and CT offsets from two properly separated integration intervals without applying a Taylor approximation to the exponential terms [7]. Multiple exponentially decaying components have also been addressed directly in the DFT domain [28], [29]. Half-cycle and hybrid formulations estimate two exponential modes through auxiliary signals, successive integrations, or carrier modulation [30], [31]. These approaches establish that retaining separate decay modes can eliminate the residual oscillations that remain after an equivalent single-DDC approximation. At the same time, their implementations involve different combinations of auxiliary filtering, interval selection, successive-window processing, model assumptions, or numerical parameter extraction. Thus, there remains a need for a concise formulation that preserves the harmonic selectivity of a full-cycle DFT, without requiring prior knowledge of the number of DDC components or iterative nonlinear parameter estimation.

This paper develops a modulation-assisted estimator to meet protective relaying requirements. The measured current is multiplied by a high-frequency carrier signal, which shifts the non-oscillatory DDC component into damped components centered at the selected carrier frequency. A sliding full-cycle projection is then applied to reject standard integer harmonics. The high-frequency modulation removes the contribution of the oscillatory term, allowing the projection sequence to be approximated by a decaying exponential. By shifting these consecutive projections by a small fractional time step, the outputs form a predictable discrete sequence. Unlike conventional estimators that rely on iterative approximations, the proposed sequence is resolved purely algebraically. Applying a simple forward difference operation across consecutive observations entirely removes constant residual integration errors. The resulting difference equation directly yields the precise decay characteristics, allowing the algorithm to dynamically track the DDC component and deliver a fully compensated fundamental phasor estimate continuously. The contributions of this paper are as follows:

  1. A robust high-frequency modulation technique is introduced to decouple DDC offsets from fundamental fault phasors. By translating non-oscillatory components into a higher spectrum, a full-cycle sliding projection precisely isolating pure DDC terms without iterations.

  1. A flexible modulation multiplier selection framework optimizes noise immunity and minimizes estimation transients. This adaptive approach guarantees overall hardware compatibility, seamlessly accommodating both standard relay anti-aliasing filter bandwidth limits and diverse digital distance protection sampling rates.

  1. A direct algebraic forward-difference formulation dynamically extracts equivalent DDC parameters. This robust first-order model accurately approximates the composite transient behaviors, seamlessly scaling to resolve multiple interfering DDC components.

The remainder of this paper is organized as follows. Section II presents the proposed algorithm for eliminating the DDC component via high-frequency modulation, detailing both the time- and frequency-domain derivations. Section III evaluates the performance of the proposed method under various scenarios, including single and double DDC components, measurement noise, varying sampling rates, odd harmonics, and off-nominal frequencies, followed by simulation-based assessments on a test network. Finally, Section IV concludes the paper and summarizes the key capabilities of the method.

Proposed Algorithm

Modulation-Assisted DDC Parameter Extraction

The overall schematic diagram of the proposed method is summarized in the flowchart presented in Figure 1. The proposed method consists of signal modulation, consecutive sliding projections, a forward-difference operation, DDC reconstruction, and finally the fundamental phasor estimation.

Flowchart of the proposed modulation-assisted method for removing DDC of the fault current

Figure 1. Flowchart of the proposed modulation-assisted method for removing DDC of the fault current.

Signal Modulation and Sliding Projection Derivation

Consider a fault current signal containing a single DDC component alongside NN harmonics:

x(t)=I0e−t/τ+∑n=1NIncos⁡(nω0t+θn)(1)x(t) = I_0 e^{-t/\tau} + \sum_{n=1}^{N} I_n \cos(n\omega_0 t + \theta_n) \tag*{(1)}

where I0I_0 and τ\tau are the initial amplitude and time constant of the DDC, respectively, ω0=2π/T0\omega_0 = 2\pi/T_0 is the fundamental angular frequency, and InI_n and θn\theta_n represent the amplitude and phase angle of the nn-th harmonic component.

Modulating x(t)x(t) with a harmonic carrier sin⁡(kω0t)\sin(k\omega_0t), where kk is the integer harmonic carrier multiplier, yields:

ymod(t)=I0e−t/τsin⁡(kω0t)+∑n=1NIncos⁡(nω0t+θn)sin⁡(kω0t)(2)y_{\mathrm{mod}}(t) = I_0 e^{-t/\tau} \sin(k\omega_0t) + \sum_{n=1}^{N} I_n \cos(n\omega_0t+\theta_n)\sin(k\omega_0t) \tag*{(2)}

A sliding-window Fourier projection is applied specifically at the kk-th harmonic bin over a fundamental cycle T0T_0, starting at an arbitrary initial time t0=mΔtt_0 = m\Delta t for the mm-th observation window, where Δt\Delta t is the sliding time step. Assuming the fault current does not contain a significant harmonic of order n=2kn = 2k, the cross-product terms of integer harmonics integrate precisely to zero over T0T_0, simplifying the complex projection to:

Zk[m]=∫t0t0+T0I0e−t/τsin⁡(kω0t)e−jkω0t dt(3)Z_k[m]=\int_{t_0}^{t_0+T_0} I_0 e^{-t/\tau}\sin(k\omega_0t)e^{-jk\omega_0t}\,dt \tag*{(3)}

Applying Euler’s identity, the mixed trigonometric-exponential term expands into a stationary baseband term and a double-frequency oscillatory term:

sin⁡(kω0t)e−jkω0t=1−e−j2kω0t2j(4)\sin(k\omega_0t)e^{-jk\omega_0t}=\frac{1-e^{-j2k\omega_0t}}{2j} \tag*{(4)}

Substituting (4) into (3) splits the projection into two distinct integrals:

Zk[m]=I02j∫t0t0+T0e−t/τ dt−I02j∫t0t0+T0e−t(1/τ+j2kω0) dt(5)Z_k[m]=\frac{I_0}{2j}\int_{t_0}^{t_0+T_0}e^{-t/\tau}\,dt-\frac{I_0}{2j}\int_{t_0}^{t_0+T_0}e^{-t(1/\tau+j2k\omega_0)}\,dt \tag*{(5)}

Simplifying both integrals at the boundaries t0t_0 and t0+T0t_0+T_0 yields:

Zk[m]=I02j(1−e−T0/τ)e−t0/τ[τ−e−j2kω0t01/τ+j2kω0](6)Z_k[m]=\frac{I_0}{2j}\left(1-e^{-T_0/\tau}\right)e^{-t_0/\tau}\left[\tau-\frac{e^{-j2k\omega_0t_0}}{1/\tau+j2k\omega_0}\right] \tag*{(6)}

where the simplification e−j2kω0T0=1e^{-j2k\omega_0T_0}=1 has been applied.

The significance of the oscillatory phase term relative to the pure decay term τ\tau is given by the ratio η\eta:

η=∣e−j2kω0t01/τ+j2kω0∣τ=11+(2kω0τ)2(7)\eta=\frac{\left|\frac{e^{-j2k\omega_0t_0}}{1/\tau+j2k\omega_0}\right|}{\tau}=\frac{1}{\sqrt{1+(2k\omega_0\tau)^2}} \tag*{(7)}

For practical power system faults (0.5T0≤τ≤5T00.5T_0\leq\tau\leq5T_0 [8]), selecting a sufficiently high carrier multiplier (k≥4k\geq4) guarantees the condition kω0≫1/τk\omega_0\gg1/\tau, making the oscillatory term mathematically negligible (η<0.04\eta<0.04). However, the maximum value of kk is practically constrained by the digital relay’s hardware configuration. To prevent signal degradation, the translated carrier frequency (kf0kf_0, where f0=1/T0f_0=1/T_0 is the fundamental frequency) must remain strictly below the cut-off frequency (fcf_c) of the relay’s analog anti-aliasing filter (AAF) and strictly within the digital Nyquist limit [32]. Therefore, an optimal modulation index (e.g., 4≤k≤84\leq k\leq8 for standard commercial relays) is selected to simultaneously eliminate the oscillatory integration error while preserving the integrity of the isolated DDC component within the AAF’s flat passband.

Omitting this negligible component, the complex sliding projection is reduced to a purely decaying sequence without phase oscillations:

Zk[m]≈[I0τ2j(1−e−T0/τ)]e−t0/τ=Ke−mΔt/τ(8)Z_k[m]\approx\left[\frac{I_0\tau}{2j}\left(1-e^{-T_0/\tau}\right)\right]e^{-t_0/\tau}=\mathbf{K}e^{-m\Delta t/\tau} \tag*{(8)}

where K\mathbf{K} is a constant complex scalar, and the substitution t0=mΔtt_0=m\Delta t discretizes the temporal decay.

Single DDC

When exactly one physical decaying mode is present, the discrete sequence modeled in (8) follows a first-order linear homogeneous difference equation:

Zk[m+1]+a0Zk[m]=0(9)Z_k[m+1]+a_0Z_k[m]=0 \tag*{(9)}

where a0=−e−Δt/τ1a_0=-e^{-\Delta t/\tau_1} is the autoregressive coefficient.

While a0a_0 could theoretically be extracted directly from the raw projections, practical fault currents contain low-frequency A/D offsets and unsuppressed spectral leakage. To remove gradual background noise and ensure computational stability, the difference between consecutive points is evaluated as

Input Fault Current x(t)x(t) (1)

Modulate: ymod(t)=x(t)sin⁡(kω0t)y_{\mathrm{mod}}(t)=x(t)\sin(k\omega_0t) (2)

Sliding Projection: Zk[m]Z_k[m] over T0T_0 shifted by Δt\Delta t (8)

Forward Difference: ΔZk[m]=Zk[m+1]−Zk[m]\Delta Z_k[m]=Z_k[m+1]-Z_k[m] (10)

Extract Equivalent Root & Time Constant: zeq[m]z_{\mathrm{eq}}[m], τeq[m]\tau_{\mathrm{eq}}[m] (22), (24)

Reconstruct DDC & Compensate Waveform

FCDTF

Fundamental Phasor Extraction

ΔZk[m]=Zk[m+1]−Zk[m].\Delta Z_k[m]=Z_k[m+1]-Z_k[m].

The differenced sequence maintains the homogeneous property:

ΔZk[m+1]+a0ΔZk[m]=0(10)\Delta Z_k[m+1]+a_0\Delta Z_k[m]=0 \tag*{(10)}

Evaluating this at m=0m=0 provides the robust coefficient a0a_0:

a0=−ΔZk[1]ΔZk[0]=−Zk[2]−Zk[1]Zk[1]−Zk[0](11)a_0=-\frac{\Delta Z_k[1]}{\Delta Z_k[0]}=-\frac{Z_k[2]-Z_k[1]}{Z_k[1]-Z_k[0]} \tag*{(11)}

The discrete root is z1=−a0z_1=-a_0, and the time constant τ1\tau_1 is extracted as:

τ1=−Δtln⁡(z1)(12)\tau_1=\frac{-\Delta t}{\ln(z_1)} \tag*{(12)}

With τ1\tau_1 known, the initial amplitude I01I_{01} is recovered algebraically from the differenced projection components after compensating for the isolated exponential mode.

Two DDC

The fault current may exhibit two DDCs. In this case, the discrete sequence is modeled by a second-order linear homogeneous difference equation:

Zk[m+2]+a1Zk[m+1]+a0Zk[m]=0(13)Z_k[m+2]+a_1Z_k[m+1]+a_0Z_k[m]=0 \tag*{(13)}

Similar to the single DDC scenario, applying the difference operator ΔZk[m]=Zk[m+1]−Zk[m]\Delta Z_k[m]=Z_k[m+1]-Z_k[m] across consecutive equations filters out practical baseline offsets, transforming the system into a robust homogeneous form on the differences:

ΔZk[m+2]+a1ΔZk[m+1]+a0ΔZk[m]=0(14)\Delta Z_k[m+2]+a_1\Delta Z_k[m+1]+a_0\Delta Z_k[m]=0 \tag*{(14)}

To determine the unknown autoregressive coefficients (a0,a1)(a_0,a_1), five consecutive sliding windows (m∈{0,1,2,3,4}m\in\{0,1,2,3,4\}) are processed to form a fully determined 2×22\times2 linear system:

[ΔZk[0]ΔZk[1]ΔZk[1]ΔZk[2]][a0a1]=[−ΔZk[2]−ΔZk[3]](15)\begin{bmatrix} \Delta Z_k[0] & \Delta Z_k[1]\\ \Delta Z_k[1] & \Delta Z_k[2] \end{bmatrix} \begin{bmatrix} a_0\\ a_1 \end{bmatrix} = \begin{bmatrix} -\Delta Z_k[2]\\ -\Delta Z_k[3] \tag*{(15)} \end{bmatrix}

Solving this matrix yields a0a_0 and a1a_1. The discrete roots z1z_1 and z2z_2 are derived from the characteristic equation z2+a1z+a0=0z^2+a_1z+a_0=0. The true time constants are subsequently calculated as τi=−Δt/ln⁡(zi)\tau_i=-\Delta t/\ln(z_i). The complex scalars K1\mathbf{K}_1 and K2\mathbf{K}_2, along with their corresponding initial amplitudes I01I_{01} and I02I_{02}, are then isolated by fitting the discrete roots back to the differenced projection sequence ΔZk[m]=∑i=12Ki(zi−1)zim\Delta Z_k[m]=\sum_{i=1}^{2}\mathbf{K}_i(z_i-1)z_i^m extract the exponential parameters while preserving baseline-offset rejection.

Generalized Extraction (n-DDC)

The formulation readily scales to resolve an arbitrary integer number nn of independent decaying modes. The projection sequence observes an nn-th order linear recurrence relation:

∑p=0napZk[m+p]=0,where an=1(16)\sum_{p=0}^{n} a_p Z_k[m+p] = 0,\quad\text{where } a_n=1 \tag*{(16)}

Applying the difference operator Δ\Delta to essentially filter out low-frequency components yields a homogeneous relation on the differenced sequence:

∑p=0napΔZk[m+p]=0,where an=1(17)\sum_{p=0}^{n} a_p \Delta Z_k[m+p] = 0,\quad\text{where } a_n=1 \tag*{(17)}

Parameterizing nn distinct modes demands an observation vector of 2n+12n+1 consecutive sliding windows (indices m=0m=0 through 2n2n). The autoregressive coefficients a=[a0,…,an−1]T\mathbf{a}=[a_0,\ldots,a_{n-1}]^{T} are determined via the n×nn\times n Hankel matrix formulation:

[ΔZk[0]⋯ΔZk[n−1]⋮⋱⋮ΔZk[n−1]⋯ΔZk[2n−2]][a0⋮an−1]=−[ΔZk[n]⋮ΔZk[2n−1]](18)\begin{bmatrix} \Delta Z_k[0] & \cdots& \Delta Z_k[n-1]\\ \vdots& \ddots& \vdots\\ \Delta Z_k[n-1] & \cdots& \Delta Z_k[2n-2] \end{bmatrix} \begin{bmatrix} a_0\\ \vdots\\ a_{n-1} \end{bmatrix} = -\begin{bmatrix} \Delta Z_k[n]\\ \vdots\\ \Delta Z_k[2n-1] \tag*{(18)} \end{bmatrix}

The mode roots {z1,…,zn}\{z_1,\ldots,z_n\} are identified as the roots of the nn-th degree polynomial ∑p=0napzp=0\sum_{p=0}^{n}a_pz^p=0. Using these extracted roots, an n×nn\times n Vandermonde system [33] is constructed from the first nn differenced sequential projections ΔZk[m]=∑i=1nKi(zi−1)zim\Delta Z_k[m]=\sum_{i=1}^{n}K_i(z_i-1)z_i^m to jointly estimate the individual amplitude coefficients Ki\mathbf{K}_i.

Equivalent Single-Mode Modeling for Multiple DDC

While the previous subsections established the formulations for n=1n=1, n=2n=2, and a general nn, the number of DDC components need not be known a priori because their combined effect is represented by a dynamically updated equivalent DDC component. Rather than implementing complex multi-order extraction routines, the combined effect of multiple decaying modes can be piecewise approximated by a single, dynamically updating equivalent decaying offset as demonstrated in [2] and [14]. To illustrate this concept, the remainder of this subsection demonstrates the equivalent modeling specifically for two DDCs.

Consider a discrete sliding-window sequence obtained from a fault current containing two distinct DDC components. Under the proposed framework, the complex projection expands into a linear combination of two geometric progressions:

Zk[m]=K1z1m+K2z2m(19)Z_k[m]=K_1z_1^m+K_2z_2^m \tag*{(19)}

where z1=e−Δt/τ1z_1=e^{-\Delta t/\tau_1} and z2=e−Δt/τ2z_2=e^{-\Delta t/\tau_2} are the discrete roots, and the complex constants are defined by Ki=I0iτi2j(1−e−T0/τi)K_i=\frac{I_{0i}\tau_i}{2j}(1-e^{-T_0/\tau_i}).

By treating the equivalent parameters (Keq,zeq)(K_{\mathrm{eq}},z_{\mathrm{eq}}) as locally invariant over three consecutive sliding steps {m,m+1,m+2}\{m,m+1,m+2\}, an equivalent dynamically updating DDC component

Zk,eq[m]=KeqzeqmZ_{k,\mathrm{eq}}[m]=K_{\mathrm{eq}}z_{\mathrm{eq}}^m

approximates the combined effect of the two DDC components of Zk[m]Z_k[m], such that:

Keqzeqm=K1z1m+K2z2m(20)K_{\mathrm{eq}}z_{\mathrm{eq}}^m=K_1z_1^m+K_2z_2^m \tag*{(20)}

To evaluate the instantaneous equivalent discrete root zeqz_{\mathrm{eq}}, the homogeneous forward difference operator Δ\Delta is applied to (20) to eliminate low-frequency integration errors and isolate the decay rates:

Keqzeqm(zeq−1)=K1z1m(z1−1)+K2z2m(z2−1)(21)K_{\mathrm{eq}}z_{\mathrm{eq}}^m(z_{\mathrm{eq}}-1)=K_1z_1^m(z_1-1)+K_2z_2^m(z_2-1) \tag*{(21)}

By evaluating (21) at two consecutive sliding window steps mm and m+1m+1, and taking their ratio, the equivalent characteristic root zeq[m]z_{\mathrm{eq}}[m] is directly isolated:

zeq[m]=ΔZk[m+1]ΔZk[m]=K1z1m+1(z1−1)+K2z2m+1(z2−1)K1z1m(z1−1)+K2z2m(z2−1)(22)z_{\mathrm{eq}}[m]=\frac{\Delta Z_k[m+1]}{\Delta Z_k[m]}=\frac{K_1z_1^{m+1}(z_1-1)+K_2z_2^{m+1}(z_2-1)}{K_1z_1^m(z_1-1)+K_2z_2^m(z_2-1)} \tag*{(22)}

Given that the pure decay projection integral renders KiK_i purely imaginary, we define Ki=−jCiK_i=-jC_i, where Ci=12I0iτi(1−e−T0/τi)C_i=\frac{1}{2}I_{0i}\tau_i(1-e^{-T_0/\tau_i}) represents the real-valued magnitude coefficient for the ii-th mode. Substituting this into (22), the imaginary operators precisely cancel, yielding a purely real equivalent root:

zeq[m]=C1z1m+1(1−z1)+C2z2m+1(1−z2)C1z1m(1−z1)+C2z2m(1−z2)(23)z_{\mathrm{eq}}[m]=\frac{C_1z_1^{m+1}(1-z_1)+C_2z_2^{m+1}(1-z_2)}{C_1z_1^m(1-z_1)+C_2z_2^m(1-z_2)} \tag*{(23)}

The result of (23) confirms the existence of an equivalent characteristic root zeq[m]z_{\mathrm{eq}}[m] that provides a local piecewise approximation tracking the true composite trajectory of the two DDC components. The instantaneous equivalent time constant is subsequently calculated as:

τeq[m]=−Δtln⁡(zeq[m])(24)\tau_{\mathrm{eq}}[m]=\frac{-\Delta t}{\ln(z_{\mathrm{eq}}[m])} \tag*{(24)}

A similar algebraic expansion can be performed to demonstrate that this approximation holds for an arbitrary number of nn DDC components. Therefore, by employing the foundational single DDC homogeneous formulation (n=1n=1), the proposed method can dynamically mitigate the combined effect of multiple DDC components on fundamental phasor estimation without requiring the true order nn a priori.

Discrete-Time Implementation for Digital Relays

Let TsT_s be the sampling period, ν\nu the discrete sample index, and Ns=T0/TsN_s=T_0/T_s the number of samples per fundamental cycle. The sliding window shifts by ΔN=Ns/M\Delta N=N_s/M samples (Δt=ΔNTs\Delta t=\Delta NT_s), where MM is an integer sub-cycle shift factor, making the starting sample of the mm-th window νm=mΔN\nu_m=m\Delta N. Modulating the sampled fault current by the kk-th harmonic carrier yields the sliding projection over one cycle:

Zk[m]=∑ν=mΔNmΔN+Ns−1x[ν]sin⁡(2πkνNs)e−j2πkν/Ns(25)Z_k[m]=\sum_{\nu=m\Delta N}^{m\Delta N+N_s-1}x[\nu]\sin\left(\frac{2\pi k\nu}{N_s}\right)e^{-j2\pi k\nu/N_s} \tag*{(25)}

For a single DDC component, its sampled form is

xDDC[ν]=I0qν(26)x_{\mathrm{DDC}}[\nu]=I_0q^\nu \tag*{(26)}

where q=e−Ts/τq=e^{-T_s/\tau} is the single-sample decay factor. Applying the discrete form of Euler’s identity,

sin⁡(2πkνNs)e−j2πkν/Ns=1−e−j4πkν/Ns2j,(27)\sin\left(\frac{2\pi k\nu}{N_s}\right)e^{-j2\pi k\nu/N_s}=\frac{1-e^{-j4\pi k\nu/N_s}}{2j}, \tag*{(27)}

the DDC contribution to the projection becomes

Zk[m]=I02j∑v=mΔNmΔN+Ns−1qv−I02j∑v=mΔNmΔN+Ns−1qve−j4πkv/Ns(28)Z_k[m] = \frac{I_0}{2j}\sum_{v=m\Delta N}^{m\Delta N+N_s-1}q^v-\frac{I_0}{2j}\sum_{v=m\Delta N}^{m\Delta N+N_s-1}q^v e^{-j4\pi kv/N_s} \tag*{(28)}

The first term in (28) is a finite geometric series Sd[m]S_d[m]:

Sd[m]=qmΔN1−qNs1−q.(29)S_d[m]=q^{m\Delta N}\frac{1-q^{N_s}}{1-q}. \tag*{(29)}

The second term represents the discrete 2k2k oscillatory component. Being small for the selected modulation index, it is neglected. The sliding projection is thus approximated by the discrete geometric sequence:

Zk[m]≈Kdzm(30)Z_k[m]\approx K_d z^m \tag*{(30)}

where the projection coefficient KdK_d and discrete root zz are respectively defined as:

Kd=I02j1−qNs1−q,z=qΔN=e−ΔNTs/τ.(31)K_d=\frac{I_0}{2j}\frac{1-q^{N_s}}{1-q},\qquad z=q^{\Delta N}=e^{-\Delta N T_s/\tau}. \tag*{(31)}

Although evaluating (30) directly could yield zz, applying the forward difference ΔZk[m]=Zk[m+1]−Zk[m]\Delta Z_k[m]=Z_k[m+1]-Z_k[m] provides numerical stability and filters practical projection errors. Within each active observation buffer of length Ns+2ΔNN_s+2\Delta N (indexed locally by sub-windows m∈{0,1,2}m\in\{0,1,2\}), evaluating the differences for the first two consecutive steps gives:

ΔZk[0]=Kd(z−1),ΔZk[1]=Kdz(z−1).(32)\Delta Z_k[0]=K_d(z-1),\qquad\Delta Z_k[1]=K_dz(z-1). \tag*{(32)}

Taking their ratio eliminates KdK_d and yields the discrete decay root zz, from which the time constant τ^\hat{\tau} is recovered:

z=ΔZk[1]ΔZk[0],τ^=−ΔNTsln⁡(z).(33)z=\frac{\Delta Z_k[1]}{\Delta Z_k[0]},\qquad\hat{\tau}=-\frac{\Delta N T_s}{\ln(z)}. \tag*{(33)}

Once zz is determined, KdK_d and qq are obtained algebraically as

Kd=ΔZk[0]z−1,q=z1/ΔN.(34)K_d=\frac{\Delta Z_k[0]}{z-1},\qquad q=z^{1/\Delta N}. \tag*{(34)}

Substituting qq and KdK_d into (31) gives the estimated DDC amplitude I^0\hat{I}_0:

I^0=2jKd1−q1−qNs.(35)\hat{I}_0=2jK_d\frac{1-q}{1-q^{N_s}}. \tag*{(35)}

Ideally, the dominant decay projection is imaginary, making I^0\hat{I}_0 real. Small complex residuals from finite sampling are suppressed by retaining only the real-valued estimate.

The DDC is reconstructed sample by sample using the estimated initial amplitude I^0\hat{I}_0 and time constant τ^\hat{\tau}, and is subsequently subtracted from the raw fault current x[v]x[v] to produce the compensated current xc[v]x_c[v]:

x^DDC[v]=I^0e−vTs/τ^,xc[v]=x[v]−x^DDC[v].(36)\hat{x}_{\mathrm{DDC}}[v]=\hat{I}_0e^{-vT_s/\hat{\tau}},\qquad x_c[v]=x[v]-\hat{x}_{\mathrm{DDC}}[v]. \tag*{(36)}

A conventional FCDFT is then applied to xc[v]x_c[v] to estimate the fundamental phasor.

For multiple DDC components tracked continuously at an arbitrary sliding step mm, the equivalent-mode formulation retains this first-order structure. The dynamically varying equivalent root zeq[m]z_{\mathrm{eq}}[m], time constant τeq[m]\tau_{\mathrm{eq}}[m], and local window amplitude I^0,eq[m]\hat{I}_{0,\mathrm{eq}}[m] (referenced to the start of the mm-th window vm=mΔNv_m=m\Delta N) are updated as:

zeq[m]=ΔZk[m+1]ΔZk[m],τeq[m]=−ΔNTsln⁡(zeq[m]),z_{\mathrm{eq}}[m]=\frac{\Delta Z_k[m+1]}{\Delta Z_k[m]},\qquad\tau_{\mathrm{eq}}[m]=-\frac{\Delta N T_s}{\ln\left(z_{\mathrm{eq}}[m]\right)},
I^0,eq[m]=Re⁡{2jΔZk[m]zeq[m]−11−qeq[m]1−qeq[m]Ns}.(37)\hat{I}_{0,\mathrm{eq}}[m]=\operatorname{Re}\left\{2j\frac{\Delta Z_k[m]}{z_{\mathrm{eq}}[m]-1}\frac{1-q_{\mathrm{eq}}[m]}{1-q_{\mathrm{eq}}[m]^{N_s}}\right\}. \tag*{(37)}

where qeq[m]=(zeq[m])1/ΔNq_{\mathrm{eq}}[m]=(z_{\mathrm{eq}}[m])^{1/\Delta N} and x^DDC[v]=I^0,eq[m]e−(v−mΔN)Ts/τeq[m]\hat{x}_{\mathrm{DDC}}[v]=\hat{I}_{0,\mathrm{eq}}[m]e^{-(v-m\Delta N)T_s/\tau_{\mathrm{eq}}[m]} over the current window. Thus, the relay preserves the n=1n=1 computational structure while dynamically tracking multiple decaying offsets without prior knowledge of the number of DDC components.

Performance Evaluation

To validate the proposed modulation-assisted sliding-window method, a series of evaluations is conducted. The algorithm is benchmarked against the standard FCDFT and the two closest methods to the proposed approach, Method [6] and Method [18], as both utilize high-frequency modulation algorithms for DDC mitigation.

The evaluation relies on three established quantitative criteria to measure the transient and steady-state performance of the phasor estimation.

The maximum overshoot (MO) evaluates the worst-case transient spike above the true steady-state magnitude (XtrueX_{\mathrm{true}}):

MO=max⁡t≥tf(max⁡(Xest(t)−Xtrue,0)Xtrue)×100%.(38)MO=\max_{t\geq t_f}\left(\frac{\max(X_{\mathrm{est}}(t)-X_{\mathrm{true}},0)}{X_{\mathrm{true}}}\right)\times100\%. \tag*{(38)}

The rise time (trt_r) measures the tracking speed during the initial fault transition. It represents the time required for the estimated magnitude to transition from 10% to 90% of the fault step change:

tr=t90%−t10%.(39)t_r=t_{90\%}-t_{10\%}. \tag*{(39)}

Finally, the settling time (tst_s) identifies when the transient effectively ends. It is defined as the elapsed time following fault inception tft_f required for the estimation to permanently enter and remain within a ±5%\pm5\% tolerance band around the theoretical magnitude:

ts=min⁡{t>tf∣∣Xest(u)−Xtrue∣≤0.05Xtrue, ∀u≥t}−tf(40)t_s=\min\{t>t_f\mid|X_{\mathrm{est}}(u)-X_{\mathrm{true}}|\leq0.05X_{\mathrm{true}},\ \forall u\geq t\}-t_f \tag*{(40)}

The modulation orders k=4k=4, 88, and 1616 are considered to investigate modulation-order sensitivity. The k=16k=16 case is included for comparative purposes, although its practical applicability depends on the relay sampling rate and AAF bandwidth.

Evaluation with Single DDC

The DDC component depends on the fault inception angle and the network’s equivalent X/RX/R ratio. This ratio directly dictates the time constant τ\tau [34]. To evaluate the robustness of the proposed methodology across a wide spectrum of fault conditions, fault currents containing single DDC are generated. The magnitude ratio (I0/I1)(I_0/I_1) is varied across {0.1,0.5,1}\{0.1,0.5,1\}, and the time constant is varied across τ∈{0.5,3,5}\tau\in\{0.5,3,5\} cycles. The proposed method is evaluated at three different modulation orders (k∈{4,8,16})(k\in\{4,8,16\}), which yield nearly identical results for the investigated single-DDC cases.

As observed in Table I and Figure 2, the FCDFT is highly affected by the DDC component. In case of severe faults (I0/I1=1)(I_0/I_1=1), the FCDFT generates an overshoot up to 25.32% and a settling time up to 27.86 ms. Method [18] exhibits larger overshoots, reaching 35.68%. While Method [6] reduces the settling time in some cases, it still permits up to a 25.32% overshoot.

Transient magnitude estimation of fault current for a single DDC

Figure 2. Transient magnitude estimation of fault current for a single DDC.

Test ConditionFCDFTMethod [6]Method [18]Proposed Method
I0/I1I_0/I_1τ\tau (cyc)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)
0.10.52.5010.9413.800.609.6412.761.249.3812.240.0411.2014.32
0.130.9011.2014.060.709.9013.020.909.3812.760.0011.2014.32
0.150.5811.2014.060.589.9013.280.589.3814.320.0011.2014.32
0.50.512.5810.4220.0512.318.8516.6712.587.0316.410.2011.2014.32
0.534.919.9012.244.848.8510.948.317.0313.020.0111.2014.32
0.553.529.9012.243.468.8510.947.817.0312.500.0011.2014.32
10.525.324.6927.8625.324.6916.6735.684.6915.360.4011.2014.06
1318.713.6527.3418.713.6516.6734.353.6515.360.0211.2014.32
1520.623.6517.9720.623.6516.6733.853.6515.360.0111.2014.32

Table 1. Comparative Analysis of Algorithms for Test Signals with a Single DDC Component k∈{4,8,16}k \in\{4, 8, 16\}.

kkη\eta (%)EI0E_{I_0} (%)Emax⁡E_{\max} (%)ERMSEE_{\mathrm{RMSE}} (%)EMAEE_{\mathrm{MAE}} (%)
43.97571.70220.42510.17320.1299
81.98901.58640.39620.16140.1210
160.99471.56240.39020.15900.1192

Table 2. Modulation-Order Sensitivity for I0/I1=1I_0/I_1 = 1, τ=0.5\tau= 0.5 Cycle

The proposed method provides the smallest MO among the evaluated methods and maintains a settling time of 14.06–14.32 ms for all investigated single-DDC cases. Regardless of the DDC parameters, the proposed method separates the isolated mode, limiting the MO to at most 0.40% (and 0.00%–0.02% for τ≥3\tau\ge3 cycles). Its settling time remains tightly bounded within 14.32 ms, indicating that the extraction accuracy is largely insensitive to the DDC time constant.

Although the transient metrics in Table I are nearly identical across valid modulation orders, Table II shows the effect of kk using higher-resolution error metrics. Increasing kk reduces the retained 2k2k oscillatory residual and the resulting estimation errors, without changing the sample-quantized rise and settling times.

Evaluation with two DDC

In transmission networks, secondary currents measured by CTs often contain multiple DDC components. These originate from both the primary line properties and the internal magnetic core of the CT during saturation [35]. A series of test signals including severe DDC conditions are evaluated. Table III details the performance across varied system time constants (τ1\tau_1), secondary CT time constants (τ2\tau_2), and DDC amplitude ratios (I01/I02I_{01}/I_{02}).

Test ConditionFCDFTMethod [6]Method [18]Proposed Method
I01/I1I_{01}/I_1I01/I02I_{01}/I_{02}τ1\tau_1 (cyc)τ2\tau_2 (cyc)kkMO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)
12.5110435.203.1335.9435.203.1316.6757.583.1315.360.3810.9413.28
835.203.1335.9435.203.1316.6757.583.1315.360.3710.9413.28
1635.203.1335.9435.203.1316.6757.583.1315.360.3710.9413.28
0.52.5110410.854.9519.7910.844.9516.6719.014.9515.360.0911.4613.80
810.854.9519.7910.844.9516.6719.014.9515.360.0911.4613.80
1610.854.9519.7910.844.9516.6719.014.9515.360.0911.4613.80
150.55426.623.6527.8626.613.6516.6745.583.6515.360.6211.2013.80
826.623.6527.8626.613.6516.6745.583.6515.360.3311.2013.80
1626.623.6527.8626.613.6516.6745.583.6515.360.3211.2013.80
12220447.912.8635.9447.912.8616.6763.142.8615.360.5910.6813.02
847.912.8635.9447.912.8616.6763.142.8615.360.5910.6813.02
1647.912.8635.9447.912.8616.6763.142.8615.360.5910.6813.02

Table III. Comparative evaluations of algorithms for performance under double DC offsets.

Under double-DDC conditions, the FCDFT reaches large overshoots with protracted settling delays, while Method [18] reaches a 63.14% error peak under slow-decay conditions. However, the proposed method adapts to the multi-modal trajectory. As seen in Figure 3, it substantially reduces the compound transients, restricting the overshoot to negligible margins (≤0.62%\le0.62\%, and ≤0.59%\le0.59\% for k≥8k \ge8) and settling within one fundamental cycle (13.02–13.80 ms).

Current magnitude estimation under two DDC

Figure 3. Current magnitude estimation under two DDC.

Immunity to Measurement Noise

Measurement signals acquired from CT secondaries inherently contain noise, typically exhibiting a signal-to-noise ratio (SNR) between 20 to 40 dB. To evaluate the proposed method under noise condition, Gaussian noise along with a severe fault signal (I0/I1=1I_0/I_1 = 1, τ=5\tau= 5 cycles), scaling the SNR down to 20 dB, is considered.

As detailed in Table IV, the proposed method provides selective filtering due to the full-cycle trigonometric carrier integral. At 20 dB noise, Method [18] reaches a 42.35% overshoot and an 83.85 ms settling time, while the FCDFT and Method [6] exhibit a 20.64% overshoot. Conversely, the proposed method bounds the maximum error tightly. At 20 dB noise, it restricts overshoot to 0.95% (at k=8k = 8) and at most 1.54% (and ≤2.47%\le2.47\% across all evaluated noise levels) while settling within one fundamental cycle (14.32–15.10 ms). These results demonstrate that the proposed method maintains accurate phasor estimation under severe noise conditions better than other studied methods.

ConditionFCDFTMethod [6]Method [18]Proposed Method
SNRSNR (dB)kkMO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)
20420.643.6515.6220.643.6517.9742.353.6583.850.9611.7215.10
820.643.6515.6220.643.6517.9742.353.6583.850.9511.7214.84
1620.643.6515.6220.643.6517.9742.353.6583.851.5411.7214.58
30420.633.6516.4120.633.6516.4120.633.6519.530.6711.4614.58
820.633.6516.4120.633.6516.4120.633.6519.530.3511.2014.32
1620.633.6516.4120.633.6516.4120.633.6519.532.4711.4614.32
45420.623.6517.9720.623.6516.6730.843.6515.360.1211.2014.32
820.623.6517.9720.623.6516.6730.843.6515.360.0611.2014.32
1620.623.6517.9720.623.6516.6730.843.6515.360.5211.2014.32

Table IV. Comparative evaluations of algorithms for robustness under different noise levels.

Interference of Harmonics

During severe fault transients or transformer energization, the fault current contains both odd and even harmonics [6]. A composite test signal is generated, superimposing a primary DDC (τ=3\tau= 3 cycles) with harmonic combinations. The first case evaluates a heavily distorted signal containing 2nd (20% of the amplitude of the fundamental harmonic) and 4th (10%) harmonics. The second evaluates a spectrum containing 2nd (20%), 3rd (10%), and 4th (10%) harmonics simultaneously.

Under the proposed methodology, orthogonal sinusoids integrate to exactly zero over the fundamental window. By selecting an even carrier parameter (e.g., k=4,8,16k = 4, 8, 16), the algorithm rejects the investigated low-frequency harmonic components. As Table V shows, these prominent fault harmonics contribute strictly zero energy to the sliding projection integrals. Thus, the proposed method achieves a negligible 0.02% MO (matching the harmonic-free baseline) with a 14.58 ms settling time and isolates the DDC component regardless of harmonic severity.

Harmonic ContentFCDFTMethod [6]Method [18]Proposed Method
DistortionkkMO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)MO (%)trt_r (ms)tst_s (ms)
2nd (20%) & 4th (10%)419.793.3927.3419.793.3916.6726.353.3916.410.0211.9814.58
819.793.3927.3419.793.3916.6726.353.3916.410.0211.9814.58
1619.793.3927.3419.793.3916.6726.353.3916.410.0211.9814.58
2nd (20%), 3rd (10%), 4th (10%)419.793.1227.3419.793.1216.6727.173.1216.410.0212.2414.58
819.793.1227.3419.793.1216.6727.173.1216.410.0212.2414.58
1619.793.1227.3419.793.1216.6727.173.1216.410.0212.2414.58

Table V. Comparative performance under harmonic distortion (I0/I1=1I_0/I_1 = 1, τ=3\tau= 3 cycles).

Impact of Sampling Rate

To guarantee compatibility with a wide spectrum of commercial digital relays, the proposed method must remain stable across different sampling resolutions. The algorithm is evaluated at standardized sampling rates extending from a sparse 960 Hz (N=16N = 16 samples/cycle) up to 7680 Hz (N=128N = 128) [[36]].

The numerical results in Table VI confirm that the discrete characteristic root extraction remains well conditioned at all practical sampling frequencies, provided the modulation order obeys the Nyquist limit (k<N/2k < N/2). When the Nyquist condition is violated, the compensation becomes invalid (e.g., k≥8k \ge8 at 960 Hz). However, as long as the Nyquist condition is met (e.g., k=4k = 4 at 960 Hz, or k≤16k \le16 at 3840 Hz), the proposed method maintains a negligible overshoot (0.01%–0.09%) and fast settling (14.06–14.58 ms) with accurate estimation.

FsF_s (Hz)kkFCDFT MO (%)trt_r (ms)tst_s (ms)Method [6] MO (%)trt_r (ms)tst_s (ms)Method [18] MO (%)trt_r (ms)tst_s (ms)Proposed Method MO (%)trt_r (ms)tst_s (ms)
960 (N=16N = 16)418.773.1219.7918.773.1216.6729.273.1215.620.0911.4614.58
8––––––––––––
16––––––––––––
1920 (N=32N = 32)418.753.6519.2718.753.6516.6732.593.6514.060.0510.9414.06
818.753.6519.2718.753.6516.6732.593.6514.060.0510.9414.06
16––––––––––––
3840 (N=64N = 64)418.713.6527.3418.713.6516.6734.353.6515.360.0211.2014.32
818.713.6527.3418.713.6516.6734.353.6515.360.0211.2014.32
1618.713.6527.3418.713.6516.6734.353.6515.360.0211.2014.32
7680 (N=128N = 128)418.693.6527.2118.693.6516.6735.123.6516.020.0111.2014.32
818.693.6527.2118.693.6516.6735.123.6516.020.0111.2014.32
1618.693.6527.2118.693.6516.6735.123.6516.020.0111.2014.32

Table VI. Impact of sampling rate on single DDC estimation (I0/I1=1.0I_0/I_1 = 1.0, τ=3.0\tau= 3.0 cyc).

Sensitivity to Off-Nominal Frequency

During grid disturbances, such as multi-mode power swings or large load switching events, the system frequency can deviate from its nominal value. The frequency deviation is usually allowed in the range of 2-3% for a short period [[37]]. To evaluate this, the estimators were tested against static off-nominal frequencies (59.5 Hz and 60.5 Hz in Figure 4 and Figure 5) as well as a dynamic condition with continuous 3% linear frequency fluctuation (see Figure 6).

Impact of a static off-nominal frequency drop

Figure 4. Impact of a static off-nominal frequency drop (59.5 Hz) on estimation accuracy.

Impact of a static off-nominal frequency rise

Figure 5. Impact of a static off-nominal frequency rise (60.5 Hz) on estimation accuracy.

Impact of dynamic frequency variation

Figure 6. Impact of dynamic frequency variation (3% deviation) on estimation accuracy.

As shown in the Figure 4 to Figure 6, the proposed method is not sensitive to normal frequency variations in the grid and is able to reconstruct the fundamental harmonic even better than benchmarked methods.

Computational Complexity

The computational complexity and required number of samples of the evaluated phasor estimation algorithms are summarized in Table VII. All estimators employ an NN-point DFT for fundamental phasor estimation. While the standard FCDFT requires no DDC compensation, Method [6], Method [18], and the proposed method additionally perform high-frequency modulation-based processing to estimate or compensate the DDC component. Method [6] combines three successive outputs of one-cycle averaging filters applied to the original and modulated signals and therefore requires N+2N + 2 samples. Method [18] obtains the DDC information from NN-sample summations of the original and high-frequency-modulated signals and requires only one cycle (NN samples).

AlgorithmDDC extraction operationDFTAdditional nonlinear ops.Required number of samplesComplexity
FCDFT–NN-point–NNO(N)O(N)
Method [6]Two NN-sample averaging filters, three outputsNN-pointSquare rootN+2N + 2O(N)O(N)
Method [18]Two NN-sample sums (original and modulated)NN-point–NNO(N)O(N)
Proposed AlgorithmThree modulated NN-sample sliding projectionsNN-pointLog/expN+2N/MN + 2N/MO(N)O(N)

Table VII. Comparison of the computation burden and number of samples required for phasor estimation algorithms.

NN-sample summations of the original and high-frequency-modulated signals and requires only one cycle (NN samples). The proposed method uses three modulation-assisted sliding projections separated by ΔN=N/M\Delta N = N/M samples, spanning an observation buffer of ΔN/M\Delta N/M samples for parameter extraction (e.g., 80 samples or 1.25 fundamental cycles for N=64N = 64 and M=8M = 8). Once extracted, the DDC parameters are used to reconstruct and subtract the decaying offset across the active NN-sample DFT window, enabling the compensated phasor magnitude to enter the 5% settling band within one fundamental cycle (≈14\approx14 ms). Furthermore, because parameter updates occur every N/MN/M samples and reuse previously computed sliding projections, only one new projection is evaluated per sub-cycle shift. Although the parameter extraction and time-domain reconstruction involve logarithmic and exponential operations (whereas Method [6] employs an algebraic square-root calculation), all three DDC-compensated algorithms retain linear O(N)O(N) computational complexity because their dominant operations consist of finite-length summations, modulation, and DFT processing. Thus, the additional computational burden of the proposed method remains compatible with real-time implementation in digital protective relays [38].

Simulation-Based Analysis

The dynamic performance of the phasor-estimation methods is coded and evaluated using a Python-based model of a 230 kV, 60 Hz, 100 km transmission line supplied from two equivalent sources. The source impedances are derived from short-circuit capacities of 8000 MVA and 8500 MVA with an X/RX/R ratio of 6 (see Figure 7 for more details). The transmission line is represented using its positive- and zero-sequence series parameters. Vbase=230V_{\mathrm{base}} = 230 kV and Sbase=800S_{\mathrm{base}} = 800 MVA are selected for per unit conversion. A solid single-phase-to-ground (A-G) fault with zero fault resistance is applied at tf=200t_f = 200 ms.

Single-line diagram of the tested grid

Figure 7. Single-line diagram of the tested grid adapted from [27]

Two complementary evaluations are performed. First, a fault at 50% of the line is used to assess the transient magnitude-estimation performance of the different methods. Second, faults at 77% and 85% of the line are used to investigate their effect on the apparent-impedance trajectories of the distance relay. The relay is located at the Source-1 terminal, and its Zone 1 Mho characteristic is configured to cover 80% of the protected line. Thus, the 77% fault represents a boundary-adjacent internal fault, whereas the 85% fault represents a nearby external fault.

The 50% fault is used to quantify the transient tracking performance in terms of MOMO, rise time, and settling time. Table VIII summarizes the corresponding results for the FCDFT, Method [6], Method [18], and the proposed method with modulation orders k=4k = 4, 8, and 16.

MethodMOMO (%)trt_r (ms)tst_s (ms)
Full-cycle DFT16.04111.45837.760
Method [6]2.0169.37515.625
Method [18]0.00410.41714.583
Proposed (k∈{4,8,16}k \in\{4, 8, 16\})0.00113.80216.146

Table VIII. Transient performance for the A-G fault at 50% of the line.

As shown in Figure 8 and Table VIII, the conventional FCDFT is strongly affected by the DDC component and exhibits the largest transient deviation, with a MOMO of 16.041% and a settling time of 37.760 ms. Method [6] reduces the MOMO to 2.016% and provides the shortest rise time of 9.375 ms, with a settling time of 15.625 ms. Method [18] further limits the overshoot to 0.004% and provides the shortest settling time of 14.583 ms. The proposed method provides the smallest MOMO of 0.001% for all three modulation orders. Its settling time is 16.146 ms, which is slightly less than one fundamental cycle at 60 Hz. The identical results obtained for k=4k = 4, 8, and 16 indicate that, for the considered fault waveform, the modulation order has negligible influence on the transient-magnitude estimation performance.

Estimated fundamental-current magnitude for the A-G fault at 50% of the protected line

Figure 8. Estimated fundamental-current magnitude for the A-G fault at 50% of the protected line.

The influence of phasor-estimation errors on distance-relay operation is examined separately using faults close to the Zone 1 boundary. The 77% fault lies inside the 80% Zone 1 reach and is therefore used to assess dependability near the protection boundary. In contrast, the 85% fault lies immediately outside Zone 1 and is used to evaluate relay response against transient overreach.

For the 77% internal fault, the theoretical fault impedance lies close to the Zone 1 characteristic, making the relay decision particularly sensitive to transient phasor-estimation errors. As illustrated in Figure 9, the uncompensated FCDFT

Apparent-impedance trajectories for the internal A-G fault at 77% of the protected line

Figure 9. Apparent-impedance trajectories for the internal A-G fault at 77% of the protected line, close to the Zone 1 Mho boundary.

exhibits a relatively large transient loop around the expected fault impedance before convergence. Method [6] also produces noticeable transient excursions, whereas Method [18] approaches the expected operating point with reduced local fluctuation. In comparison, the proposed method produces the most confined trajectories, with the results for k=4k = 4, 8, and 16 closely overlapping around the expected 77% reach point. This behavior is particularly important for a boundary-adjacent internal fault, where excessive transient displacement can delay or destabilize the in-zone decision.

The 85% fault provides a complementary reliability test because its theoretical apparent impedance lies outside Zone 1. As shown in Figure 10, transient errors in the estimated current phasor displace the apparent-impedance trajectories during the initial fault period. The FCDFT exhibits a large transient loop extending toward and into the Zone 1 characteristic, indicating susceptibility to transient overreach. Method [6] and Method [18] reduce the local oscillation around the final operating point, although noticeable transient excursions remain. In contrast, the proposed method maintains tightly confined trajectories around the expected 85% reach point for all investigated modulation orders and remains outside the Zone 1 characteristic. This reduced transient displacement decreases the risk of transient overreach and improves Zone 1 discrimination for the investigated external fault.

Apparent-impedance trajectories for the external A-G fault at 85% of the protected line

Figure 10. Apparent-impedance trajectories for the external A-G fault at 85% of the protected line, outside the Zone 1 Mho boundary.

Conclusion

This paper proposed a modulation-assisted algorithm for fault current phasor estimation that effectively eliminates DDC offsets causing severe spectral leakage in conventional DFT. By modulating the signal with a high-order harmonic carrier, the algorithm isolates DDC offsets and utilizes a forward difference operator to dynamically track multiple DDC components as a single equivalent decaying signal. Extensive evaluations validated the algorithm’s accuracy, demonstrating a MO strictly bounded below 0.62% under complex double-DDC conditions and settling within one fundamental cycle (under 13.80 ms). Furthermore, the method maintained robust performance under severe 20 dB noise, limiting the MO to 2.47%. Ultimately, this approach guarantees fast, secure distance relay operations during complex Zone 1 grid faults.

Acknowledgments

The authors acknowledge the use of AI tools for English writing assistance, grammar checking, and mathematical derivation verification in the preparation of this manuscript.

References

References

  1. [1]Y. Guo, M. Kezunovic, and D. Chen, “Simplified algorithms for removal of the effect of exponentially decaying DC-offset on the fourier algorithm,” IEEE Transactions on Power Delivery, vol. 18, no. 3, pp. 711–717, 2003.DOI
  2. [2]S. H. Kang, D.-G. Lee, S.-R. Nam, P. A. Crossley, and Y.-C. Kang, “Fourier transform-based modified phasor estimation method immune to the effect of the DC offsets,” IEEE Transactions on Power Delivery, vol. 24, no. 3, pp. 1104–1111, 2009.
  3. [3]S. Mohammadi, A. Mahmoudi, S. Kahourzade, A. Yazdani, and G. M. Shafullah, “Decaying DC offset current mitigation in phasor estimation applications: A review,” Energies, vol. 15, no. 14, p. 5260, 2022.DOI
  4. [4]S. Mohammadi, N. Rezaei, A. Mahmoudi et al., “A novel analytical method for dc offset mitigation enhancing dft phasor estimation,” Electric Power Systems Research, vol. 209, p. 108036, 2022.DOI
  5. [5]S. Mohammadi and W. Su, “Symbolicphasor: Power system phasor estimation via deep symbolic regression,” arXiv preprint arXiv:2608.08552, 2026.
  6. [6]S. Afrandideh and F. Haghjoo, “A DFT-based phasor estimation method robust to primary and secondary decaying DC components,” Electric Power Systems Research, vol. 208, p. 107907, 2022.
  7. [7]S. Jamali and H. Zamani, “Removal of system and ct decaying dc component in fault signal using selective interval integration,” IEEE Transactions on Power Delivery, vol. 37, no. 2, pp. 905–912, 2022.DOI
  8. [8]G. Benmouyal, “Removal of DC-offset in current waveforms using digital mimetic filtering,” IEEE Transactions on Power Delivery, vol. 10, no. 2, pp. 621–630, 1995.DOI
  9. [9]C.-S. Yu, “A discrete fourier transform-based adaptive mimic phasor estimator for distance relaying applications,” IEEE Transactions on Power delivery, vol. 21, no. 4, pp. 1836–1846, 2006.DOI
  10. [10]Z. Jiang, S. Xiao, and P. Liu, “A modified empirical mode decomposition filtering-based adaptive phasor estimation algorithm for removal of exponentially decaying dc offset,” IEEE transactions on power delivery, vol. 29, no. 3, pp. 1326–1334, 2014.
  11. [11]M. Pazoki, “A new dc-offset removal method for distance-relaying application using intrinsic time-scale decomposition,” IEEE Transactions on Power Delivery, vol. 33, no. 2, pp. 971–980, 2017.DOI
  12. [12]J. Ren and M. Kezunovic, “Elimination of DC offset in accurate phasor estimation using recursive wavelet transform,” in 2009 IEEE Bucharest PowerTech, 2009, pp. 1–5.
  13. [13]B. Jafarpisheh, S. M. Madani, and F. Parvaresh, “Phasor estimation algorithm based on complex frequency filters for digital relaying,” IEEE Transactions on Instrumentation and Measurement, vol. 67, no. 3, pp. 582–592, 2018.DOI
  14. [14]K. M. Silva and F. A. Nascimento, “Modified dft-based phasor estimation algorithms for numerical relay applications,” IEEE transactions on power delivery, vol. 33, no. 3, pp. 1165–1173, 2017.
  15. [15]K. N. A. Al-Tallq, G. A. Putrus, and X. Li, “Online algorithm for removal of decaying DC-offset from phasor estimates,” Electric Power Systems Research, vol. 81, no. 12, pp. 2209–2218, 2011.
  16. [16]A. A. Abdoos, M. K. Ghataki, and J. Sadeh, “Accurate and fast DC offset removal method for digital relaying schemes,” IET Generation, Transmission & Distribution, vol. 10, no. 8, pp. 1877–1885, 2016.DOI
  17. [17]H. Hajizadeh, S.-A. Ahmadi, and M. Sanaye-Pasand, “An analytical fast decaying dc mitigation method for digital relaying applications,” IEEE Transactions on Power Delivery, vol. 36, no. 6, pp. 3529–3537, 2020.DOI
  18. [18]B. Jafarpisheh, S. M. Madani, and S. Mohammadh Shahrestani, “A new dft-based phasor estimation algorithm using high-frequency modulation,” IEEE Transactions on Power Delivery, vol. 32, no. 6, pp. 2416–2423, 2017.DOI
  19. [19]Z. Liu, Y. Zou, H. Zhao, J. Han, and Y. Liu, “An analytical phasor estimation method for transient currents considering double decaying dc offsets,” IET Generation, Transmission & Distribution, vol. 20, no. 1, p. e70309, 2026.
  20. [20]B. R. Kumar, A. Mohapatra, and S. Chakrabarti, “A novel sub-cycle-based method for estimation of decaying dc component and fundamental phasor,” IEEE Transactions on Instrumentation and Measurement, vol. 70, pp. 1–10, 2021.DOI
  21. [21]P. Jafarian and M. Sanaye-Pasand, “Weighted least error squares based variable window phasor estimator for distance relaying application,” IET generation, transmission & distribution, vol. 5, no. 3, pp. 298–306, 2011.DOI
  22. [22]J. K. H. Hwang, “Least error squares phasor estimation with identification of a decaying dc component,” IET Generation, Transmission & Distribution, vol. 12, no. 7, pp. 1486–1492, 2018.DOI
  23. [23]A. Mahari, M. Sanaye-Pasand, and S. M. Hashemi, “Adaptive phasor estimation algorithm to enhance numerical distance protection,” IET Generation, Transmission & Distribution, vol. 11, no. 5, pp. 1170–1178, 2017.DOI
  24. [24]M. Sachdev and M. Nagpal, “A recursive least error squares algorithm for power system relaying and measurement applications,” IEEE Transactions on Power Delivery, vol. 6, no. 3, pp. 1008–1015, 1991.DOI
  25. [25]M. Tajdinian, M. Z. Jahromi, K. Mohseni, and S. M. Kouhshari, “An analytical approach for removal of decaying dc component considering frequency deviation,” Electric Power Systems Research, vol. 130, pp. 208–219, 2016.
  26. [26]P. D. Acherlkar and B. K. Panigrahi, “Assessment of dc offset in fault current signal for accurate phasor estimation considering current transformer response,” IET Science, Measurement & Technology, vol. 13, no. 3, pp. 403–408, 2019.
  27. [27]A. Haji-Mohammadi and M. Sanaye-Pasand, “Novel method for decaying dc component removal based on solving the differential equations,” IEEE Transactions on Power Delivery, 2024.
  28. [28]M. Parpaei, H. Askariyan Abyaneh, and F. Razavi, “An innovative method to eliminate multiple exponentially decaying dc components based on the discrete fourier transform in the numerical distance relay,” IET Generation, Transmission & Distribution, vol. 16, no. 18, pp. 3731–3743, 2022.DOI
  29. [29]J. K. Hwang, C. K. Song, and M. G. Jeong, “Dft-based phasor estimation for removal of the effect of multiple dc components,” IEEE Transactions on Power Delivery, vol. 33, no. 6, pp. 2901–2909, 2018.DOI
  30. [30]M. Tajdinian, A. R. Seifi, and M. Allahbakhshi, “Half-cycle method for exponentially dc components elimination applicable in phasor estimation,” IET Science, Measurement & Technology, vol. 11, no. 8, pp. 1032–1042, 2017.DOI
  31. [31]M. Allahbakhshi, M. Tajdinian, A. R. Seifi, M. Zareian Jahromi, and A. Bagheri, “Hybrid approach for immunisation of dft-based phasor estimation method against decaying dc components,” IET Science, Measurement & Technology, vol. 13, no. 2, pp. 238–246, 2019.DOI
  32. [32]S. M. Brahma, P. L. De Leon, and R. G. Kavasseri, “Investigating the option of removing the antialiasing filter from digital relays,” IEEE Transactions on Power Delivery, vol. 24, no. 4, pp. 1864–1868, 2009.DOI
  33. [33]Å. Björck and V. Pereyra, “Solution of vandermonde systems of equations,” Mathematics of Computation, vol. 24, no. 112, pp. 893–903, 1970.DOI
  34. [34]H. Yu, Z. Jin, H. Zhang, and V. Terzija, “A phasor estimation algorithm robust to decaying dc component,” IEEE Transactions on Power Delivery, vol. 37, no. 2, pp. 860–870, 2021.DOI
  35. [35]H. Dashti, M. Sanaye-Pasand, and M. Davarpanah, “Fast and reliable ct saturation detection using a combined method,” IEEE Transactions on Power Delivery, vol. 24, no. 3, pp. 1037–1044, 2009.
  36. [36]S. A. Saleh, E. Okzop, A. Al-Drura, T. Hill, J. Meng, and M. E. Valdes, “On the assessment of sampling rate impacts on responses of digital protective relays,” IEEE Transactions on Industry Applications, vol. 59, no. 5, pp. 5420–5431, 2023.
  37. [37]C. Luo, H. G. Far, H. Banakar, P.-K. Keung, and B.-T. Ooi, “Estimation of wind penetration as limited by frequency deviation,” in 2006 IEEE Power Engineering Society General Meeting. IEEE, 2006, pp. 8–pp.
  38. [38]A. G. Phadke and J. S. Thorp, “Computer relaying for power systems,” New York, NY, 2009.

Paper details

vlnc:W_urqm43ym
Version
v1 · latest
Published
Fresh — added to the Hub within the last 30 days
Added
License
CC BY 4.0
Usage

views · 0

downloads · 0

A view counts once per browser per day, a download each time the PDF is requested.

  • Engineering

AI tools

View statement
Looking for related papers…
Contents